Heating VentiiiAting Air Conditioning Guide 1939
Combustion and Fuels
decrease in the size of the fuel pieces, with increase in the depth of
fuel bed, and with increase in the area of the firepot; the ratio als<y!|
increases with increase in rate of burning.
i*
Size of the fuel is a very important factor in fixing the quantity 0f
secondary air required for non-caking coals. With caking coals it is not
so important because small pieces fuse together and form large lumps
Fortunately a smaller size fuel gives more resistance to air flow through! the fuel bed arid thus automatically causes a larger draft above the fUej
bed, which draws in more secondary air through the same slot openings
In spite of this, a small size fuel requires a larger opening of the door 51 slots; for a certain size for each fuel no slot opening is required, and for!
larger sizes too much excess air gets through the fuel bed.
^ '
bweislltcwoohlictheregdausceessbethloewsmthoekiegntoitioanmpinoimntu, man.d pTrooovemhucahrmfuKr^f^/'r
beneficial. The following suggestions will be helpful:
U lnsteaci of
hal1f.opInencoalldl twheattihmeer,. with high combustion rates, the seconda*rTMy air daamper should tie sho2u. ldInbevecrloysmedildallwtehaethtiemr,ew. ith a very low comubusscti.on rate, the second. ary air damper sho3u. ldFober tinemanpeinrateturrmesedbiaetewepeonsitvioenry. mild and ver3v midu' nn,e. s.econd, ary air damper one4.hoFuorr. ordinary house operation, secondary air is needed alfter e,,ac,h fciring f,or about
In the field of domestic heating the use of secondary air in the com bustion of oil is generally restricted to the larger semi-commercial tvoes of oil burners used m large heating boilers. This factor is discussed in
Chapter 11, Automatic Fuel Burning Equipment. The air that is supplied around the flame in a domestic heating gas
bbuyrnneartuisraclodnsraidfetreadctaiosns,ecthoendnaereydaifro. r Apsroipt eisr.ddrraawftncionntotrothl eisapeoviiidaenncet
Fig. 3. Relative Amount of Fire Door Slot Opening Required in a Given Furnace to Give Equally Good Combustion for High Temperature Coke of Various Sizes When Burned at Various Rates
It is impossible to establish a single rule for the correct slot opening for all types and sizes of fuels and for all rates of burning. Furthermore, the effect, of slot opening is dependent on whether the ashpit damper is open or closed. It is better to have too much than too little secondary air; the opening is too small if there is a puff of flame when the firing door is opened.
The relationship of the slot opening, for a domestic furnace, to the size of coke and the rate of burning is shown in Fig. 33. These openings are with the ashpit damper wide open, and would be less if the available draft permits of its being partly closed. The same openings are satisfactory for. anthracite. -
Bituminous coals require a large amount of secondary air during the period subsequent to a firing in order to consume the gases and to reduce the smoke. The smoke produced is a good indicator, and that opening is
*From Bureau of Mines Report of Investigations, No. 2980.
170
Draft Requirements
The draft required to effect a given rate of burning the fuel as measured at the smokehood is dependent on the following factors:
1. Kind and size of fuel. 2. Combustion rate per square foot of grate area per hour.
3. Thickness of fuel bed. 4. Type and amount of ash and clinker accumulation. 5. Amount of excess air present in the gases. 6. Resistance offered by the boiler passes to the flow of the gases. 7. Accumulation of soot in the passes.
Insufficient draft will necessitate additional manipulation of the fuel bed and more frequent cleanings to keep its resistance down. Insufficient draft also restricts the control by adjustment of the dampers.
The quantity of excess air present has a marked affect on the draft required to produce a given rate of burning. If the excess is caused by holes in the fuel bed or an extremely thin fuel bed it is often possible to produce a higher rate of burning by increasing the thickness of the bed. The thickness of the fuel bed should not, however, be increased too much because-the increased draft resistance will reduce the rate of primary air supply and the rate of burning.
DRAFT REGULATION
Because of the varying heating load demands present in most instal lations it is necessary to vary the rate of fuel burning. The maintenance of the proper air supply for the various rates of burning is accomplished by regulation of the drafts. Correct and incorrect methods of draft regulation are shown in Fig. 4. The air enters through the ashpit, firing door and by leaks in the setting, whereas the gases leave only through the up-take. By throttling the gases with the damper in the up-take all the
171