Document DXjRrQZaEGJVqRbK1qjxXoMN
Compliance Evaluation Inspection Report Kyle Grocery June 2024
Submitted to: U.S. ENVIRONMENTAL PROTECTION AGENCY
REGION 8 1595 Wynkoop St. Denver, CO 80202
Submitted by: Eastern Research Group. 14555 Avion Parkway, Suite 200
Chantilly, VA 20151 EPA Contract No. 68HERC21D0007
Task Order 68HERC23F0460 COMPLIANCE EVALUATION INSPECTION REPORT
Date of Report:
June 20, 2024
Date and Time of Inspection: April 29, 2024, at 10:30 am MST
Weather:
Sunny and clear, 65 Fahrenheit
Facility Contact/Owner:
Owner Address:
545 Main St Kyle, SD 57752
Facility Address:
545 Main St Kyle, SD 57752
Facility Phone:
Facility ID Number:
4070021
Reason for Inspection:
Compliance Inspection
Inspector(s):
, ERG (Lead) , ERG
, Oglala Sioux Tribe UST Coordinator
Kyle Grocery CEI Report
ii
June 2024
TABLE OF CONTENTS
1. NARRATIVE ..................................................................................................................... 1 2. SUMMARY........................................................................................................................ 4
ATTACHMENTS
ATTACHMENT A: ATTACHMENT B: ATTACHMENT C: ATTACHMENT D: ATTACHMENT E: ATTACHMENT F: ATTACHMENT G: ATTACHMENT H: ATTACHMENT I: ATTACHMENT J:
EPA REGION 8 UST COMPLIANCE CHECKLIST PHOTOGRAPH LOG TANK LEAK DETECTION RECORDS & INVENTORY PIPING LEAK DETECTION RECORDS & ATG CERTIFICATION SPILL & OVERFILL PREVENTION TESTING RECORDS CATHODIC PROTECTION TESTING RECORDS OPERATOR TRAINING RECORDS WALKTHROUGH INSPECTION RECORDS FINANCIAL ASSURANCE DOCUMENTATION NOTICE OF INSPECTION
Kyle Grocery CEI Report
iii
June 2024
1. NARRATIVE
The Region 8 (R8) office of the Environmental Protection Agency (EPA) requested multiple facilities be inspected on tribal lands. Eastern Research Group (ERG) under EPA's Contract No. 68HERC21D0007, Task Order 68HERC23F0460, provided assistance to EPA in preparing for, conducting the inspection, and preparing this inspection report. ERG inspected the Kyle Grocery facility in Kyle, South Dakota on April 29, 2024. The facility was last inspected on June 15, 2021.
Mr.
, contract inspector, contacted Ms.
, representative of Kyle Grocery, on March
27, 2024, to notify the facility about the inspection prior to the inspection team's arrival. The
inspection verified compliance with the federal underground storage tank (UST) requirements of
Resource Conservation and Recovery Act (RCRA) Subtitle I under 40 CFR Part 280.
Initially, Mr.
and Mr.
arrived at the facility to begin the inspection and
introduced themselves to
and
, representatives for Kyle Grocery. Mr.
provided an in-brief and notified them that Mr.
had travel delays, and he would
return later in the day to close out the inspection. Mr.
and Mr.
gathered
records, interviewed Mr.
and Mr. , and conducted a walkthrough of the site
including access ports for the UST. Mr.
and Mr.
departed at approximately
12:30 pm and notified Kyle Grocery that they would return with Mr.
later in the day. At
approximately 3:20 pm, the inspection team
returned to Kyle Grocery. Mr.
stated he was a contract inspector for EPA and presented
his credentials. The inspection team finished gathering records and conducting the walkthrough
at that time. Mr.
concluded with an exit brief and had Mr.
sign the Notice of
Inspection. Mr.
took photographs during the inspection.
UST System Description
The Kyle Grocery facility, located at 545 Main St in Kyle, SD, has one UST. According to the previous EPA inspection report and observations made during the inspection, the UST was constructed in 1994 with single-walled STI-P3 construction and single-walled steel piping. The UST has a 9,500-gallon capacity and holds regular unleaded gasoline. The dispensing system for the UST is pressurized piping. The inspection team completed an EPA Region 8 UST Compliance Inspection Checklist for the UST while on site which is included in Attachment A. Photograph #4 in Attachment B shows an overview of the UST.
UST System Records
The listing of documents reviewed for the Kyle Grocery inspection included the following:
1. UST Leak Detection Records and Inventory 2. Tank Gauging and Line Leak Detector Test Records 3. Spill and Overfill Protection Test Records 4. Cathodic Protection Test Records 5. Operator Training Certificates 6. Walkthrough Inspection Records 7. Financial Assurance Records
Kyle Grocery CEI Report
1
June 2024
The facility maintains all records on site. Mr. the inspection.
provided the records for the UST during
Tank Release Detection
Releases from the tank are detected by a Gilbarco EMC monitoring system and associated intank probe that conducts automatic tank gauging (ATG) of the tank. Attachment C contains a compilation of the ATG static leak test results printed from the ATG system for the previous 12 months. The tank had passing leak detection records for each of the months. Attachment C also includes a tank inventory from the day of the inspection. Grimms Pump and Industrial Supply tested the performance of the ATG probe in December 2023. Attachment D includes the passing test record for the ATG system.
Piping Release Detection
The UST was installed with pressurized single-walled steel piping. The submersible turbine pump (STP) is equipped with a mechanical line leak detector (LLD), and Kyle Grocery conducts annual line tightness testing for piping release detection. Grimms Pump and Industrial Supply tested the LLD and conducted line tightness testing in December 2023. Attachment D includes the passing test records for the LLD test and the line tightness test. Photograph #1 in Attachment B shows the STP observed during the inspection.
Spill/Overfill Prevention
The fill pipe for the UST has a spill bucket surrounding the pipe, and Kyle Grocery has an overfill alarm for overfill prevention. Photographs #2 and #3 in Attachment B show the fill port for the UST. The spill bucket and drop tube appeared in good condition. Grimms Pump and Industrial Supply conducted hydrostatic testing on the spill bucket and performance testing on the overfill alarm in December 2023. Attachment E shows the passing test records for the spill and overfill prevention equipment.
Corrosion Protection
The tank is single-walled STI-P3 construction, and cathodic protection testing records were provided from 2018 and 2021. The UST passed cathodic protection tests in 2018, but the piping under the dispenser failed the tests in June 2021. Repairs were made, and then in September 2021, the tank was retested and passed. Attachment F includes the cathodic protection testing records from 2018 and 2021.
Operator Training
Kyle Grocery has a Class A operator, Class B operator, and seven Class C operators trained. The
inspection team reviewed training certificates onsite. The Class A operator is
, and
the Class B operator is
. Appendix G includes an example training certificate for
each operator class.
Kyle Grocery CEI Report
2
June 2024
Walkthrough Inspections
Kyle Grocery completed monthly and annual walkthrough inspection records using EPA R8 checklists. Monthly walkthrough records were available for January 2022 to April 2024, and annual walkthrough records were available for 2021 to 2023 Attachment H includes the monthly and annual walkthrough inspection records collected on site.
Financial Assurance
Kyle Grocery is registered with the state of South Dakota and covered under the state trust fund,
which covers facilities using a fee on each gallon of fuel sold. Mr.
also provided a
general commercial liability insurance policy for Kyle Grocery, which has a limit of $1,000,000
per occurrence. Attachment I includes the notification of inclusion in the state trust fund as well
as a copy of the commercial insurance policy.
Physical Inspection
During the site visit, the inspection team reviewed documents on site and observed the fill ports,
the STP, the dispensers, and the ATG monitoring interface for the UST on site. Photograph #5 in
Attachment B shows the interface for the Gilbarco EMC ATG system. Attachment C includes an
inventory report for the USTs that Mr.
had printed during the inspection to verify
operation. The inspection team also observed the spill bucket and fill pipe for the UST. The spill
bucket was dry and in good condition, with some moderate corrosion, at the time of the
inspection (see Photographs #2 and #3, Attachment B). The tank also had an access port for the
STP, and no issues were noted (see Photograph #1, Attachment B). There were two double-sided
dispensers on site. Mr.
inspected dispenser 3/4 and did not observe signs of leaks from
the dispenser at the time of the inspection. The inspection team did observe the ATG probe, and
no issues were noted. The inspection team asked Mr.
about the location of the overfill
alarm, and Mr.
stated that the overfill alarm is located inside the store building.
No monitoring wells were observed at the tank field during the inspection. The vent line is located adjacent to the tank, and no obstructions or concerns were noted for the vent line at the time of the inspection.