SECTION V A-la.51
APPLICATION BASIC INSULATION
PIPE AND FITTINGS
CALCIUM SILICATE SINGLE LAYER:
M. Insulation supports
M. 1. V 1.1
' 1.2 1.3
All vertical pipe having an O.D. larger than 3 inches
and requiring 1-1/2 inch thick insulation or more,
shall have a means of supporting the insulation above
each flanged joint.
If there are no laterals, supports, etc., within IS
inches of the flanged joint (Figure 63 A) that would
serve;jthe. purpose, then angle clips, or sinfilLar,
shall,^j.e welded to the pipe. Figure 63 B..1
The supports shall be located, aboye the flanged joint,
allowing for the standard bolt removal space - "Z".
Figure:^ B. .
_ ., .
The supports shall extend out from:. the pipe approximately
the thickness of the insulat ion but'. no; more. See nZn
Figure. 63 C.