Document DDn9zqXYzaGpZv9ZZbB4Y44K5

American Society of Heating and Ventilating Engineers Guide, 1934 SIZE AND LOCATION OF VENT The size and location of the vent outlet is important. In many cases the sizes for public buildings are regulated by law, but the location of the vents generally is left to the discretion of the engineer. Best results have been obtained with a velocity through the vent openings nearly equal to that at which the air is introduced into the room, thus maintaining a slight pressure in the room. Calculated velocities at the vent openings of from 600 to 800 fpm produce the best diffusion results from this system. The cross-sectional area of the vent flue itself may be figured on the basis of 15 sq in. of flue for each 100 cfm. Thus the vent flue area of a flue for a room equipped with one 1200 cfm uiiit ventilating machine would be 180 sq in. The area of vent flue opening from the room may be figured on the basis of 25 sq in. per 100 cfm. In buildings provided with wardrobes or cloakrooms the vents may be so located that the air shall pass through these spaces, heating and venti lating them with air which otherwise would be passed to the outside without being used to the best advantage. Many state codes for venti lation of public buildings make this arrangement mandatory. The individual vent flue and the corridor or central vent flue are the types generally used with unit ventilators. The individual vent flue system provides for separate vent flues from each room. The corridor vent or central vent outlet system provides for outlets centrally located to take care of a group of classrooms, the air passing from the classrooms,' wardrobe or cloakroom to the corridor, and from the corridor to the central outlets. The grilles between the wardrobes and corridors may be near the ceiling, provided the air leaves the classroom to enter the ward robes near the .floor in the classrooms. A velocity of 800 to 900 fpm" may ' be used for the central outlet from the corridor. Where the law and the type of building construction will permit, the escaping spent air from the building may circulate throughout the attic on its way out. CAPACITIES Unit ventilators are available in air capacities ranging from 450 cfm to 5000 cfm and with corresponding heat capacities (above that required for ventilation purposes based upon an outside temperature of zero and an inside temperature of 70 F) ranging from 125 to 600 sq ft of equivalent direct heating surface. Some manufacturers furnish a unit with several heating capacities for each air capacity, thus enabling the engineer to select the unit best adapted to the heating and ventilating load. Capaci ties should be determined in'accordance with the A.S.H.V.E. Standard Code for Testing and Rating Steam Unit Ventilators4. Typical capacities are given in Table 3. The amount of heat to be supplied by the unit ventilator will depend on the amount of air passed through the unit and the temperature range through which the air is heated. The weight of air (W) to be circulated per hour is fixed by the ventilating requirements. ^Adopted 1932. See A.S.H.V.E. Transactions, Vol. 33, 1932. 182 Chapter 13--Unit Heaters and Ventilators If no direct heating surface (radiation) is installed, the combined heating and ventilating requirements must be taken care of by the unit ventilators, and the total heat to be supplied is obtained by means of the following formulae: Ht = 0.24 W (ty--to) . V W = dQ (D (2) ty- H +t h 0.24 W + (3) where d = density of air, pounds per cubic foot. H = heat loss of. room, Btu per hour. Hy = heat required to warm air for ventilation, Btu per hour. Ht = total heat requirements for both heating and ventilation, Btu per hour = H + Hy. Q = volume of air introduced for the ventilating requirements, cubic feet per hour. t -- temperature to be maintained in the room. t0 -- outside temperature. ty = temperature of the air leaving the unit. W -- weight of air circulated, pounds per hour. 0.24 = specific heat of air at constant pressure. From Equations 1, 2 and 3: Ht = H + 0.24 dQ (t--to) (4) Example 1. The heat loss of a certain room is 24,000 Btu per hour, and the ventilating requirements are 1000 cfm. If the room temperature is to be 70 F and all air taken from the outside is zero, what will be the total heat demand on the unit if it is required to provide for both the heating and ventilating requirements (combined system). Solution. H - - 24,000; d -- 0.075 <2 = 1000 x 60 = 60,000 cfh; < = 70 F; <o = 0. Substituting in Equation 4; Ht = 24,000 + 0.24 x 0.075 x 60,000 (70 -0) = 99,600 Btu ty -- 24,000 0.24 x 0.075 x 60,000 + 70 = 92.2 F Table 3. Typical Capacities of Unit Ventilators for an Entering Air Temperature of Zero. Cubic Feet op Am per Minute 600 750 1000 1200 1500 Total Capacitt in Square Feet op Equivalent Direct Heatinq Surface (Radiation) Capacitt Available for Heat ing the Room in Square Feet op Equivalent Direct Heating Surface (Radiation) AmFinal Tempera ture (Deo Farr) 285 95 105" 350 115 105 455 150 105 565 -490 105 705 235- ' 105 183