CHAPTER 42
size motor provided to prevent overloading of the fan motor
as the air flow is`throttled.
'.'j.'j..'.,"
Another commonly used method of head pressure control-is
to modulate the active condensing surface. This is accom
plished by filling a portion of the condenser with refrigerant,
and thus rendering it inactive. ..Several methods now in'use
are .based on this principle.. The 'modulated bypats method
winch .was introduced. first (US. jPateiit No. 2;564,310) is
illustrated in Fig.`20.'An'outlet pressure-actuated modulating
valve W is installed in a'bypass'between the condenser inlet
and outlet. At iow, receiver pressures, the valve opens and
permits discharge vapor to flow: through the bypass to the
receiver, restricting drainage of'liquid refrigerant from the
condenser so as to flood the condenser; The quantity of by
passed' discharge vapor'is adjusted by the valve which re
sponds to receiver.pressure.'. VT~'
Modulated bypass control may,also be accomplished by use
of a three-way valve in the liquid return line. This valve con
trols the amount of hot gas bypass from the hot gas,line to the
return line, leaving the;condenser, in response to ^condenser
pressure-(Fig.'21)! x v.
................
In the heat exchanger method shown in Fig. 22, the Hquid
return line from the condenser to the receiver is heated by dis
charge vapor at lo'wer than'norinal head pressures; vaporisa
tion of liquid in tfee return:Iine causes the condenser to flood;
When the head'pressure is normal,'the liquid'side of the'heat
exchanger 'it bypassed through- a' pressiire: regulafiiig'yfllve
responsive to iixlet pressure;, This pressure'r^ulatihg 'valve
modulates flow'at intermediate condititins to proportion*the
liquid'flow between the bypass and the heat'exchanger;'r'"';
V The liquid throttling method is'similar to the heat exchanger
method'except tKatit omitsthe1 heat exchanger and
tutes'an"open- bypass, from the-condenser discharge'to'the receiver; inlet, which'contains;a' check; valve (Fig.'*23).l'TKe
pressure regulating valve in the' liqtiid'return' line from the
condensertd the receiver'opens on a rise in'condenser 'pressure
and'throttles on a drop in condenser pressure,' forcing the
1965 Guide And Data Book
check valve to open so that.dischaige gas is bypassed to the
receiver, thereby causing flooding of the condenser.
The control methods described maintain sufficient head
pressure for proper expansion valve operation. On off-cycles
with low outdoor,ambients, the refrigerant will migrate from
tjm;evaporator and-receiver and condense in the cokicon-
dfJiser. The system presure will'drop and may correspond to
the outdoor temperature. On startup, insufficient feeding of
liquid refrigerant to the evaporator due to low head pressure
will result in cycling of the compressor until the suction pr^~
sure reachee'an operating level above the'eettirig of the low
pressurestat. At extremely low "outdoor temperature, the
pressure in the system may be below the cutrin point of the
low1 pressuiestat and the' compressor will'not' start/ This
difficulty is solved by either of two methods': (1) bypaimng the
low pressure switch bri startup, or (2)` use of the condenser
isolation method bfcOhtroL''"
; `;
,1 On. system 'startup, a time delay relay( may be'-ueed to
bypass.'the low pressure switch for'a'period of approximately three, minutes to permit' the' brad pressure - to' bund up, and
pennhcompresaoroperation.- .. U [;
2.. The condm*er isolation method adds to,the modulated bypass
of Pig. 20 an inlet pressure regulating valve R in the the,discharge
line'(Fig. 24).'Valve R is dosed during the off^cyde to isolate the
cold condenser' from the'evaporator and thereby prevent migra
tion of refrigemat vapor from: the evaporator to the condenser.
A.check.valye jC attthe receiver inlet prevents.liquid migration
from the receiver to. the.condenser so that , receiver pressure is
substantially unaffected during the off-cycle! When the primary
control starts the compressor; Bypass valve'W opens'and permits
head;,pressure to act-directly on ;the receiver, while; valve R
prevents any flow, to the condenser; until the receiver pressure
w raised to.the control point* Valves R, W, and C are combined
into'oneassembly.'
....................
. ^IWben.'head .pressure control of the-flooding: type,- or air-
side control where,-the :liquid temperature 'from 'the con
denser; may. be lower-.than-the[ evaporator temperature, is
used, / a: non-condensable,-.- charged. thermostatic >expansion
yalye. must.be-used.--ThiSiprevents erratic'operation of lthe
expansion valve due:to condensation, of -the:'thermal .bulb
charge on the head of the expansion'valve.''
-
Condensers.
<697,
INSTALLATION AND MAINTENANCE/ to S
The and maintenance of remote unit condensers
require tittle labor because of their relatively-simpledesign.
The abynf* of water and sewer connections and .the ample
electrical hookup make it possible to complete an installation
without subcontractors. Remote condensers, are located at
any-desired distance from thercompressor, either, indoors-or
outdoors. They may be located far. above orj below ,the level
of the compressor. Various considerations relating,to,installs-;
tfon find matntennjiftft follow.
-. '
- - Indoor tiftil condensers. Where unit condensers are located
^doora, the warm discharge air must be conducted to the out
doors. Ao outdoor-air intake opening near the condenser is pro
vided, and may be equipped with shutters. Indoor condensers
w>n be utilized for space heating'during' the winter and for
ventflatkmdaring the summer'. (See Fig. 25.)`
Outdoor installation. In outdoor installations of vertical face
condensers, prevailing winds'ahofild blow'towards the air intake,
dr discharge shieldsehould be'used to deflect opposing winds.'
Piping.'Piping practice with linit'condensers is identical with
that' established by experience with other types of'remote'con
densers. Discharge piping should be sized for a total pressure drop
equivalent .to 2 F deg .saturated temperature-drop. For aatb:
factory'o3 return, the gas velocity in vertical risers shquld.be in
ocebrdance'witb the'recommendations in Chapter,77 of thel984
Guide And Data Boos. To minimi** transmission of compressor
vibratioh'to-.the.piping, run-the suction and'discharge, lines at
logrt g pipe diameters m each of three directions before reaching
the first point of support. In this manner, the piping can absorb
the vibration without being overstressed.'Oil separators are'used
in the hot gas line from the-compressor in systems having ex
tensive pipe lines, especially with unloading type compressors or
with numerous evaporators. The oil separator must be installed
in conjunction with a check valve at its outlet; otherwise, it fills
with liquid refrigerant during shut down,' resulting in drainage
of the " refrigerant to the compressor crankcase With' nuisance
trip-outa on the oil safety switch on start up. Properpiping de
sign often eliminates the need for oil separators.
, i.
"'Discharge'piping should be well supported without .transmit
ting vibration to the building. A muffler in the discharge line may-
be used to prevent noise due to refrigerant pulsation, particularly
with high speed compressors.
Thermal expansions. Long discharge mains may undergo con
siderable thennal expanaion and contraction due to temperature
changes. Discharge piping must therefore be designed so that it
can move without damage to itself or the condenser. Branch lines
from the discharge main to individual condensers should be laid
off with offsets in accordance with standard piping practice.
Receiver. Unit condensers may be equipped with built-in re
ceivers, or the receiver may be separate and installed at a distance
from the condenser. Certain system designs, particularly, those
with'capillary tubes, function without any receiver. If the receiver,
is located in a 'comparatively 'wknn'ambient' temperature,''the
liquid drain line from the condenser to the receiver should be sized
for a liquid velocity of 100 fprh for gravity drainage and venting to
the condenser. The receiver should oe equipped with a purge valve
and sight glass.
,. ,
' Maintenance. Relubrication' of ,fan motor and fail' bearings
nhi-Mild be scheduled from once every six months to booe every
year, depending on location.-Adjustment of belt .tension may-be
necessary after installation and.at yearly intervals. Industrial re-\
frigeratioh experience indicates that the maintenance cast of air
cooled condensing equipment is only 25 percent of that of water-
cooled-equipment, while' the capacity foes due to fouling with
increased age is less with'air-cooled condensing equipment than
with wet' condensing equipment: ...
......... - .-
Unit condensers are usually in locations that are relatively free
of dust or dirt. In dirty locations, the condenser coil may require
periodic removal of lint or leaves, either with a long bristle bnish,
steam, or compressed air. A cleaning solution will be required to
remove grease. Indoor condensers in dusty locations such as
textile trulls or supermarkets should be equipped with washable
filters:
PART III: EVAPORATIVE CONDENSERS
The !term evaporative condenser is applied to equipment in
truding a coil with its inner surface condensing refrigerant
and its outer surface wetted* with water and,exposed.to a
moving air stream for the purpose of rejecting heat to it,
principally by evaporation; Fig. 26 shows-Lypical arrange^
menta of components.
...
Coils
.'
Coils are generally fabricated from copper tube, steel tube,
or iron pipe, in multiple passes and circuits...'When ferrous
materials are used, they are'.protected externally, generally
by hot-dip galvanizing.
Extended external-finned surface is sometimes added, al
though it is not so essential as with air-cooled condensers, due
to the higher heat transfer rates obtained on the sir side of
the evaporative condenser.
The coil dprign should be such as to provide sustained per
formance under fouling water conditions and should be
accessible for cleaning.' . r
_,
Coil Wetting Means
Coil wetting is usually accomplished by a recirculating sys tem consisting of a sump, a pump, and a distributor.
The sump catches the drainage off the;coiL The correct operating level is maintained by a float valve positioned to admit make-up water'above the maximum water level at tainable in the sump (a water supply sanitation requirement). Overflow and cleanout drains are supplied. '
Nozzles or pans are commonly used'as distributors to pro vide thorough wetting of the coil:'Nozzles provide greater atomization and require higher pump heads, but permit
Rg.22.. ^.Condenser; Flooding by^theiNeat Exchanger - Method
Rg.023
Modulated' Condenser'"'Rooming' by the - -Liquid ThrottfingMethod*
Rg. 24 .... Condenser Control-by; the Isolation-Method