Document DM60YXjkrLevpxNzMkr4m7EJM
Specialties, Heating
Wright-Austin Co.
317 West Woodbridge St., Detroit, Mich.
PRODUCTS--Steam Traps, Strainers, Air Traps, Steam and Oil Separators, Compressed Air Purifiers, Exhaust Heads, Boiler Feeders, Alarm Water Columns, Water Gauges, Trycocks.
"Airxpel" Bucket Type Steam Traps
Are "double duty1' traps, because they automatically discharge both air and condensate.
At left is illustrated the "Baby" Airxpel, a new streamline body design, which adds at tractiveness to the installation. Has the handiest type of pipe connection for radiation, etc..
The Cub sizes are made in in., in., 1 in. Especially suitable for in dividual unit drainage on heating and process equip ment.
Also three "Master" sizes XA in. to 2 in., for general service.
"Emergency" Float Type Steam Trap
Three valve trap with large capacity at high pressures. An ex ceptionally reliable trap for use in inac cessible places.
Air Relief Trap
For relieving air from forced circulation hot water heating systems, water supply lines, closed tanks, receivers, pumps, etc.
tuway strainer
May be used two ways-- as a straight-way or angle s| strainer, in either hori-J zontal or vertical pipe' line, because it has the, choice of two inlets at rightanglestoone another.
For cleaning, flush through blow-off connection, or remove screen by unscrewing bottom plug.
Boiler Feeder
"Combination" Stc
Float Type with internal thermo static air bypass and strainer. A modernly designed and very success ful trap for vacu um and pressure heating.
An iron watch man that auto matically main tains uniform water level in low pressure boilers.
Separators--Steam and Oil
Type "A" Vertical Steam
Type "S" Horizontal Oil
"Victor" Low Pressure Steam Trap
For heavy vol umes of conden sation at low pressures.
We make separators of every type. Send for descriptive Bulletins on any o] the items listed on this page.
1098
Specialties, Heating
Yarnall-Waring Company
Philadelphia, Pa.
Branch Offices In Principal
Cities
More than 100 MUi Supply Distributors
Throughout the U. S. A.
Manufacturers of the YARWAY Impulse Steam Trap
Principal Advantages of the Yarway Impulse Steam Trap
Light Weight--Yarway traps need no support--H in. trap weighs only lY lb. 2 in. trap weighs &Y lb.
Small Size--They practically eliminate radiation losses--can be installed in cramped quarters--Y in. trap measures
234 in. long--2 in. trap, 4% in. long.
Will not air bind. Require no priming. Insure quick heating. Operate on exclusive Impulse principle {U. S. Patents No. 8,051,732. Other Pat. Pend.). Low Price--Often cheaper than re pairing old traps.
A--Cap Nui B--Lock Nut C--Bonnet
D--Control Cylinder E--Lock Pin . F--Valve K--Control Chamber L--Control Diec
G--Valve Sent H--TestPlug
J--Body
Six Sizes Serve Practically All Trap Requirements
Yarway Impulse Steam Traps in sizes from Yl in. to 2 in. are factory set for all pressures up to 400 lb. Simply select the correct size from the table below.
Operation--The Yarway Impulse Trap operates on an entirely new principle--the difference in flow characteristics of steam and water flowing through two orifices, with a chamber between. Movement of valve is governed by variations in pressure in the space above the valve, called control chamber--these changes in pressure oc curring with changes in temperature of condensate.
When handling condensate, the pressure tending to lift valve is greater than reduced pressure in control chamber, and the valve opens. As accumulation of condensate disappears, remaining condensate ap proaches steam temperature, flashing takes place, the flow is choked and pressure builds up in control chambers, closing valve.
Construction--The Yarway Steam Trap is unique in that there is only one moving part--the simple valve F illu strated. This trap is made of44 bar-stock" throughout--no castings used in its con struction. Body is cola rolled steel, valve and seat are of heat treated stainless steel, bonnet and cap of hex tobin bronze.
Years of service of thousands of Yarway traps in leading plants have proven these materials suitable for the service.
Capacities--Maximum continuous dis charge of condensate in pounds per hours at 30 deg. below steam temperature.
Pressure Vl In. Vs In. 1 In. V/a In. I'AIn. 2 In. Pounds No. 60 No. 61 No. 63 No. 64 No. 66 No. 67
10 20 30 40
50 60 70
80 90 100
125 150 200 to 400
475 650
800 900
980 1050 1140 1200
1240 1290 1400
1490 1630
825 1150 1375 1575 1725 1850 1975 2080 2175 2260 2460 2640 2900
1360 1725
1985 2220
2425 2600 2775 2925
3075 3215 3550
3870 4380
1910 2315 2650
2950 3200 3425
3660 3875
4075 4280 4760
5175 5960
2400
3050 3525
3950 4315 4630 4940
5200 5440
5675 6165 6630
7410
3425
4340 5050 5615 6100
6525 6930 7260
7600 7875 6530
9075 9950
Where greater capacity at low pressure. is required, use two or more traps with check valve on discharge end of each trap.
Prices, Weights and. Dimensions
Size
V in. No. 60
1 in. No. 63 V/4 in. No. 64 P/2 in. No. 66~ 2 in. No. 67 <
CroTmrp*plete
$15.00 22.00 31.00 48.00 68.00 90.00
Wt Lb
' 'Yf m
%
6 v/l
Length Inches
2=4 W, 514 4V. 414
For further information, send for descriptive bulletin--T-1721.