BULLETIN NO. IC/FP.;;r (Revised iV.ardi, 1 975)
> \I \ \`t. * '*> 'W
r'\r a / *
I' ' . : *: i r ! 'X ** 1 ! I * ` 1
U *J li
''J 4. -.V,
TOWOLDMON0040472 WATER_PCB-00024941
SECTION A TRANSFORMER ASKARELS............................................1
I. Introduction............................................................ 1 II. History of Trade Name Types...............................1
Table I - The Composition of Transformer Askareis ............................................2
III. Interchangeability ................................................. 2 IV. Table II - Official Transformer Askarel
Shipping Specifications.........................................3 V. Ordering Instructions ............................................2 VI. Stability....................................................................2 VII. Precautions When Handling Drums, Tank Cars
and When Opening Transformers......................... 2 A. Keep Dry During Handling ............................2
Table III - Handling and Pumping Temperatures................................... 4 B. Use Ordinary Personal Precautions .............. 4 C. Precautions on Opening an Askarel Transformer.........................................5 VIII. Avoid Environmental Pollution............................5
1. Labeling Askarel Transformers...................... 6 2. Disposal of Liquid and Solid Wastes ........... 6 3. Conditioning of New or Recycled Askarel .6
4. Teardown of Transformers for Repair or Scrap .........................................7
5. Transformer Disposal...................................... 7 IX. Expected Service Life........................................... 7 X. . General Characteristics of Trr.nsformer
Askarel Fluid............................................................7 XI. Sampling Transformer Askarel Fluid .................8
XII. Evaluation of Askarel Received in New Equipment.................................................8
XIII. Dielectric Breakdown Voltage -- Moisture Relationship........................................... 9 Table IV -- Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in
Askarel and Mineral Oil.........................................9 Table V -- Approximate Solubility of Water in Transformer Askarel and Mineral Oil .... 10 XIV. Turbidity ...............................................................10 XV. Check Points for Maintaining Askarel Insulation ...............................................10 A. General Considerations................................. 10 B. Modern Scaling Procedure s ..........................11 C. The Older Sealing Arrangements..................12
XVI. Periodic Fluid Inspection and What Checkpoints Mean ....................................12 A. Visual Inspection............................................13 B. Dielectric Breakdown Voltage .................... 13
XVII. Inspection Checklist............................................13 XVIII. Contamination in Transformers.......................... 14
Table VI - Effect of Common Insulation Materials on Power Factor and Dielectric Strength...............................................14 Table VII -- Ef I net of Common Insulation Materials on Volume Resistivity of Askarel.............................................................. 14 XIX, ASTM Method for Investigating the Compatibility of Transformer Insulation aixl Construction Materials in Askareis...........15 XX. Refining Askarel for Re-Use...............................15 A. f- iiti-'ir) 1 ('rough Dry Blotter Paper
to Ri'inove MoMun# and C xUiinrous Particles.......................................15
--
XXI. XXR.
Table VIII - Water Removal by Filtering Askarel Through a Paper Press ...............
B. Disposal of Solid Wastes .................. C. Solid Insulation Requiring Drying . . , D. Earth Treatment for Maximum
Improvement of Power Factor and Volume Resistivity .............................
Table IX - Effect of Power Factor and Volume Resistivity.............
Cleaning Arced Transformers ................ Sampling Askarel.....................................
16 16 16
17 17 17
SECTION B ASKAREL FILLED SWITCHES
AND TERMINAL CHAMBERS .....................................19 I. Introduction.........................................................19 II. Sources of Contamination.................................19
III. Sealing Switches and Terminal Chambers...20 IV. Askarel Used Under Mild Arcing Conditions .20 V. Maintenance for Askarel Filled Switches . . . .20 VI. Askarel Under Excessive Temperature
or Fault Conditions ........................................... 21
SECTION C
:
TOXICITY AND SAFE HANDLING.............................21
I. Inhalation.............................................................21
II. Skin Contact........................................................21
SECTION D
ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO ................... Types of Analyses Available: .............................
1) Routine Maintenance Check........................ 2) Complete Analysis........................................ 3) Analysis After Earth Refinement .............
22 22
22 22 .
N
SECTION E APPENDICES ........................................................
Appendix A - Askarel Stability and Composition of Arc Formed Gas.....................
Appendix B - Solubility of Gas in Transformer Askareis ........................................
Appendix C - Effect of Temperature on Dielectric Breakdown Voltage of Askarel . . .
Appendix D -- Comparison of the Approximate Viscosity in Saybolt Universal Seconds of Transformer Askareis and Mineral Oil.............
Appendix E - The Density of Inerteen 54201 KA 7336-9 and Transformer
Pyranol A1233B-3............................................. Appendix F - Thermal Conductivity Values
of Transformer Pyranol A1333B-3................... Append x G - Heat Capacity............................. Appendix H - Coefficient of Expansion.......... Appendix I -- Fire Resistance............................. Appendix J - Seals, Properties
and Procurement ............................................... Appendix K - Caution Label.............................
23 23 23 23
24
24 24 ?4
25 25
NOTICE: "Nothing contained herein is to be construed as a recommendation to use any product in conflict w.m any patent. MONSANTO MAKES NO WARRANTIES a;
TO THE FITNESS FOR A PARTICULAR PURPOSE C ' MERCHANTABILITY OF ANY PRODUCT REFErV: ~ TO, no nuar.ir-tre of satisfactory results from reliance u. on contained information or recommendations, and 0.. claims all fiabi itv for any resulting loss nr damage."
j % <
1
I I
1 I I f t
V
I 1
I I
0666604
I
TOWOLDMON0040473 WATER_PCB-00024942
|j r*c* XL!*
; c^ mrrr^ OT1* w' ii L.-ib* Xsix
As
1. Introduction
'
The term "askarel" as defined bv IEEE. ASTM and the National
Electrical Code generally describes a broad class of fire-resistant*
synthetic chlorinated hydrocarbon insulating liquids widely used in
transformers, reactors end accessory equipment operated at power
frequencies. Askarsls of various compositional types are in use. (For the
general properties and types, see ASTM 0*2233.) Under are.rg
conditions the gases produced, while consisting of predominantly
non-combustible hydrogen chloride, can contain varying amounts of
combustible gases depending upon the askarel type.
.
.
This manual describes the operating characteristics of transformer askarel liquid insulation as manufactured by Monsanto and how it differs from mineral oil. .Appropriate handling and disposal procedures
for both scrap askarei liquid and impregnated solid materials are given in accordance with the- guidelines recommended by the American National Standards Institute.'
The information is based on facts gathered by Monsanto over 40 years as a producer of askarei, plus knowledge gained from the experience of transformer manufacturers and users. This guide. outlines- the maintenance required lor askarel fluid in "modern" transformers and offers suggestions for sealing and maintaining askarel in old units. By following this guide, v.'e believe users wiil obtain maximum service from askarel insulation with a reasonable minimum of maintenance If
questions arise relating .o the designing and building of transform;rs, these should be referred to regular transformer suppliers.
fvton:nto gratefully ?c<nowledges the assistance, guidance and :;t.: contributions c' certain lata by the following:
Edward L P.aai-- General Electric CV. T. K. Soat - V/estinghouse Electric
It. History of Trade \iame Types
"Askjr*! ' is the o'errir name for the fire-resistant awci inv.ib! ir>"
and ccolant first used t ' General Electric Company in
lor nc-,r
Pyranol1 brand name fi i-resistant transformers, Westirwroui.1 Electric
Corporation uses their b 2nd name, Inerteen.2
Whatever tha trademarked brand, the askarel contains chiorin; ted biphenyl -- one of the b ,-st liquid insulations developed by ycience. ' nis inert materiel is ch mically stable, fire-resistant, heat to >lo, non-corrosive, and has high dielectric strength under the cpt-ra m.i conditions encountered n transformers.
In addition to manufacturing Aroclor (chlorinated biphenvi),
Monsanto aiso mixes this dielectric fluid with chloicbenrenes to produce the presently used Inerteen and Pyranol blends described in
Tabic I.
'
"NOTE. f,\urisl* dim-)' .nod "fire resistant- Generally o>e more diMicu t to ignite, cr once tinned, turn at a slower r.nc man coiiesDpnntng convent oral rrutftrials. This term cues ict tr.vjn that Ure icuttont nuiwui. w"l not tum. However, w'lcrt pi w u . .`d. Monv.into's h'C rcsist.mt ASK Arte L ? L U t IP .;-e useful m nelpmi custonics ivtr :;nr hre safety re.-iuiuim-nts.-
1 Tr.KSciTi.trk. e* or'i'.Ml i'.-'X ' i. Company "T* :-.l n' n't o* Wenii'.'tou* L ' e-rtr *c CorpoMUnri
Hroi'itp; <*J Iiwr1n.11 o' I lui'wnto Curniuny
0686605
1|
TOWOLDMON0040474 WATER_PCB-00024943
Table I The Composition of Typical Transformer Askareis
Method ASTM D22S3
Type D
Type
Type G
Trade Names
Inerteen 70-30
Inerteen 100-42
Pyranol A13B3B3
Ingredients (% by wt.)
Aroclor 1254, chlorinated biphenyl (54% chlorine by weight)
70
Aroclor 1242,
chlorinated biphenyl (42% chlorine by v;eight)
Trichlorobenzene
30
Phenoxypropene oxide scavenger
0.16 to 0.22
Diepoxide scavenger
.
"
100 -
0.18 to 0.22
-
' 60
40
--
0.115 to 0.135
ASTM Method D-2283, titled "Chlorinated Aromatic Hydrocarbons (Askareis) For Transformers", also lists the composition of all transformer askareis used at various times since 1932.
Monsanto manufactures similar transformer askarel fluids in England where the trade name Pyroclor is ured.
HI. interchangeability 'In general -all transformer askareis are interchangeable. However, it is suggested that the transformer manufacturer be consulted prior to mixing in significant O'Oporticns a> tetd t':b:titu*icn.
IV. Transfornvsr Askarel Specifications Specifications for the three modern transforms askarri fluids era shown in Table II.
V. Ordering Instructions Monsanto's current coiicy is to v.-il .:k. ;J transformer fiuids o^lv to transformer manufacturers. Otr.o.s .ntorcstc-d in these rluids - icLld contact the manufacturers of ask rei transformers and not N'civtarn The transformer name plate indicates the transformer maker c:vj usually gives suuicient dat3 to identify the spscific askarel fluid; .\yi.
VI. Contamination Askarel insulation must never bt mixed with mineral oil. Over two percent of mineral oil by volume in askarel begins to lower its fire resistance.
In modern transformers, the principal "enemy'* of askarel is contamination by water. Keeping askarel water-free will insure long time service.
Askarel is heavier than water. If water nets into askarei insulation, only a tiny amount (approximately 12; ppm.i dissolves -- the rest floats on top. Askarel is very insoluble in water, only about 200 parts per billion o' a:-.are! dissolve m water, at normal temperatures.
Ml. Proc.tutions When Handling Drums, Tnnk Cars, and When
Opening Transformers Tin- f.'lkvi 111 11* iymf ur.mt pn-c.v.itions:
A. r%i-rii Li tv Ihiimg H.indn. In lut.idiinj, P.ormi). .....i;i-1j .nd I'^.vuting .isk-nel --
m
'
'' .. '
-
1 i
i
.
.....
............................
..
i i
i
i
TOWOLDMON0040475 WATER_PCB-00024944
t! _pti Transformer Askarc! Specification* (New Fluid)
Specification Properties1
- General Electric Co. Transformer
Pyrsnol A13030*3 ASTM D2283 Typo G
Westinghouse
Transformer
.
Inertccn 70-30*
ASTM D2283 Type D
Westinghouse . Transformer
Inortcen 100-42* ASTM D2283 Type E
df-r ovUent ppm (ASTM 01533-60) A. ;cJ ty mg hOH'g (ASTM D974-55) D n tnc Strength. 25 C. 0.1 in. gap
150 max. Clear ;
30 max; 0.014 max. 35 KV. min.
150 max. Clear
30 rnax. 0.014 max. , 35 KV. min.
.
60 max. Clear
35 max.
0.01 max. 35 KV. min.
3 -
037 7 49) C:)r*st3h 'hr>r no Hr
4,2 to 4.6
4.2 to 4.5
'
4.7 to 4.9
i AST M 0924-49)
i . Rr s'Shvity, 10OC,
.
LuU volts DC 0.1 mch yep, 109 ohm-cm
ti)3 .
ioo ;
100
iASTM D1169) lr '/did thlo'tdes ppm (ASTM D1821 and
0.10 rnax.
'
0.10 max.
;
0.05 max.
(. F Mr-thud E4C41B) R fructiv- index. 25 C (ASTM D1807)
V'.ciAiiy ot 37.8'C (ASTM D88-56)
1.6110 to 1.6120 44 to 48
1.6153 to 1.6173
56 to 61
;
'. 1.6240 to 1.6260
82 to 92
Sj.l-jlt tJtnvef'.il Seconds P...JI Puint 'C (ASTM D 97 57) S ctf-crjMvity 25. 15 5^ (ASTM D18)0) !..rn nt (ASTM D92)
3U or lower
1.495 to 1.510 None to boiling 1st drop 200C min.
'
30 or lower
'
k 1.518 to 1.520
None to boiling
1st drop 200C min.;
* ,
17 or lower 1.381 to 1.392 None to boiling 10% 325C min.
40% ir'jx. below 27QX
35% below 270C
90X- 360 max.
90'% 370 to 394 _
90% 379 to 394
r . i - -. i
C'v'*0'.>on tost
Color. APHA Af iclity. mg KOH-'g lno: j<jnic chlorides ppm Condition Stjvf.yvr content
Typical ProperUct2 CoeMu it*oi td Thurm-tl Expansion
iASTM D 1903). cm7/cm?/C . Aic fo.-inc-d g t-.es
*cr> ~h jljso usas thur private numlxir Incrleci 5*To1KA !tr In-;'teen 70 30 ao-i ;neif pnv.no
- Irt/v -n `.4I01CM fo> h.yn 100-13.
; 1...
j'iCi.LO V e hnj
J,l..U -:i; on1;
s mt! % tesi^d in hi'- liioo I;.
56.4 *- 0.5%
' 55.6% min.
43 1 0.5%
er heating with aluminum (or 6 hrs. at 200 to 220C, the aluminum must not be corroded
zither visual or weight inspection and the askarel should meet the following specifications:
200 max.
. 200 max.
200 max.
0 014 max.
0.014 max.
0.01 max.
0 15 max.
2.0 max.
0.15 max.
Clear
Clear
Clear
0.115 toO.135%
0.18 to 0.22%
0.18to0.22%
Dicpoxidc
:
phenoxypiopene oxide
phenoxypropene oxide
0.0007
0.0007
0.000G8
Aikarah of various compositional types ate used. Under arcing conditions the gases produced, while consisting
piedorr.'njr ily ul nori-cumpi'stible hydrogen chloride, can include varying amounts of combustible gases depending
upon div j'.k.itel type. Insulation systems Incorporating these askarels and criluloyit; or oth;r organic materials may.
,.ivi .irevd. prod in.** g.'sious mixtures which are moderately flammable. As a precaution, such gases should Iw
-cinowJ lr uni ;he
cl by bubbling dry nitrogen through the asxarel and flushing the gas space with dry nitrogen
` * c .. r, ...irk is pe; loiri'io on the apparatus.
i ;m..i ||,B. c ;incij3 wtth Mjnsanto's published speed ications.
0686607
iJ - iii'i t; . -jni_- d ":,i .ill i.mples. W/lte us for complete soles ipocdir.itiniis fer AskirBl fluids.
TOWOLDMON0040476 WATER_PCB-00024945
operating askarel transformers - take every precaution to guard the ar.kj'-J insulation from exposure to high humidity and
moisture contamination. Keep 5 or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarel by the drum "breathing"). This precaution is not necessary when drums are stored indoors, which is the preferred place for storage.
To avoid leakage the drums used for askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construction. The drums should be drained as completely as possible and then flushed Twice with kerosene type solvent to remove all of the askarel. Accumulated liquids and washings should be collected and should be incinerated at high temperatures, e.g., about 2C0Q"F, to destroy the polychlorinated biphenyls (PCBsl. See Section A, VIII.
Tank cars used to transport askarels are in exclusive service and
not used interchangeably for other products. All cars must be
unloaded through the top (dome fitting) either by pumping or
with controlled pressure using dry air or dry nitrogen. If nitrogen
has been usird for unloading it is necessary to advise the shipper so
that when the car returns the nitrogen can be replaced with dry air
before any one rmy enter the car. If the car is to be unloaded by
pumping it will be necessary to use a dryer on the air intake line to
remove moisture.
-
All tank cars are fitted with steam coils, which are available for
unloading under extreme low temperature conditions.
Convenient handling and pumping temperatures are given in Table HI.
B7* Use Ordinary Personal'Precautions: Transformer askarel has been muds, handled, und used for over 40 years, lx can be handled suuiy with recommenced precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid askarel has a solvent action (similar to paint
Table III Handling and Pumping Temperatures
Product
Unloading,
Handling -rvj Pumping
Temperature C
Pyranol A13B3B-3 Jnertcen 70-30 Ineiteen 100-42
20-55 20-55 35 -75
thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin.
In case of contact, wash the skin with soap and wau,r: remove and dry dean saturated doming. Clean up spills with rags, sawdust anJ cb,Of bent clay. Eye contact m;y result in pjintul iifu.it'nn hut no permanent damage to tissues. If askarel gets in the? eyes, iIlhii uhli lornJ amounts of water. As with all eye fust ad, u-ui '.u a physjcior). To relieve irritation, physicians have used an m;:i du e anesthetic solution as well as cipthalmic cortisone acetate Noiuu.m, or castor oil.
Intuquenl I'rpi'uiii' to .
Vapors Will nut
>'
I K'.. < \ i i, pr olni
i' .-r. :n h. /i vapor ci:;>rr:i .'!.< vr
he avoid, it. If hot jtk.ael lun-t be ban ?' d id a cd ' ' i arm, provide t,w>c aiea wu> mich.oir 1 . \h.;.ict v-uiin 1
TOWOLDMON0040477 WATER_PCB-00024946
wear an organic cartridge respirator approv'd by me U.S. d,,reau of Mines,
C. Precautions On Opening an Askarel Transformer: Askareis of various compositional types are used. Under dicing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can yiald varying amounts of
' combustible gases depending upon the askarel type.
Insulation systems incorporating these askarels and celluiosic or
other organic materials may, when arced, produce caseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus.
The American Institute of Electrical and Electronic Engineers Guide No. 76, March, 1974 gives more detailed instruct.ons and outdance "For Acceptance and Maintenance of Transformer Asiorei in tpuipment". This guide s published by the Institute of Electrical & Elec tronics Engineers, .nc., 345 East 47th Street, New York, New York. 10017. We recommend that users of askarel transformers refer to this IEEE document.
VIII. Avoid Environmental Pollution Transformer askare's contain polychlorinated biphenyls (PC3.) which have been used in the United States and elsewhere over the past 40 ygars for many industrial and consumer applications. During the past several years evidence has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological effects.
The United States Government's Interdepartmental Task Force on PCBs, Com-72-1&M9, in their March 20, 1972 report titled, "Polychlorinated diphenyls and the Environment", recon n.-nded restricting PC[3s to use in capacitors and transformers.
This report is distributed by the National Technical fnfi.-- -von Service, U.S. 0 jp.nr ment of Commerce, Springf efd, Virginia 2 I1
A document titled, 'Guidelines for Handling ano Disposal o* C ... ro und TranHc-'rr.e Grade Askarels, Containing rolycn / - j:lj Biphenyls", DoS bten prepared and is available from the t -van National Standards Institute, Committee Cl07, 1430 Erocb.siy, New York, New York 10018.
The scope, objectiv s and the composition of this commit'';? .u
ANSI Committee C107
Scope: Procedures and guides for safe use, maintenance and m . .. _f askarel and 3'Karcl-soaked materials used m electrical r ; -
Objectives: 1. Source uf technical information and advice 'or State, lor al authorities and ali others concerned 2. Enrojrure development of suitable disposal *e ke(,p all concerned informed.
r
3. Serve os me advisory group for United States i;.i''. ini. inuti inji organisations: CEE, I EC, CIGRE.
Compo'.ition;
Qrgani.-jiions active m or represented by This ANh
include: National Electrical Manufacturers Associa: in i
Industri'i Auoc .it'on, Inst tute of Electrical .r : :
Li'O'nw'rs, Arxi ctn Society frv Testing and M.i'
L t f >' ' ' As.a. ..d-un, Certified t-L'u,: ''
A , ; > _
f. i'. (/ -'IjilJ Pi-t:'Ctir.'n \i . ,
-n,
.1
m
' : -
. '
I
0686609
^
TOWOLDMON0040478 WATER_PCB-00024947
B-icou of Standards; Department of the Army, Rura1 E Itcinf.cation Administration; Division of Environmental Fc'-.v'ch, TVA; Am.-ncan Public Power Association, VV,;:er Pollution Control Federation; Food and Drug Administration; National Fire Protection Association; Underwriters Laboratories; and several sections of the U.S. Department of Interior.
The fo'lowmg are pertinent excerpts taken from the ANSI Guidelines
for askarel transformers:
1. LABELING ASKAREL TRANSFORMERS (Pg. 16) 4.22.1 New Transformers. AH new transformers that
contain PCBs shall have a label of adequate durability, permanently and prominently attached to the tank by the manufacturer, given adequate warning and instructions. A suggested label includes the following:
CAUTION: The insulating liquid in this transformer contains polychlorinated biphenyls (PC8s). Care should be taken to prevent entry into the environment. In case of . malfunction or leaks, consult the instruction manual or the manufacturer.
4.2,22 In-Service Transformers. The transformer manu facturer should make available suitable labels with a similar warning as shown in 4.2.2.1 for use on existing transformers.
2. DISPOSAL OF LIQUID AND SOLID WASTES {Pg. 15) 4.1.6.5.1 General. Disposal of oskarels and as.karel-soaked
materials should be accomplished by means in wfiich.there is no significant release of askarel to the environment. At . present, disposal is accomplished by carefully controlled incineration of liquids and soaked software, and by con trolled landfill burial of apparatus and other hardware from which askarel has been previously drained and washed.
Present knowledge indicates that proper incinsrarion ' must involve a suitable balance between dwell time and ------------ temperature in the incineration plus oxygen availability and, finally, suitable scrucbi-rs to remove the HCI that will pa formed; for example, 2-second dwell time at 2CXTF and 3% excess oxygen in stack gas, or 1.5-second dwell time at 270CTF and 2^ oxygen in stack gas.
These facilities should meet the applicable requirements of the state in v.hich they are located and should control effluents wnhin the limits set forth in this standard.
Controiled landfill or deau-wdi uisoosc! con be used where permitted by federal, state, and local regulations.
The ANSI Guide lists the locations of facilities that conform with the above recuiremer ts. Monsanto has such an incin erator at the W. G. Krunmrich Piant. Department S31, Saugat, Illinois 62201, where arrangements can be made for scrap askarel liquid disposil for a modest tee. For d<sp>o*3i of solid scrap a controlled dry land-fill can be used where permitted by Federal, State and local regulations.
3. CONDITIONING OF NE'.V OR RECYCLED ASKAREL
IPg. 16)
4.213.1. Askarel Conditioning SoJiprr.cn:. The condi
tioning unit should be located either in the storage tank urea
or In the main transformer manufacturing area for i.-iing
w'th <)S<<!fci.
4.2.1.2.2 V's
Conjit.'ohir.g uf new
rs! cr
ro-'yclod asia'cl requires hitter's earth treatment. The sprm
!u tier's earth in cartrmpes or bags, when replaced,
be
allow tl to it'.un thcrouqdv ov--r , rin pons to remove as
much liquid askarel js posuldc. P'-V cc'tnr.g:' units of steel
TWdlNA rCD WITH ASKAHEL" com-up for u..pus-l.o-\
0666610
|
TOWOLDMON0040479 WATER_PCB-00024948
4. TcARDOlVN OF TRANSFORMERS FOR RERAJR OR
SCRAP (P3. 16)
4.2.1.4.1 Dro.r. j'l csk.jrcl from the unit cither t.rro c holding tank or reuss or into the drum labeled "SCRAP
0 ASKAREL" for disposition, and then allow sufficient time for all of the askarei to drain from the core and cons.
4.2.1.4.2 Remove the core and coil assembly from the
transformer. Sufficient absorbent material should be placed
on the floor to absorb any askarei fluid that still drips from
. the transformer.
_
.
4.2.1.4.3 Place all materials in the appropriate salvage containers during the dismantling for later disposition.
4.2.1.4.4 All used materials, including rags, sawdust,
tape, etc, regardless of quantity, shall be put into the
appropriate containers for disposition.
5. TRANSFORMER DISPOSAL fPg. 17)
4.2.3.6 The ultimate disposal of an askarel-fiiled franc-
former may be accomplished in either of bwo ways:
(1) Complete drainage and dismantling with the proper
disposal of the askarei and askarehsoaked components cs
- described in 4.1.6.
.
(2) Disposition of askarei transformers by means of junx
or scrap dealers. This should be avoided unless a transformer
is first drained, followed by soaking the interior with a
suitable solvent. Accumulated liquids and washings are to be
, disposed of es described in 4.1.6.
IX. Expected Service Life Manufacturers indicate that properly designed and installed askarei transformers are expected to give trouble-free service for at letst 30 years. Since their introduction in 1932, the manufacturers report finding the overall failure rate to be less than 0.5% for all units under test and service conditions. The Edison Electric Institute's report (1956-1958) on their member utilities publishes the failure r. te foaskarei transformers as 0.13 per hundred banks per year.
Mr. Frank M. Clark. ,vho invented transformer askareis at the C r-'erai Electric Company it the early 1930s, made the hiohly pz tmen: comment besea on tis many years of experience with G.E. < /ranol (askarei type) transformers that -
"The important thing is to keep them dry - otherwise lea-- thtm alone".
These words or ivuom became especially ctpphceblc m mote uoant years when welding s-iut rather than gasketing became the man) motnoJ of sealing askarei transformers. These units are sold wt n :r.: understanding that the liquid is in a normally hermetically cioa-.-d system.
X. General Char; ateristics of Transformer Askarei Flni 1 _ Appreciation of ih. following characteristics, as given in th? lEcE Guide, leads to understanding the masons for selecting c 'ii'ctric breakdown voltage and moisture as the prime practical tests n jnc-*
the quality of transformer askarei fluid. Also, due ;c tm- -? characteristics the pjwer factor of transformer askarei will Le n ji.njiy much higher than th corresponding values for mineral oil.
In comparison to mineral insulating oil. askarei is d relative / pour
material; i.o.. 't.- <r,c:eculcs are dipoles, free to rotate .`.round t>- m and responsive to o' icntcfion by electrical forces. Askarei also xin>ms a much higher died cme constant and capacitance than mud'
and these diil.renct s must be kept m mmd wlun inter jm
n i. i
Ins! data.
[I...-MjVj a r, r r -! ,,<!.. l ly polar. and possesses htgli sol veru.y now. ' . -> in.ii h 'P'lri i``i`:tne.il!y sensitive than r.'.uier..! cl la n .
rMumeuvis son:!)1;? polar materials, and consi'(UkmU> 'me el .
0666611
TOWOLDMON0040480 WATER_PCB-00024949
constructional mantras destined tor use m askarel is very cntical. Tins mnrtivTy is reflected m the power factor and r<?sst<vity (specific resistance) of the askarel.
It is important to note that, with the exception of water, the dielectric breakdown voltage of askarel is not generally adversely affected by many of the soluble polar materials to which its power factor end resistivity (specific resistance) are so sensitive. In fact, the dielectric breakdown voltage of askarel is somewhat g'eater than that of insulating oil. Therefore, the values assigned these dielectric fluids in newly supplied transformers are 30 KV min, and 26 KV min., respectively.
At with insulating oil, askarel must be kept dry. It can pick up moisture
from exposure to humid atmosphere. Under similar conditions of
exposure, askarel can pick up nearly twice as much moisture when
measured on a parts per million weight basis.
.
XI. Sampling Transformer AskareJ Fluid The following precautions about sampling are quoted from the IEEE
Guide.
"Representative samples, whether of the complete contents or only parts thereof, are extremely important from the standpoint of
evaluation of the quality of the product sampled. Obviously careless sampling procedure or contamination in the sampling equipment will result in a sample that is not truly representative. This generally leads to erroneous conclusions concerning quality and Incurs loss of time, effort, and expense involved in securing, transporting, and testing the sample. It is strongly recommended that all of the procedures and precautions outlined in the latest revision of ASTM D 923 (Sampling Electrical Insulating Liquids) be followed.
"Because of the high specific gravity {relative density) o' askarel . - (greater than. 1), water.and some other impurities are most likely to be
found at or near the surface. The top sample, therefore, is considered to represent the worst condition."
XII. Evaluation of Askarel Received in Npw Equipment Some users of askaret equipment find it desirable to make "as received tests" on all equipment. It is qui common ;o use the dielectiic breakdown voltage test and visual appearance as the most signif emt tests. If suitable equipment and trained personnel are available additional information may oe obtained from the power factor, color,
and moisture contort tests.
In sampling askarel contained m loparatus extreme care must be exercised in order to obtain a representative sarnpic. ASTM Method D 923 should be followed.
Now equipment with askarel exhibiting the following characteristics is considered acceptable:
Dielectric Breakdown
Vo'tage Color Condition Visual Water Content Power Factor <;1 2'j1'C
30 KV min. 300 max. (Straw color) Clear 35 ppm it ax.
ASTM Methods
D 877 D 2129 D 1702 D 1S33
'The power fjetor of askarel taken from .new trjnsrprnurs,
fo'*c'o's and accessory equipment can reflect the pieseruv of
mmsture, dissolved polar compounds, or other cont rmmants end
m.q- v-ry with the type of cqu-pment from winch tne -. i.iipv .is
tjM'n due tu the uilfuent tjties of liquid tc-voUi h ..uu.non , ;.J
to the fu'jh solvency power q< the .ib.-nol. (.'.vu .;> -.t-p: ' '>
water content
tin iei ti ut hi . ikoown volt. ... . r :tc . ..............
It\(*ic.)tt>d oliuvn, a high power lector : .I'.K'-u m1' i ii. ; M-
serviceability of the askarel wim.m ' jt'ti-i tvtvq i.mits .,,i
TOWOLDMON0040481 WATER_PCB-00024950
indicative of the degree of extraneous soluble Doiar rrminais present.
Recognizing the possibility of a wide range o* power factors being recorded for askarel in new equipment, it is difficult to establish a single limit which would be acceptooie to bom supp iers and '..s-.-rs .for all applications. However, as a broad guide, power factors up to about 10% at 25*Cand 60 cycles per second ihertz) do not m general indicate any abnormal contamination prov.dmg that the other criteria (water content, dielectric breakdown voltage, etc.) are met. Much higher power factors may indicate excissive contamination or the misapplication of the solid materials used <n manufacture in contact with the askarel and should De investigated.
XH1. Dielectric Breakdown Voltage -- Moisture Relationship The dielectric breakdown vcltage of askarel is highly sensitive to excess moisture; not sensitive to ordinary dissolved poiar materials. While the dielectric breakdown voltage can also be lowered by severe vcmg, askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced.
If the dielectric breakdown voltage is checked periodically and decreases significantly -- this indicates moisture pick-up, aremg, cr both. When the dielectric breakdown voltage has dropped to 25 KV or less, ah analysis for water is necessary. If water is found in excess of 40 ppm at room temperature, its source should be located and corrections made.
When the moisture content approaches 125 ppm [saturation level at room temperature), the dielectric breakdown voltage of askarei drops below the value lequircd for efficient insulating. The moisture c orient should not be allowed to rise over 70 ppm, sampled at op?raring temperature. IT the moisture content is found to be in a satis .dory range and the dielectric breakdown voltage is low, the tran- ;ormer 'manufacturer should be consulted.
Table IV shows tm- relationship of dielectric fcreckdown vol cea vs. moisture and Table V indicates the approximate water sclubiht/ limits in askarel and miner I oil.
Table IV
Relation of IDiair? trie Breakdown Voltage to Amount of DissilvuJ ' .'ater in Askarel and Mineral Oil
Water Content (PPf. )
Breakdown Voltage (AST' 1 DS7 7
Askarel
Mm -roi <X
0
70 KV
13 KV
20 55 ; 9
40 47 : 0
60 40 i 0
80 38 '.2
110 10 5
0606613
TOWOLDMON0040482 WATER_PCB-00024951
Table V Approximate Solubility oi Water in Transformer
Askarel and Mineral Oil
<r fF.
Amount of Water (PPV11 Dissolved
Askarel
Mineral
20 22 20 -4 10 14
0 32
10 50 :o 68 20 86 40 104
8 16 28 41
65 94 128 170
8 10 13 20 33 58 35 130
XIV. Turbidity .. . may be the visual sign of undissolved water, or may indicate dirt. Cloudiness may also result from cold precipitation of tin tetrsphenyl 'scavenger" that was used in the earlier Pyranol transformers. This scavenger begins to come out of solution around 15F above zero. To redissolve it requires heating to 15Q-20DF and agitation.
High dielectric breakdown voltage will nuickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askerel is still excellent, However, if the dielectric strength is below 26 KV, moisture should be determined, using the Karl Fischer method lASTM D1533-60).
The dielectric breakdown voltage test tor askarel serves primarily as an
indicator ter moisture. It is by far the most important maintenance test
for transformer askarel.
.
XV. Check Points for Maintaining Askarel Insulation A. General Considerations:
Modern askarel transformers with welded construction or silicone or Viton* gaskets (hand -hole-cover, switch and terminal compartment covers) and with properly constructed bushings
require little maintenance. With properly constructed trans formers, annual or semi-annual visual inspection 3nd dielectric breakdown voltage test of the askarel fluid should suffice for routine maintenance chocking over many years oi service.
However, many askarel units wer; installed in the early 1930s b-.-fore the development of some of the bettor modern gasketing materials and before improved designs were developed ior sealing out moisture. Such early units should be, and can be, modernised, leaky or deteriorated gaskets should be replaced. If the osk;*rei l.os become contaminated, it should be reconditioned. Ai the same t me, ,i general clcan-up of the unit and possible rcfinicntng tnav be nos ruble.
II il is not convenient to take an o:d transformer out of service for g !ncil repairs, U\jky gaskets can b: sealed temporarily by panning . ever the leaky u.vu w<rh epoxy cement.
A survey of users indicates a rmed number of curly bu.lt
i
tr,, i,,t'uiTi.rv level 20 yujis old) ait kept in continuous .ei via m
;r -.tji!arts by tin: following ste;.n im-teud of
: i rm.'.itiun),
i he e; otn.'i utnts .ire equipped with coinpoun ' ;-n "ini'
-s
tnr ii.iOing
un: ,.:>ovu 0ii.J t.vlow .itmu ; n. i-e r.'M'u-
('<*> mlu.i .S, lb -n i, '.i', y , In,
TOWOLDMON0040483 WATER_PCB-00024952
pressure is maintained on the shell by introducing nitrogen ct 2 to 3 pounds above atmospheric. Regular workman m t--.? ar-oj . *y record the temperature and pressure. It a sudden pressure crop ,* noted more nitrogen is introduced and the gaskets are checked tor leaks with soap solution. Leaks are sealed by applying epoxy cement.
Modern Sealing Procedures:
Transformer purchasers should specify the following modern
techniques for sealing;
1. Welding Construction: Covers, radiator connections, switch
and terminal housings, instrument connections, etc. should
be welded.
2. Bushing Connections: A number of bushings have Deen
developed to obtain a proper seal for the electrical
connection through the tank wall. They are classified as
follows:
1) Welded Type (Bushing flange welded to tank wall)
a. Cast resin bushing with a molded seal to the
- bushing stud end external stainless steel or copper
flanges. -
b. Rolled flange bushing with the metal to poiceam
' . seal at the cap and flange made by being rolled into
grooves in the porcelain over silicone rubber rings.
The seal between the cap and stud is made by
welding.
c. Porcelain or glass bushings with metal to g'ass or
metal to porcelain seals.
2) Bolted Type - (Bolted to tank wall)
a. Cast resin bushings with either cast or metal flanges
' containing recessed gasket grooves.
b. Porcelain or glass bushings with flanges containing
recessed grooves or gasket stop.
The gaskets may be either of rectangular or circular cross-section, usually 'A inch thick. Bushings with recessed grooves are suable to use with cork, cork-nitrile rubber combinations or nitrile uboer as well as gasket materials such as silicone or Viton.
3. Small Size Connections: When not possible to weld small size connection seals should be made with Flex ;a.hc.* stainless steel rings. The surfaces must he machine J and parallel. The filler between the steel laminations -i the Flexiteihc ing should be either silicone or Viton.
4. Gaskets fer Hand-Hole Covers: Modern design sp.oued silicone ga.kets. Such gaskets must be retained in arc - .c. The groove preferably is machined into the flange or cov;-. However, it can also be formed by welding concentre ...el strips to the flange or the cover. Generally the gaskets t-cu'd be 5/16 to 1/2 in. thick for covers, depending on the u urn of the grove or stop. A rectangular cross-section is usually
used.
The silicone material should be Dow Corning No. 50 Silastic** or equivalent. This is a low comr'rrssi :?: material. For best sealing 20-25o compressi ;n is recommended, with ample clearance in the groove or ; top to allow for this compression.
No cemcn- is required. With reasonable care tne gj-k-t s
removable vithout damage and is reuseable.
.
Silastic DO is slightly swelled by askarel which contnb urn to the tightne.s of the seal. It is not deteriorated by ;:skar< ' `k.id or vapors, t resists weathering and it is therms.y sMl e 'd
1 (. .11 k i)l t i * la "c Ci.i*krl C.in|>iiny * T(ih>mi k Ot Oov* C< rnimj
0666615
|
TOWOLDMON0040484 WATER_PCB-00024953
2t s'l operating temperature?. It is an excellent
NOTE: Oow Corning, Midland, Michigan will supply a list of
Silastic 50 gasket fabricators to all transformer
manufacturers or users. They will also furnish technical
data. See Appendix J: Seals, Properties and
Procurements.
.
The Older Seeling Arrangements: The older type gaskets consist of either cork or cork-nitrile rubber
combinations or straight nitrile rubber. 1. Cork-Nitrile Combinations: Covers for the main tank,
hand holes, switch and terminal chambers, relief diaphrams, etc., are held in place by studs welded to the flange or by bolts. The gaskets are cut with openings and placed over the bolts. Often Snellac {Westinghouse Style No. 1150419, or General Electric Company's GlyptaT 1276) is used to cement the cork to the flanges.
The following is recommended for sealing with the cork -- nitrile rubber combinations:
Use Armstrong NC-757 cork-nitrile material or equivalent. The gasket can bs cut from a single sheet or by scarfing strips of the material. A convenient method for joining strips is to make a Keystone Type joint. For this purpose, Westinghouse, Sharon, Pennsylvania, offers their gasket cutter Style No. 328 B614 G01, (about S15).
The joints -- and also the gasket -- should be cemented to the flange, using one of the above cements. Excess cement should not be allowed to reach the interior of tne transformer.
__ _ After installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase weather resistance.
This epoxy cement is a paste to wlvch a curing catalyst is added immediately before use. Typm:-' ere:
a. Epoxy Patch Kit cl-C Hysol Corporation, Olean New' ork
b. Scotchcast*' Resin #4 Minnesota Mining & Manufacturing Company St. Paul, Minnesota
c. Adhesive A-1 and Activator Type B Armstrong Products Company Argonne Road, Warsaw, Indiana
d. Adhesive 9360-1, Synthetics Organic Company, Cleveland, Ohio, used with activator diethylene triamine (C3tbide and Carbon Che riical Company)
2. Straight Nitrile Rubber: When straight nitrile rubber was originally u*ed, invariably the gasket was recessed in a groove. This was to prevent gasket flow and to protect the material n.urv.t excessive compression. Although this type seal was no: cemented, the nitrile rubber gasket is not reuseable.
? ice grooves or stops have already been provth'J for the ninle rubber seal, Silastic 50 can be eayly substituted and is
..'umnivnai J. This conforms with modern practice.
Pi'ip Hie Fluid Inspection and What Checkpoints Mean 1 .Puk' - at six, rme, or tvvelve month inturv.i'S - m..ke
'P.u v i.uiii ii'vpeuuun u; yuui jskui ul Insulation arid i jn a d.-. ivctr >c
C:< niunv
0686616
TOWOLDMON0040485 WATER_PCB-00024954
A. Visual Inspection:
Askarei is a dear, faint-yellow liquid. After long-term use this color may gradually intensity to hgttt brown. The fluid snou.J remain clear and free from tuibidny or cloudiness.
Any color change - such as to a green, red or blue cast - indicates extraction of impurities (color materials) from the solid insulation. If a distinct foreign color pick-up is noted, check the compete range of electrical characteristics and notify the transformer . maker. Blackening of the askarei may .ndicare an arcing condition. Other color changes alone are not danger signals since the .. , .. dielectric breakdown voltage is not likely to be impaired.
B.
-
Dieiecrric Breakdown Voltage
If the dielectric breakdown voltage has decreased significantly
from the last inspection, or if it has graduaUy decreased below 26
KV range (at 25C) - RUN A CHECK FOR MOISTURE. Use
ASTM 01533 (Karl Fischer Method). ..
..
The dielectric breakdown voltage of askarei is the major indicator to the operating efficiency of your liquid insulat:on. Besides the visual inspection tests, dielectric breakdown voltage is the only test necessary to run on a routine basis. Well-sealed askarei transformers have service records of 25 to 30 years on the original askarei,
XVU. Inspection Checklist 1. If askarei is clear -- even though darkened to light brown, has no
sediment or turbdity, has dielectric breakdown voltage over 26 KV - give it the inspection "OK".
2. If askarei is clear, but has foreign color of blue, green, red ... it is
"extracting color'' from internal materials. This is not, of itsf if, an
operating hazard when the dielectric breakdown voltage stay;. over
26 KV and moisture remains low. However, This rare occurence
calls for checking into the condition of the interior constr: ?;:on
and consulting the transformer maker. However, when san cling
the fluid care should be taken to avoid getting color in: a me
' askarei from paint that may be inside or outside of the simple
valve.
.
3. If the moisture tontent is found to be above 70 ppm at op< ating temperature, ih n sampling should be done at more friquent intervals to estiblish a possible trend, particularly on oi vfjor installations.
4. If askarei is cleap but dielectric breakdown voltage drops tc 22 or lower KV, and moisture rises over 80 ppm whan sam; nJ at Operating temperature ... the askarei is ready for .-.mole "refining". If {he moisture is near the saturation level UooJt 123 ppm at room temperature) a thorough inspect,on snouic. o- nude for water dro 'lets in the transformer tank, and ev n for "glouules" of water floating on the askarei surface. If foui J, the transformer ma .ufacturer should be consulted for rc-condi un-ny both the transformer and the fluid.
5. If aska'Cl >< dorr; brown to black, if black particles of corf on are s^en. and dielectric strength is low .. . the aska.-ei has been ire-ken down by arcing. It cannot be refined and shotnd be remo* ; .md incinerated u1 l) r foper conditions. (See ANSI Commit;, C.Q? report on Use and Disposal of Askarei and
'.`jterrais. M30 Broadway, New York, New York 10013.
If u-iy cf dms- five simple inspection tests appejr out of the
ordinary oi tv. t > `1 orv.lnp b.lVM-en .ipoe er.mo- and test -
'S
jbnorrn.il, con act your transformer supplier for ,i c.
. 1:' hi- shipped to f.Yi-r, mi.\ pi- .1 e fo d--: "GAMBLING AGK.AF.lL*',
0686617
TOWOLDMON0040486 WATER_PCB-00024955
XVIM. Contamination in Transformers urc, ratter arid oiccd decomposition produce a<o
known to be venous contaminating influences on transformer askarel.
The power factor test normally used for the detection of contamination m rr.meral oil filled transformers is of little use for th.s purpose in askarel filled transformers, due to the extreme effect of extraneous soiuole polar materials. Tnis increase in power factor as illustrated in Tas.e VI has no adverse effect on dielectric breakdown voltage.
Table VI Effect of Common Insulation Materials on Power
Factor and Dielectric Strength (Heat Aged 96 Hours in Askarel at 100C.)
Material Immersed
Askarel After Exposure
Power Factor, Percent at 60 eye., 10CTC
Dielectric Strength
25*C.
None (control) Black varnished cloth Copper Pressboard Manila paper Phenol formaldehyde resins Shellac Iron Synthetic rubber
1.0 85.0
1.5 2.0 1.5 1.6 6.0 5.0 70.0
35 KV 42 40 37
39 41
36 39 39
Similarly, trace contaminants from commonly used construction materials can lower the volume-resisti'-ity of askarel, without affecting its dielectric breakdown voitage. This i-; shown in Table VII.
Table VII Effect of Common Insulation Materials
on Volume Resistivity of Askarel
Sample
. Volume Resistivity x 109 ohm-cm (at lOCFC., 500 Volts DC., 0.1" gap)
1. New askarel before heat aging 2. New askarel after heat aging 96 hou'sat 100C
3. After heat aging with 1 sq. inch specimens of: a P:.. nnlic resm tap changer material b. P.-ipcr c. Gr^e" A p'fssboard (tan)
d G<;:::e A pressooard (gray) e. Gracia A pressboard, laminated strip
'
f. Cotton wrapping
g. Giyptal 1276 cement, cured 48hrs. at 110*C
2,000 1,900
i,20Q 750 500 500 400 300 ICO
While trace contamination easily lowers volume resistivity from high levels, it is important to note that heavy contamination (as when arceol does not lower the resistivity below tfv ruder of lO1-1 ohm cm. at 100 C.
The c ff''r`.,rit tr:h;t\ior of askarel vs. mineral oil in these respects can bn
turnr j- . j ji fni'ows:
Hign power ijCtor and low volume lesistivity m transformer
n.'-vjl o h
commonly regarded as "danger signals" that tne
oil nos U'. tenorated and bioken down chenvculy or r-xci-mvo
mpu/ue is p: vsi nt.
Thu. - NOT ThUh o' a .k.uel l..,u>d i-v.uhifon ink s the tiir'ceir ,c I)mv` down \ ill . lew or tfv- moisture cnr'V'U is loon.
1 I
0666618
|
TOWOLDMON0040487 WATER_PCB-00024956
Manufacturers of askarel type transiormers point out that a is qu.;; w"H known that askarel transformers with initial power factor of :t; askarel flu'd in txcc-:s c ? L 2 w p: room tcmr,:-c:ore a: : i-Z : ,-c q , satisfactory service life. However, there needs to be assurance tnat fcotn dielectric breakdown voltage and moisture are at satisfactory revels and do not show adverse trends,
XIX. ASTM D3255 Method For investigating The Compat
ibility of Transformer Insulation and Construction Materials
in Askarels
*
This method uses the change of electrical and/or chemical
characteristics of transformer askarel resulting from its controlled
exposure to insulation and construction materials, in order to eva'uate their immediate major "contamination'' effect on the askarel fluid.
Delayed or long time contamination effects may not be detected.
The method also utilises various physical tests on the insulation and construction materials after controlled exposure to the askarel to determine the compatibility of these materials with transformer askarel,
Properly proportioned specimens of the insulation cr structural materials are immersed in refined askarel for 168 hours at ICO + VC m a forced draft oven. Changes in electrical and chemical properties of the transformer askarel are compared against a control sample of tne askarel treated in the same manner, in absence of the test specimens.
Dissipation factor {ASTM D 924} change is one of the criteria used. The askarel fluid is refined by absorptive treatment to a dissipation factor level of 0.05 max. at lOG'C and 60 Hz and 0.01 max. at 25*C and 60 Hz. Corresponding values of the askarel fluid after heating 168 hours at 100*C in absence of a test specimen are 0.075 and 0.02 respectively. The maximum dissipation factor levels suggested for the askarel alter heating in presence o- the test specimen are 0.20 at 100C and f-Q Hz
and 0.04 at 25`C and ; 0 Hz.
XX. Refining Asicp.rel for Reuse A. Filtering Through Dry Blotter Paper to Remove Moistur .md
Extraneous Po?t< les: Most operators r refer portable refining apparatus, such as ; p -fa press fitted win a dolly, available from Sparkler, Muni ; \ Illinois or Generd Electric Company, Pittsfield, Vbssuunusu. i.r the earthen emridgs filter type available from Industry! -r Corporation, Lebanon, Indiana. Filter paper liner* tor tn,, . ,
press are availal >e from Carl Schleicher and Schucii Cm p Keane, New Hampshire and manufacturers of filter pieces " ;
above.
The filter paper must be dried immediately Lufcre use. F results, spread tic paper for maximum surface exposure u ' 't air circulating o\ en and heat it for 4 to 6 hours at 11 ChC.
Circulate the arkarel hot (but not over 40*0 through. ,n ' ' ' fitted with the cry paper liners.
After filtration the dielectric breakdown voltage ot ne 1 should be 25 K\ minimum.
PRECAUTION:
1. Fii U i ."i j Mould -iot be done when the re I :ti. exceeds ' 5f>.
2. Any flex'o:c noses und gaskets on the refining ^ : . should h ' lined with or mode of materials tn.d be suite met by contact with .vskarei fluid. Imed wi ' Silicone, IV.on or Tiileri* or i ' niaUTiai1 are suitable.]
*Tr..,i<.m:i(k rf f 1. Pi: <;nt (S^Nerrou*i & Cnmiwny, Inc.
0686619
TOWOLDMON0040488 WATER_PCB-00024957
8. Make cure that the askarel is at least as warm $ the surround:^ air. (Cold liquids can condense moisture from humid air.)
C. When sampling askarel from transformers, it is best to take the samp.e v.hcn the unit is warm and operating at average or may ,-num load, especially for a check on moisture as reflected bv a dielectric breakdown voltage test. Sampling the warm askaret more truly represents its condition during operation.
Experience shows that water will migrate from a transformer's solid insulation to the askarel liquid and vice versa, depending on temperature. Therefore, when the transformer is hot, the moisture is most likely to be found in the liquid. This accounts largely for periodic variations in dielectric breakdown voltage. For example, a relatively high dieiectnc breakdown voltage may be found during winter months and a relatively low dielectric breakdown voltage during the summer months on samples taken from the same unit.
When testing has been completed, the remainder of the fluid sample should be destroyed by high temperature incineration described in Section VIII.
063662 0
|
TOWOLDMON0040489 WATER_PCB-00024958
0
h(StSm AsCisiirsS Sw^dres
iLeirnrrnsai]
af^rrrp'i'^ ^ir63 i*jr WM kjJ
I. Introduction
High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and switches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually rotary or drum type fitted with a revolving block and porcelain unit as the principal element arranged for three-phase service.
Askaref transformers with attached switches have been m use for about 30 years. When they were first introduced, the availability of insulating and gasketing materials was rather limited and even the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rubber-and-cork particles were used. While satisfactory for a limited period of time, these materials cannot be depended upon for the expected long nfa of the equipment.
The terminal chamber is usually above or below the switch
compartment and separated by a steel wall through which the bushings
are inserted. When bushings are properly selected and correctly
installed, there is no leakage from one compartment to the other. W th
poor bushing seals, and the terminal chamber above the switch, potting
compounds or cable oil can seep into the askarel. When the teimmal
chamber is below the switch, askarel can drain into the terminal
chamber.
.
II. Sources of Contamination There are three possible sources of contamination for asktrel in switches and termina chambers; they rank in this order of frequency: (1) water entering tf rough poor gaskets; (2} decompose.on pr jaucts from arcing when switch is used to break magnetizing current. (3J entrance of porhead or cable compounds through leaky bushing seals.
Unlike an askarel transformer where the amount of contamirmi is likely to be very sm< II Iprobably only trace amounts} in relation to ;,-,e volume of askare) fit id -- in switches or terminal chambers with fetr'-y seals, the amount of i ontamination can be relatively large.
Experience has shewn that, based on the number of ir stalled askarel-switch units, the percentage of failures is extremely small i'. hen investigated, it hos b ten found that most failures originate m the switen chamber. Water is the chief source of contamination. However contamination of as..3rel with petrolatum and asphalt material, ooc to
leakage, hove caused a few failures.
Petrolatum rj used frequently for filling terminal chambers. Wher cither cable oil or p-stral-iturr soups mto askarel, no great barm resul.s. "he fire resistance will \>o somewhat decreased and power tjrttor cl tne 3skarel will increase with on accompanying drop in resistivity Wmie highly undesirable, n is doubtful that failure of the unit f^surts V.'.nen? asphaltic compounds are used in place ol petrolatum, me u. '.< is increased somevvha: because jsnhaltic contamination may excessively high dieli etne losses in the askarel.
When the jtrrr.m;>l rum her is below the switch member, the er "j compound can bo oMnnuvd by rku'el il the buO ng sirs . fe k.iky. This is ufs:I ir.ible because thp askarel will mcreave thit i -.-.or factor end ccivliwr wfy <>r thp j'otti'ig comprounu or u..ih* "l , i>i develop he,, i (rum end ctr ><. loss M this mixture is d- awn . -. :o tf
0686621
TOWOLDMON0040490 WATER_PCB-00024959
,nsulct.an, a cable failure is like//. This sga>n emphasizes the imoortancu of tight b-shir.g assemblies.
III. Scaling Switches and Terminal Chambers Proper Du-hir.g construction, use of Silastic seals and welding wherever pots'ble '$ hghlv desirable las covered in Section A). Where an c'Ji'.omerc seal is to be used in contact with both askarel and petroleum oil, DuPont's Viton is suggested.
For new equipment the user should specify these modern sealing arrangements to keep out contaminants and minimize maintenance.
IV. Askarel Used Under Mild Arcing Conditions
The IEEE Guide for Transformer Askarel calls attention to the
following;
.
"Askarel is used, to some extent, in apparatus where it is subjected
to light intermittent arcing, such as in self-contained induction
regulators, where operating switches are continually producing
slight arcs, in transformer de-energizing switches, etc., Under
normal conditions, deterioration of the askarel is very slight.
However, improperly adjusted or defective switches in this type of
apparatus can produce excessive and prolonged arcing and
accelerated deterioration of the askarel. Jt is recommended that
when askarel is used under these conditions, checks of the liquid,
especially for moisture and dielectric breakdown voltage made
more frequently than when it is used only as a ccoling and
insulating fluid. Deterioration of this type is indicated by a
blackening of the liquid. It can usually be reconditioned as
previously described. Special attention should be given to
maintaining the scavenger at the appropriate concentration."
V. Maintenance for Askarel Filled Switches
A. Switches used for grounding after power source has been
de-energized will not undergo arcing.
B. Switches interrupting magnetizing current will be subject to arcing; the amount of decomposition will depend on power interrupted, time and frequency of operation. As a general rule, the liquid should be checked afte1 5 to 10 operations. 1. On newly installed switches, check the askarel at 3, 6 and `2 month intervals; if found satisfactory, check once annually thereafter. Witn proper attention to tns gasketing of covers and bushings, experience will probably indicate that less frequent inspection is warranted. 2. Check askarei for: a. Dielectric breakdown voltage (ASTM 0377): It should be 2G KV minimum, 'f dielectric breakdown voltage is low, confirm presence of water by Karl Fischer method ASTM D-1533. Filter to remove moisture. Dielectric strength should then be 30 KV minimum, b. Presence of carbon from arcing: Fluid should be relatively frea of carbcn. If badly arced and very black, replace fluid. If only minute amounts of carbon are present, filtration is recommended. Check power factor
of liquid (should not be over 5% at 25*C and CO cycles). Flush out switch chamber with several gallons of fresh askjiel before refilling. 3. If there is discoloration, hig t power factor, detectable change in r;.H-cific gravity or rofraci've index, or if fluid flashes below 25 D r, : e iso po.S'bi! ty of saen^oe of potting compound into the switch compartment. In this Core, correct any Icky b.mmng !.,,jls with proper replacements and fill with new
4. If tcrnnal chamber is below switch, check potting con-p.nnvj for pm,t nee of oskarcl lean usually he u h-at *1 by c.ior or by ,m tnty-.-jso m Sfv.cbic c.vvitv). M .nk.mJ <s P'lsvMl, correct jny l'-\,V;y buvinrii) H'.hS wiib p.M'T rent;'.: mu nt\ and renew co'npouiu!,.
5. E' ..mine cover g.:P <ms vsuu'S . 0 tenor .v.tyn i-o ' be >i -ct'-d
. Ii \
I I
0686622
|
TOWOLDMON0040491 WATER_PCB-00024960
by swelling and cracking ol the uxpus.d edge. :,i c.v.^ -f
severe deterioration, liquid seipaae is usually present. 6. Check for leakage at packing ,;:ur.p of sv..tcn:rg . . i* leaking, repack with a Silastic ring type gasket.
VI. Askarel Under Excessive Temperature or Fault
Conditions
.
The IEEE Guide also points out that,
"Chlorobenzenes used in transformer askarels begin to boil at
temperatures of about 2C5:C, under atmospheric conditions, 1; the
material is heated to such high temperature m a sealed system,
pressure develops. Pressure will also develop in the system if the
askarel is arced sufficiently to generate copious hydrogen chloride
gas.
'Therefore, it is recommended that wherever possible, sealed askarel'fiiled equipment be provided with pressure relief devices. . >c These devices must be large enough to provide immediate nii-.t at a definite pressure, and to prevent further build up of pressure it decomposition continues. It must be remembered that the presence of devices of this sort does not necessarily prectuae the rupturing of containing vessels, since pressure build up can be extremely rapid under violent arcing conditions.''
> tw,'...
rr~n
o e>
r7:''T"'f"7
n ,-s
';*! 1
A-1
T
i. Inhalation At ordinary temperatu'es the chlorinated biphenyls in Askarel hav' not presented industrial toxicological problems. The hazard of pun ntial toxic exposure varies with thsir volatility: the lower-chlorinated, morevolatile ones present n ore of a potential problem from the st:rd >oirtt of both inhalst'-on 2ml skin contact. When Askarel fluids arc us -d at elevated temperatures engineering controls must be applied, ehh r by the use of cfc:ad systems or by effective local-exhaust vsnv ,rion
together with general vrorkroom exhaust.
Vapors of Askarel at room temperature should not be breather in a confined space, and no vapor of any fluid evolved at eis ct.-J temperatures should be allowed to be dispersed into the g ncrol
workroom.
Inhalation tests on an.mals indicate that the maximum rare conc.-nrmtion of vapor is in tfe range of from 0.5 to 1.0 milligram pc- cubic meter of air, The threshold limit vaiue (maximum allowable cr ncentration of an 8 hour working day) set by the American Conte -"we of Government Hygienists are 1.0 milligram of the lower-cnior n s*rcj biphenyl compounds per cubic meter of air and 0.5 mT.jram it the more-hichlychiorinat1 d compounds, per cubic meter of air.
II. Skin Contact Prolonged or n.-peated skin contact with the Askarel fluids m >*. !>;
avoided by the use cf gloves and protective garments, bec.-sus? * t possible occurrence f'f a concision called chioracne. Aluioua . i v-:`s
of this condition caved by Askarel are rare, it can be prc.fw .d u/
excessive skm comae.. If Tne fluid is spilled on the skin the s-.n . -ou'd
be washed in the usu;; manrer with a soap solution.
A burn caus.d by cc tact with a hot Askarel should be tr- n > u y orci.n.iry burn.
;\-r d :p:' .it in- lui. t .-:is Ol A'k.iril fluids, s.w -Hon A '.'HI
'
0686623
TOWOLDMON0040492 WATER_PCB-00024961
SB
TT'
.r
-> "
li nTlLHSk'GS'L^lSF Ai8Lf-IT6ii
A r.jr^r* |! o r * | y*^ i ^ WTh rv--"' j\ / '
x\ V
Ll. (X fca^ * W AaA- < a.iu X *
^ C15> r-- ^ t>
".-ensformer users not wishing to make their own fluid analyses can obtain the service from Monsanto. Simply contact Monsanto end si^ci'Y vvnat analyses are wanted. You will be sent the proper-sized, clean sample container, fitted with a oroper label. When yoj receive this, carefully take your sample {following the procedure for sampling in this guide). Send the container to f.'.tnsanto's laboratory. Charges listed include sample container and laboratory costs. The charges are those in effect March 1,
1 u-75, end are subject to change.
Types of Analyses Available Analysis 1) ROUTINE MAINTENANCE CHECK
.. Iota) Charge: S30.00
.... .
.
To determine the general condition of the fluid and find whether further analysis is necessary, {one-quart sample required)
Properties Tested
Dielectric Breakdown Voltage
Color and Condition
Moisture
You will be notified of the results of this test. If further testing is indicated, and you want a complete analysis, you will be sent a
five-pint sample container, This sample will be used for the following series of tests:
Analysis 2) COMPLETE ANALYSIS
Total Charge: S75.00
{1) To determine the extent cf fluid contamination, {21 earth refinement to determine what degree of restoration of electrical and insulating properties is possible, (3) check test to see how the fluid responded to earth treatment.
' Complete Analysis: to determine the extent of contamination
Properties Tested
Free Chlorides
Color and Condition
Acidity
Specific Gravity
Dielectric BreakdownVoltage
Refractive Index
Power Factor, Dielectric Constant, and Resistivity
Water
b) Earth Refinement Response: Consists of treatment for 2.5 hours at 50-60*0. with 0.1 to 0.2 percent by weight of properly conditioned Artapuious e: / and then filtration through dry filter oaoer,
c) Analysis After Laboratory Earth Refhement:
Properties Tested
Acidity
-
Refractive Index
Dielectric Breakdown Voltage
Water
Power Factor, Dielectric Constant, :nd Resistivity
Free Chlorides
You will b notified of the results of this test series on ycur sample. Then after refining your entire transformer fluid fill v - j
can check on the results by requesting the following analysis:
Arv'vsis 3)
ANALYSIS AFTER EARTH REFINEMENT
Total Charge: $50.00
{This charge will not aoply when
analyses T and 2have already been made.)
termiftL* whether the entire lot of the askarel fill responded to the same ext nt as the laboratory sample, (five-pint s.im; e
Jrt)
:parties Tested
Free Chlorides
;cr and Condition
Acidity
tractive Index
Dielectric Breakdown Voltage
VL .ter
Power Factor, Dielectric Constant, c-nd Resistivity
.:".''n'-^ !or torts c.-y,~r bd above write to the fo'ipwing address:
David Wnod Vo"'.ir-1p Inojstrw Chemicals Ccmpcny ,hj f-Aftn L/rJirmh Blvj.
Lou s, Virrou'i 63)60
;0n-4 to t? tmtet! il.oi ild tv clearly marked tor ii.;rntific.iho
V..n:..-n;o Co'*':vnv
. ,tW. G Km r-> i >
c . ...... f.nn31
and sent da
:iiy tc
f P,. Kvister
0686624
TOWOLDMON0040493 WATER_PCB-00024962
(Qj -TV
APPENDIX A
Arkarcl Stability and Composition of Arc Formed Gas: Askarel insulation is one of the most inert, chemically-stable heat resistant, non-corrosive liquids known. It will not break down, oxidize or sludge when exposed to air and high temperatures. 150*0. or even somewhat higher. Arcing, however, will break down the compound to liberate some hydrogen chloride and small amounts of carbon.
'
- APPROXIMATE COMPOSITION
............................
.
ARC-FORMED GAS FROM TRANSFORMER ASKAREL BLENDS
ASTM TYPES D AND G
(INERTEEN 70-30 AND PYRANOL A1333B-3, RESPECTIVELY)
Gas
carbon monoxide
carbon dioxide
oxygen
inert gases
"
hydrogen chloride
(note the absence of phosgene)
Amount
0.3% 0.3% 0.6% 1.5% 97.3%
This arc-formed gas from ASTM Type D and Type F transformer askarels is non-flammable and non-combustible.
For ail practical purposes, the amount of gas liberated from askarel under a given set of arcing conditions is about 100 jubic . centimeters per.kilowatt-second.
APPENDIX B
SOLUBILITY OF GAS IN TRANSFORMS 1 ASKARELS ASTM TYPES D AND G
'C-irbon dioxide Air Nitrogen Hydrogen chloride1
Hn absence of scavenger
Percent of Gas 3y Volume Corrected to:
25C 760 mm
0^.760 mm
25*C
71% 5.7 6,0
37.8
iccrc
47% 4.3 4.8
50.9
25*C
5.8 5.5
100C
-5.0 4.4
APPENDIX C
EFFECT OF TEMPERATURE ON DIELECTRIC BREAJ* DOWN VOLTAGE OF ASKAREL
Temperature C
-60 . -!0 -20
0 20 to 60 60
Dielectric Breakdown Voltage
ASTM D877
67 KV 63 57 55 50 50 48 45
0666625
-)}))
TOWOLDMON0040494 WATER_PCB-00024963
APPENDIX D
COMPARISON O F THE APt'P.DXfMATE 'YISCOSITY IN SAYcOLT UNIV'E.-.SAL SECOND OF TRANSFORMER ASKARELS AND MINERAL OIL
Temp. *C
-20 0
20 40 60 80 100
Pyranol A13B3B-3
1,000 100 70 45 39 34 30
10-C Mineral Oil
1.000 150 85 49 40 34 30
Inerteen 70-30
2,800 195 85 50 40 36 33
APPENDIX E
THE DENSITY OF INERTEEN 70-30 AND TRANSFORMER PYRANOL A13333-3
Approx. Density gm/cc.
Temp. *C
0 20 40 60 80
Inerteen 70-30
1.574 1.552 1.529 1.507 1.485
Pyranol A13B3B-3
1.577 1.555 1.532 1.510 1.488
APPENDIX F
The thermal conductivity values cf transformer Pyranol A13333-3 at 27*C and 58C are 26.2 and 25.8 x 10'5 calorics centimeters-i, degrees centigrade*1. second-*, respectively. Or. approximately 0.06 BTU per (hr.) (sq. ft.) (*F.) per foe t. ""This same approximation applies to inerteen 70-30.
APPENDIX G
Heat Capacity Over the temperature range of 25* to 125*0 the specific heat of transformer askarel is close to 0.30 calories per gram p *r degree.
APPENDIX H_______________________________________________________________________________________
Coefficient of Expansion The average coefficient of expansion of transformer askarel over the temperature range 20 to 1Q0C is0.0007 cc/cc/X. O 12 r:i!on would increase to 1.056 gallons on heating from 20 to 100X.
APPENDIX I
r;' C- R-m'StjnCO A'.-'jrcH of various compositionrl types are used. Under arcing conditions the gases produced, while consisting of p 'itommamly non-combustible hydrogen chloride can yield varying amounts of combustible gases depending upon tie os'. i J type.
Insulation systems incorporating these askarcls and collulosic or other organic materials may, when arced, produce osseous mixtures which are moderately flammable. As 0 precaution, such gases should be removed from the askarel by buOb'mg a. y nitronun through the askarel and flushing the gis space with dry nitrogen befoie any work is performed on the apparatus.
0686626
|
TOWOLDMON0040495 WATER_PCB-00024964
APPENDIX J
Seals, Prop:-ties and Procurement
-
Do.v Corr> ' 3 Corporation, Midland, Michigan with Districts at Atlanta, Boston, Chicago, Cleveland, Dallas, Los Angeles, 1 l.e.v York C t,, Washington, D.C. and Toronto has avaiLule Bulletin 09 019, August 1902 entitled "S.lashc Dcs.gn Data".
^ Th s lists gzsket fabricators throughout the country from whom the "Silastic 50" gasketing can be purchased in sheet,
extrusions or molded shapes.
Generally, Silastic 50 sheet goods are stocked by local die curlers, hence, could be generally purchased locally. Usually small Quantities of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other elastomers.
Where the casket is extruded for fitting into a machined groove or between gasket stops, Dow Corning advises use of a scarved joint. This joint is then cemented using Dow Coming's Silastic 140 (clear) or their RTV 731 (white) materials, which air cure.
Do.v Corning points out that the local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill in preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure the Silastic 50 for 24 hours at 480*F.
SPECIFICATIONS*
ASTM D67G ASTM D4I2 ASTM D412 ASTM D395
Color Specific Gravity at 77*F Hardness, Shore A. Scale Tensile Strength, psi, min Elongation, percent, min Compression Set after 22 hrs
at 300*F, percent, max
White 1.20 + 0.02 45 to 60 800 250
30
* AH physical properties measured on 0.075 inch thick safnples molded 5 minutes at 240^, and oven cured 24 hours at
480*F.
'
APPENDIX K
Caution Label The following or equivalent caution statements should be fixed on all containers of transformer askarels and the transformers themselves: 1
This product contains Polychlorinated Biphenyls (PCBs). Care should be ;aken to prevent entry into the environment through spills, leakage, use, vapoi ization, or disposal of liquid or containers Avoid prolonged breathing of vapors or mists. Avoid contact with eyes or prolenged contact with skin. If skin contact occurs, remove by washing with soap and water. Following eye contact, flush wi:h water. In case of spillage onto clothing, the clothing should be removed as soon as practical, skin washed, and clothi xj laundered.
r. n i ',
tsaiitoI \ !
MONSANTO INDUSTRIAL CHEMICALS COMPANY S"l;CIALTY PRODUCTSGROUP COO N. LINDBERGH BLVD. ST. LOUIS, MISSOURI 631G6 Tnc information herein regarding obtaining optimum results from askarel fluids in your transformer has been accumulated by Monsanto for over 40 years from the experience of makers and users of askarel transformers and it is believed will be helpful. Nutning herein shall be construed JS applying to other than askarel insulation. Data and maintenance suggestions herein do not upp-Y to me other components of .he transformer. All operating and maintenwee suggestions recommended by the manufjet-'cr of the transformer should also be carefully followed. T-cause these maintenance directions apply only to the askarel insulation. Monsanto disclaims any liability for damage to property or injury to persons arising from transtormcr operation.
0666617
TOWOLDMON0040496 WATER_PCB-00024965