20--Industrial Sanitation and Personnel Facilities
contaminants (a) those which usually have no toxicologic effect, but may give an unde sirable taste or appearance to the water, and (b) those which constitute a health hazard and, if present, are grounds for rejecting the water supply Standards under consideration for limiting mercury as a contaminant, pro pose values between 0 002 and 0 005 mg/L (See EPA reference at end of chapter) A limit of 0 5 mgAg of fish is used currently
Criteria for asbestos fibers, if present as a discharge from an industrial process m the surrounding area, may be less than those present in already treated or natural water Information on proposed fibers testing and standards are available from the American Waterworks Assn , see References
Temperature cntena which affect the lim iting concentrations of fluoride m drinking water are given m Table 20-B Other factors influencing the limiting concentrations of these contaminants, particularly m combination with other substances, are given in the USPHS Drinking Water Standards, published in 42 C F R , part 72 These Standards also serve as a guide to radioactive substances m water supplies
if the degree of contamination from the substances previously discussed is within rec ommended limits, the water supply source may be used, provided its bacteriological quality is acceptable Standards for bacterio logical quality are specified in the USPHS Manual of Recommended Water-Sanitation Practice
The equipment necessary to treat water and make it potable depends on the degree of contamination and the likelihood that the source will become more heavily contami nated later These factors can be evaluated only on the basis of a thorough sanitary survey of the water source Such a survey will determine not only the type of treatment necessary, but also the nature and fiequency of periodic laboratory tests of the source wa ter and the treated water (Fig 20-1)
Wells
The safest source of water is often a drilled well whose intake is well below the water table Such wells show a reliable yield and are reasonably free from bacterial contamina tion and finely suspended fibers If both well
and city water are used, there should be no cross-connection between the two systems Be sure to check the local code
The wellhead should be carefully located away from sewage lines, septic tanks, and sewage drainage fields or process waste dis posal systems The following distances are often considered adequate for separation sewers, pit pnvies, and septic tanks, 50 ft, seepage pits and disposal fields, 100 ft, cess pools, 150 ft Process waste disposal systems require special consideration As soil and drainage conditions vary from one location to another, approval by local health authorities is recommended
The USPHS Manual of Individual Water Supply Systems recommends that the casing for such wells be made of wrought iron or steel with threaded couplings or welded joints "Stovepipe" or sheet metal casings are not recommended
To prevent contamination of the under ground water by seepage of surface waters, the space between the casing and the sur rounding area should be sealed with a cement grout to a minimum depth of 10 ft below the finished ground level or floor As a further precaution, the casing should be grout-sealed to the lowest impervious stratum it passes through
The well casing should extend 6 in above the pump platform, which should be of rein forced, waterproof concrete at least 4 in thick and continuous with the grout seal which sur rounds the well casing The platform should be designed so that water spilled at the well head will drain away from the casing The joint between the casing and the concrete pump platform should be sealed with an as phalt caulking compound
The top of the well casing should be at least 2 ft above the highest known floodwater mark The pump should be self-pruning and designed so that it makes a watertight seal with the well casing The wellhead should not be covered over by paving or other ma terial which would make access difficult
Both submersible and turbine pumps must be considered Submersibles are located in the well and do not requne a pumphouse
A safety factor is provided by two wells and two pumps An automatic alternator can take effect if either unit fails