CHAPTER 20
1951 Guide
when the boiler is steaming under pressure conditions which would prevent the return of condensate by gravity. The typical connections for an auto matic return trap are illustrated in Fig. 13.
Each heating unit in a vapor system, as in all two-pipe systems, is pro vided with a graduated or modulating valve which permits the control of heat in the radiator by varying the opening of the valve. .
Two-Pipe Vacuum Systems
Vacuum systems operate under conditions of both low pressure and vacuum, but employ the use of a vacuum pump to insure maintenance of sub-atmospheric pressures.
A typical two-pipe up-feed vacuum system is illustrated in Fig. 14, and a down-feed arrangement in Fig. 15.
The return risers are connected in the basement into a common return main which slopes downward toward the vacuum pump. The vacuum
Steam Heating Systems
467
float control for the pump at the low point of the return main, located adjacent to the vacuum pump..
When the vertical lift is considerable, several lift fittings should be used in steps as shown in Fig. 16. This permits a given lift to be secured with a somewhat lower vacuum than where the vertical distance is served by a single lift. Where several lifts are present in a given system at different locations, the lifting cannot occur until the entire system is filled with steam. A lift connection for location close to the pump, where the size may be above the commercial stock sizes, is shown in Fig. 17. It is desirable that means be provided for manually draining the low point of the lift fittings to eliminate danger of freezing. *
TWO-PIPE SUB-ATMOSPHERIC SYSTEMS
Sub-atmospheric systems are similar to vacuum systems but, in con trast, provide control of building temperature by variation of the heat
pump withdraws the air and water from the system, separates the air from the water and expels it to atmosphere, and pumps the water back to the boiler or other receiver, which may be a feed-water heater or hot well. It is essential that no connection be made from the supply side to the.retum side at any point except through a trap. The desirable practice demands a return flowing to the vacuum pump by an uninterrupted dovmward slope. In some instances local conditions make it necessary to drop the return below the level of the vacuum pump inlet before the pump can' be reached. In such an event one of the advantages of the vacuum sys tem is the ability to raise the condensate to a considerable height, by the suction of the vacuum pump, by means of a lift connection or fitting in serted in the return. The height the condensate can be raised depends on the amount of vacuum' maintained. It is preferable to limit lift con nections to a single lift at the vacuum -pump. A still more preferable arrangement is the use of an accumulator tank, or receiver tank, with a
output from the radiators. The radiator heat emission is controlled by varying the pressure, temperature and specific volume of steam in circu lation. These systems differ from the ordinary vacuum system in that. they maintain a controllable .partial vacuum on both the supply and return sides of the system, instead of only on the return side. In the vacuum system, steam pressure above that of the atmosphere exists in the supply mains and radiators practically at all times. In the sub-atmos pheric system, atmospheric pressure or higher exists in the steam' supply piping and radiators only during severe weather. Under average winter temperature the steam is under partial vacuum which in mild weather may reach as high ^as 25 in.; Hg, after which further reduction in heat output is obtained by restricting the quantity of steam.
The rate of steam supply is controlled by a valve in the steam main or by thermostatically controlling the rate of steam production in the boiler.