60-50 ENVIRONMENTAL PROTECTION AGENCY 140 CFR PART 761] [OPTS 6203 5;?SH FRL ] POLYCHLORINATED BIPHENYLS (PC8*> MANUFACTURE, PROCESSING, DISTRIBUTION IN COMMERCE AND USE PROHIBITIONS* USE IN ELECTRICAL TRANSFORMERS REFERENCE DOCUMENT VII. (1) HONS 214062 * '/ {*> ' USEAP. OPTS, EEO, tW.ITI OPTS 62035 PCB (Fires) 0 File Reports ORAFT REPORT EXPOSURE ASSESSMENT: FIRES INVOLVING PCB TRANSFORMERS EPA Contract No. 66-01-6271 Task No. 7S Prepared for: U.S. Environmental Protection Agency Exposure Evaluation Olvislon , Office of Toxic Substances ' 401 M Street. S.U. Washington, O.C. 20460 Prepared by: Versar Inc. 6B50 Versar Ctnter P.D. Box 154 Springfield, Virginia 221S1 December 16, 1963 Revised January IS, 1964 MOWS 21*083 a.usjjin*r This document ts a preliminary draft. It has not bean released formally by the Office of Toxic Substances, Office of Pesticides and Toxic Substances, U.S. Environmental Protection Agency, and should not at this stage be construed to represent Agency policy. It Is being circulated for comaents on Its technical merit and policy Implications. MONS 214084 TABLE OF CONTENTS Paat 1. INTRODUCTION............................................................................................................... 1 2. PYROLYSIS OF PCBS BY FIRE................................................................................... j 3. SUNNARY OF FIRESINVOLVING PC6 TRANSFORNERS.................................... 3 4. DISCUSSION.................................................................................................................... 17 5. REFERENCES...........................................!..................... .............................1.19 MOWS 214085 1 1. INTRODUCTION Electrical transformers containing PCB-based collant liquids ware manufactured In the unltad States from tha aarly 19901t until 19TB. Nora than 100,000 such units nay still ba In sarvlca. Although transformers filled with PCBs ware more expansive than transformers filled with mineral oil, tha PCS units ware used In those locations where tha flammability of mineral oil would present a significant fire hazard to adjacent equipment or structures. In many applications, such as In . underground electrical vaults, the decision as to whether the transformers should contain PCBs was.a matter of policy which varied significantly among the various electrical utilities In the United States. Although normally operating PCS transformers are totally enclosed units, there have been a few documented Incidents where physical 'damage to a transformer or electrical failure within the unit has resulted In the loss of PCBs with significant exposure to people or the environment. The most serious consequence of physical damage may have been the transformer leak that occurred when a transformer being stored for eventual reuse by Pierce Packing Corporation In Billings, Montana, was struck by a truck and leaked Into a water recovery sump In a meat packing plant (Anonymous 1979). The resulting contamination of animal feed resulted In a F0A recall of food products In 17 states, and led directly to the EPA ban on the use of PCB transformers In locations where food or feed could be contaminated (EPA 1962). PCB transformers can also lose PCBs to the environment by venting through the safety valve. The transformers are equipped with pressure relief valves set at about 1$ psl which are designed to prevent rupture of the casing If the transformer becomes pressurized due to the generation of gas or vapors due to Internal arcing. However, the release of hot pressurized PCB vapors can entrain considerable quantities of 1 HONS 214086 liquid RGBs is a fine mist. DocuiMntad safety valve release* from transformers In Washington, O.C. (Lees and Breysse 1083) and Frankfurt, 6ermany (Folk 1)03) demonstrate that such Incidents can release hundreds of pounds of RGBs and, depending on the wind conditions, distribute the aerosol for several hundred feet. However, the arcing conditions are usually of fairly short duration, and the resulting pyrolysis of RGBs does not result In the formation of more than a few parts per million of pyrolysis products In the oil remaining in the transformer (tees and Breysse 1983, pp. 29-35.). Greater pyrolysis of RGBs has occurred In several recent Incidents where RGB coolant fluid has leaked from transformers Into an externally fueled fire. The formation of polychlorinated blphenylenes (RCBRs), dlbenzofurans (PCOFs), and dlbenzo-p-dloxlns (PCOOs) and their wide dispersion in the smoke generated by 'the fires may present a ` significantly greater risk to human health and the environment than results from the previously Identified transformer failure mechanisms. 2. PYROLYSIS Of RGBS BY FIRE Laboratory experiments have demonstrated that RGBs are converted Into polychlorinated dlbenzofurans when heated for two weeks In the presence of oxygen at temperatures between 2?0*c and 330*C, but that the furans decompose at temperatures above 330*C (Norite et al. 1978). Experimental pyrolysis of RGBs held at elevated temperatures for less than one minute In the presence of air demonstrated that RGBs were completely destroyed et temperatures above 700*C, but that measurable amounts of PCDFs were formed by exposure to temperatures as high as 6$0*C (Buser et al. 1978). A comparison of the pyrolysis products from two capacitor fires In Sweden suggests that exposure of RGBs to high temperatures In the presence of oxygen can form PCOFs, but that exposure of RGBs to these temperatures In the absence of oxygen can lead to the formation of RCBRs and other chlorinated polynuclear aromatic chemicals (Rappe et al. 19B2). RGBs MOWS 214087 apparently do not degrade to PCDDi, but PCDDi can be formed by the pyrolysis of the trl- and tetrachlorobenzenes that are mixed with the PCBs In many transformers (Webber 1982). The chemical reactions leading to the generation of PCDDs and PCOFs are discussed in detail in a recent review article by Choudhry and Hutzlngar (1982). The formation of planar chlorinated compounds, such as PCOFs, PCDDs, and PCBPs, Is of concern following tho pyrolysis of electrical fluids as some of the congeners of these compounds are much more toxic than PCBs (Vuceta 1983), An assessment of the data from recent fires In the united States that involved the loss of PCBs from transformers Indicates that the formation of these compounds by pyrolysis of PCBs Is a common occurrence that does not depend on a peculiar set of conditions, and that the normal air convection caused by a fire may spread thesj chemicals far beyond the confines of a transformer vault, ' 3. SUMMARY OF FIRES INVOLVING PC6 TRANSFORMERS State Office Building. Binghamton,.New York At S;30 a,m. on February 5, 19B1, a fire occurred In the switchgear adjacent to a PCB transformer In the basement mechanical room of the Binghamton State Office Building. This building Is an .16-story office tower that was completed in 1973 (OGS 1962). Power to the building was supplied by two transformers which contained a coolant fluid consisting of 65% Aroclor 1254 and 35% mixed trl- and tetrachlorlnated benzenes (Schecter 1963). Although the city fire department responded within minutes, they did not enter the mechanical room until the power was disconnected to the transformers approximately fifty minutes after the fire started t&eimann 1983). Ourlng this period, there was repeated electrical arcing and reports of loud explosions occurring In the mechanical room. Smoke generated by the fire was distributed by convection throughout the 3 MONS 214086 bunding through an open vertical chase that started In the mechanical room and ran to the penthouse. This concrete block chase contained the sheet metal duct for the exhaust air from the men's restrooms on all the floors. The chase was not air tight, and allowed smoke to escape Into the space between the structural celling and the suspended celling on each floor of the building. As a result, the entire Inside of the building was coated with black soot. Air and wipe samples were taken one to two weeks after the fire occurred to define the levels of PCBs prior to cleaning. The results are summarized In Table 1. The probable source of the soot was combustion of the materials In the switch gear. The heat of the fire apparently caused a ceramic bushing to crack on one of the transformers, allowing approximately 180 gall ons of Insulating liquid to drain onto the floor in the vicinity of the fire. Photographs taken shortlylafter the fire was extinguished showed that the switchgear was completely destroyed, but that there was little damage to the transformers. The mechanical room was heavily coated with soot, and puddles of liquid remained on the floor. The heat from the fire was sufficient to slightly damage a structural steel beam that was directly over the switch gear. However, the fire apparently did not spread to any material other than the switchgear Itself. Elevated levels of PCOFs In the soot were reported within a week after the fire. Initial analyses of soot samples were performed by the New York State Department of Health, U.S. Department of Fish and wildlife, and the university of umea. Each of these labs analyzed for those constituents for which they had standards available. The results of these analyses are summarized In Table 2. The New York State Department of Health subsequently did a more thorough investigation of the PCD and PCDF levels In soot taken from the top of the suspended pi l celling in each of the floors of the building and of a large composite sample of soot that was collected by vacuum cleaner from the third and i i \ MONS 214069 Table I. PCS Levels In the linghaatfon State Office Building Before Cleaning Type of taplt Date of sailing Location-floor Type of surface II Air try wipe** Dry wipe** try wipe** Dry wipe** Dry wipe** Dry wipe** Ory wipe** Dry wipe** Ory wipe** 2/11-2/13, 1981 2/18,2/12,2/13 2/10.2/13 2/10,2/11,2/13 2/11 2/12,2/13 2/12 2/11-2/13 2/11-2/12 2/12 1.2,9,1.10,13,15.18 8,1.2 1.2 3,5,8,IT IT 5.10,13 10 5,10.13 10,17 8.18 Open areas, horizontal surfaces Open arnas, vertical surfaces Open areas, horizontal surfaces Open areas, vertical surface Enclosed areas,***' horizontal surfaces enclosed areas,*** vertical surfaces Move impended celling, horizontal surfaces Move impended ceiling, vertical surfaces and fee blades 19 9 3 1 8 3 8 3 8 *AlI air taelet are wgAa*: ell wipes are nj/h* of Arocior 1259. **Wipe smplet taken By wiping one square Meter with dry Ml ter paper. Inside closed desk and rile cabinet d-auers. asswed to be I/? of detection |M|. Source: DON 1*1. Range* Seonetrlc fern* 0.21*0.7 <. 1*100 0.3*84 1.98 2.93**** 8-78 57*930 182.18 T.8 7.8 12.8*980 79.97 .92*19 800*18,000 9.82 1995 1.5*3.8 2.92 9.9*020 131.83 HONS 214090 Polychiortnated liphanylt Polychlorinated Oibanzofurant 2,3,7,8-tttra Total tetra Total panta Total hexa Total hapta Total ocu Polychlorinated Oibenzo-p-dioxlnt 2.3.7.6-tatra Total tttra Total panta Total hexa Total hapta Total oeU Polychlorinated btphenylanes 2.3.6.7-tttra Total tttra Notts Tabla 2. Coapotitton of Soot Samlet From tha tnfhaitoft State Office tutldtng - yg/g Smith 196 It Smith 1961b Aappe 1961 Stalling 1W1 273 124 46 S97 12 26 S.4 970 105 SIS SI 2 101 2.6 2.9 1.2 1.6 0.5 1.2 5 4.7 7 2 S $ Sample 8I171195Ssoot uted In animal feeding ttudiet 6 SO MOWS 214091 fourth floor of tho building and subsequently used for animal feeding studies. The results of these tntlyses are summarized in Table 3. The variation In the conctntratlon of PCOFs from floor to floor Vs thought to be a function of the extent to which the various soot samples were contaminated (and thereby diluted) with normal building dirt that had accumulated on the ceilings. Animal feeding studies Indicated that the homogenized material from Floors 3 and 4 had an acute toxicity in guinea pigs equal to that expected for an Inert material containing 58 ppm 2,3,7,8-TCDD (tadon et al. 1982). The building has been extensively cleaned by vacuuming and washing to remove the soot. The effectiveness of the cleaning has been monitored by wipe samples taken both with dry filter paper and with hexane saturated gauze pads. The results of a study to compare the effect of the sampling procedure on the measured levels of PCBs on surfaces after completion of the preliminary cleanup are summarized in Table 4. A number of dry wipe 1 samples from vinyl walls were analyzed for PCDDs and PCOFs. The results of these analyses are presented In Table S. Analysis of air samples (Smith et al. 1963a, 1963b), wipe samples from vinyl walls, and bulk samples of sprayed-on celling insulation (Versar New York Inc. 1963a, 1963b) have demonstrated that the ratio of the various toxic constituents Is not constant from one matrix to another. The relative concentrations of PCOFs having various degrees of chlorination In different media are summarized In Figure 1. These data suggest that vaporization and redeposition processes are causing a gradual redistribution of the material within the building. The Binghamton State Office Building Is still closed to normal use awaiting the establishment of a reoccupancy criteria which will specify the residual levels of PCBs, PCOFs, and PCOOs that will be considered to be safe. The most recent draft risk assessment for re-entry to the Binghamton State Office Building would require that the air contain no 7 MONS 214092 libit 3. Concentrations (119/9) of M^blorimM Biptanylt mb Polychlorinated Diberuofurans In Soot Sables Taken Fran the inghMtOT State Office Oeilding Floor 1 2 3 4 5 4 7 8 9 10 II 12 13 14 15 14 17 . SS i=if KH* 28 waft* fetre CDF 0.2 Penta CDF 0.2* Mesa CDF 0.3* Hapta CDF 0.3* OctoCOF <0.3* Total FCOF - Itotlo Toiol FCOF cone. PCD oonc. 1300 MO 220 2800 4400 1800 23000 9400 21000 11000 3400 930 10000 9200 4500 7200 5000 <8* <9* <11* <12* <14* - W 220 21 280 13 180 1.2 42 <1.2 21 $1 WO 23 190 70 31 180 79 14 35 32 3 3.7 14 0.5 - 3 W 4K> 200 320 140 250 440 170 340 290 M 240 100 4.5 97 35 2" 31 d d d d d 1200 400 1000 - .Ml .021 .042 .11 .052 .042 .048 d 32 300 b 220 d 31 310 150* 240 d 54 09* 140 d 5.8 71 33* 32 d 2.8 17 II* 15 - 87 750 470 145 IOO 145 120 84 70 31 20 II 4 438 310 .094 .075 .103 .044 .042 ^Quantitated Arcelor 1254; dali unoomcM for rtawtry. ^Correction for recovery Incorporated. Sot sapled Decease of dies ini lar ceiling construction. 4dU not mod become of poor recovery of Internal *'Cl-letra CDF standard (<101). ^ttte lost becooM of InstnanenUI mlfonctloo; for purpose 1 of colcoUttoo of toto) PCDF, it Is asstned that btu CDF Is 1/2 the concentrat ton of peote. . *5oot col leetod by tmoi cleaner ond osod in ooiool tonicoloey studies. ^Detection Units ore per agnpar, not per ch Iorinot Ion wedirr. SiU not corrected for recovery. Instrument aolfoncttoe coesed loss Of dote on *rCI-fetro CDF recovery. MOWS 214093 Soerce: Codon IW. Table 4. PCS levels la the Blnghaatea State Office Betiding After Prelfcainary CI*Mf Type ef spl* Date rf sa^l tag location-floor Ory wipe* Urt wipe** Dry wipe Hat wipe ST wipe Urt wipe 5/5/02 S/S/02 5/5/02 S/S/02 S/S/02 S/S/02 0 0 9 9 9 9 Type of surface n Vinyl floor Vinyl floor Vinyl wall Vinyl wall plaster wall Plaster wall _ 12 12 12 12 3 3 wg/u* Geoeetrlc Naan P9/U 3.2*19.4 14*400 0.45 214 0.0*12.4 3.9*240 3.44*** 44.5 1.4*1.4 1.2*19.4 1.5 4.2 wipe Urt wipe by wipe Urt wipe S/S/02 S/S/02 S/S/02 S/S/02 9 9 9 a* Quarry tile floor Quarry tile floor Window glass Window (less 3 14*21.4 3 000*940 4 0.0*4.0 4 0.0*2.1 20.1 920 .12*** 1.1*** Dry wipe - 0.25 *' area wiped with dry fitter paper. AM wipe - 0.25 e* area wiped with a cotton yawn pad wetted with S al ef banana. --mt mwed to be 0.4. ' Source: Versar Maw Mr IW. HONS 214094 Omnicel TAI 5. CMtarnation of Vinyl Wills in the (ia^wUn State office Ouilding After Washing Dry Wipe Sopln Units 7th Floor location llth Floor Keen Std. Deviation Si mi 2.3,7.8-tetra total tetr* ToUl rente ToUl Mho Total Hqrte Total Octe id*1 ngde* 2.4 1.0 1.2 1.3 2.0 1.2 0.1 1.0 1.4 1.13 0.25 5.50 2.00 0.03 0.25 0.8) 0.55 0.53 4.50 4.25 4.25 4.00 2.10 2.50 l.M 1.13 0.8) 0.50 0.23 0.13 0.13 0.10 0.13 0.00 0.03 0.55 0.03 0.25 4.15 4.00 0.00 2.15 3.25 3.25 4.50 2,18 3.0) 2.20 3.75 0.50 0.85 0.50 0.05 0.00 0.28 o.to 0.38 0.70 5.01 3.73 2.10 0.55 0.22 0.78 0.22 1.04 t.53 1.04 0.28 0.10 PCIMh 2,3,7,8-tetra Total tetra ToUl penta ToUl leu ToUl NpU ToUl ocU a|Al, MO 0.50 0.14 NO 0.55 MO NO NO r 0.14 HD 0.53 0.48 HD 0.10 0.05 * * * * ** .* * N0 - avenge detection twit * 0.01 nj/e* "00 - average detection 1 ienit * 0.1 Source: Wersar dew York 1183b. HONS 214095 MOT oat mnt i m i l H V 1AI1V1M MATH AIR 2 ti CEIIIRB MEVLATlOH S i UWVMMV u u v im DECREE Of COLOR IAATIOR OEOREE Of CH10AIRATI0R Figure 1. Rolotlvo Abundance of Chleredlbenzofuran Congeners In Various Media In the Binghamton State Office Building Source: Eadon 1982; Smith 1983a. 1983b; Vertar New York Inc. 1983a, 1983b. 11 MONS 214096 more than B.4 pg/m* 2,3,7,8-TCOF end tht surface contamination be no more than 2.S ng/m* 2,3,7,8-TCOF (Kim 1983). This criteria assumes that the ratio of 2,3,7f8-TC0F to other tonic chemicals remains the same as In the soot and that the level of contamination remains constant for 30 years following the reopening of the building. The draft risk assessment Is being reviewed by a panel of experts and the calculated re-entry criteria are subject to revision. One Market Plata. San Francisco. California Shortly after 11 a.m. osp May IS. 1983, a fire started In the sub-basement transformer vault of the One Market Maze office building at the corner of Steuart and Mission streets In San Francisco. The vault contained three transformers that were filled with Aroelor 1242 coolant liquid. Heavy black smoke Issued froiji the sidewalk grating adjacent to the building for about three hours until the high voltage power to the transformer was Interrupted by the utility (Burks 1983). During this three-hour period, there was considerable vibration and loud noises occurring In the vault that were described by reporters as explosions (Smith and Solffer 1963). No Information Is available on the size of the transformers, but It was reported that only one transformer leaked, and that after the fire there was 50 to 60 gallons of liquid In the vault, with the floor and walls of the vault caked with black soot and liquids dripping from the vault celling (Bartlett and Solffer 1983). The liquid remaining In the transformer contained 127 ng/g TCDFs and no detectable TCDDs (detection limit > 7.4 ng/g) (Anonymous 1983a). Contributing to the seriousness of the fire was the failure of a protector In the vault (Melnlck 1983). Smoke and soot from the transformer vault contaminated the adjacent switch gear room through the bus duct, and small areas of the adjacent parking garage and work shop areas through small cracks in the concrete block vault walls. Soma of the heavy smoke Issuing from the sidewalk 12 MONS 214097 grating was apparently pul lad in through the street level air makeup louvers on Stauart Street and Into the ventilating fans that supply air through the sub-basement, basement, plate level, and floors 7 through 6 of the Steuart Street office tower. Tests later indicated that the contamination was limited to the second basement, the air handling system through floor 6, and the exterior of the building. The upper floors of the Steuart Street Tower receive air from ventilating fans mounted In a penthouse above the 78th floor. Air samples taken In the vault starting a week after the fire measured 370 to 1500 yg/m* PC8s, depending on the rate of ventilation through the vault. The switch gear room adjacent to the vault had air concentrations as high as 98 vg/m* PC8s before ventilation was started. Air levels In the sub-basement fan room .i ; (outside the fan housings) found a peak level of 7.7 vg/m PC8s : ; (Anonymous 1983b). The San Francisco Department of Public Health restricted access to any area having a level of PC8s In the air In excess of 1 vg/m* or surface contamination In excess of 100 ug PCfis/m* when sampled by wiping with a cloth wetted with octane. Although no samples collected In the offices on floors 7 through 6 were contaminated above these levels, the city requested that the ventilation system not be operated because of the possibility of spreading contamination to these clean areas; without ventilation, the floors could not be occupied. Analysis of the soot collected in the transformer vault and In the sub-basement adjacent to the wall of the transformer vault showed the presence of PC8s, TCOFs, and TCDOs as shown In Table 6. Only one sample was completely characterized fr polychlorinated dlbenzofurans. This was a wipe sample taken August 9 from the floor of the HVAC fan room In the second basement that had the following amounts of CDFs (Anonymous 1983b): 13 HONS 214098 Typ# of unpit Soot soot Tafel* 6. M8t. PCOFt, and ACOOt In Sanplat fra# On# H*rt*t fl*u Mfor* cleaning Location Oattd Sanplt rot v/ Total TCOFt Vft/ adjactnt to vault Insld# Of vault -- -- 86,000 -- 29.9 13.6 2.3.7,8TCOF Vft/9 6.3 7.3 Total TCOOs W/9 .324 2,3,7,8TCOO uft/g .059 .400 -- nj/t? ng/o? I*/*? nft/(#2 Hip#** Hip#** Hip#** Hip#** Hip#** Hip#** fan room -- witch gr rocn -- - fft ' twitch g#ar root -- - floor 28th floor -- vault floor 7/17 fra* roa* top of fan 8/9 -- 7.3 -- .006 -- '-- .016 , 1.0S 1 7.3 <0.0$* 2.3 7.9 .004$ .93 2.9 .06$ 2.4 .001* .017 : ;, - -- .017 -- ** -- * -- VO*3 nj/*3 ft*'** #9** n9/i*3 Air intld# vault -- ISO 9.2 1.63 <.003* - Air 21tt floor -- .6 .006 <.001* - - Air vault 7/17 490 .99 .13 *- - Air vault 8/12 $60 2.8 1.0 ... - Air twitch g#ar 8/20-21 2.8 .07 .022 ... - roa* Air fan roea 8/S-7 .84 .013 .004 - - *hon# d*t#ct#d it detection Unit Indicated. ' **w1p# tanpl# eo11#ct#d utlnfl Kln-wlp# pap#r w#tt#d with ocunt. Source Anonymous 1983a, 19838, 14 MONS 214099 Tot*l TCDFt 2.3.7,8-TCOF Total pent* CDF* TotAl hex* COF* Totel htpt* COF* Tot*l oct* COF* Amount 73 ng/ng* 29 ng/m* 22 ng/m* 4 ng/m* 2.3 ng/m* .2 ng/m* Illative abundance .40 .30 .06 .03 <.01 The cv11*ble report* on the *n*1ytlc1 result* from One Market Plat* do not specify the analytical procedures nor, in most cases, the detection limits. However, it is apparent that the conversion of PCS* to PCOFs occurred with about the tame efficiency In both Singhamton and San Francisco. Reoccupaney of One Market Plata depends on whether the cleaning efforts achieve the criteria established by the State of California (Sravltx 1983) and the City ..of San Francisco (Sflverman 1983). The criteria established by the City are summarized in Table 7. First National Bank Building, micaoo. Illinois On September 28. 1983, a fire occurred In a bus bar between a transformer and the switchgear In a transformer vault under the plaza on the same block as the First National Bank Building. Although power to the transformer was cut after about 10 minutes, smoke continued to Issue from the tide walk grating for about 4S minutes. Inspection of the transformers after the fire was extinguished found that one of the four transformers In the vault had leaked approximately 15 gallont of coolant consisting of 65X Aroclor and 35* chlorinated benzenes (Simon 1983a, 1983b). The source of the leak was a small hole In the transformer casing that was perhaps caused by electrical arcing. Significant PC8 contamination was limited to the vault, the exhaust air ducts from the vault, and to the exterior surfaces of a small building that was adjacent to the transformer vent. The highest readings outside the vault and Its exhaust system were on a window near the vault (119,000 ug/m*) and on an Intake air well grille (181,000 ng/m*) and window (96,000 vg/m'). The transformer vault was 15 MONS 214100 Tabla 7. Raoccupancy Criteria for Ont hartat Plaza GENERAL OFFICE SPACE Ml PC00*/PC0F# PCM Muu PCOOv/PCOFi* pai TRANSFORMER VAULT &k PCOOa/PCOFa* PCM Surfacti PC00t/PC0F* PCM 10 PR/ I M/n* . 3 hr/*1 loo kr/b* GO PR/B* 1 pR/t* 24 1000 |*R/B* Oaflnad a tha <* of all PC00 MO PCOF conROnort chlorinated at tha 2,3,7, and petition. Source: Silvarow 1RO. 16 MOWS 16101 7 adjacent to an underground parking garage and shared a ventilating system with the garage and the small adjacent building; none of the adjacent areas were heavily contaminated. The tall First National Bank Building was about one half block from the vault and was not contaminated. Although one fiber glass filter on an air intake vent on the fourth floor of the First National Bank was found to contain about 90 t>g/g RGBs, the adjacent filters did not show high levels. None of the measurements of PCBs taken In the building indicated unsafe levels of contamination. However, the building was evacuated when smoke was seen coming from a window vent; the source of the smoke was later Identified as the exhaust from an auxiliary diesel generator that started when power was shut off at the transformers. No Analyses were reported for PCDf.s or PCOOs In the sabt. iA; number of wipe samples were collected In the First National Bank building and from the air supply Intake near the transformer, but no PCDFs or PCOOs were found at a detection limit of 250 ng/4 ft1 (673 ng/m1) for total PCOFs and PCOOs by full spectrum NS scanning, and a detection limit of from O.B to 15 ng/ft* (B.6 to 160 ng/m1) 2,3,7.B-TCOO. The First National Bank building was evacuated at the time of the fire, but reoccupied the following day. Cleaning was limited to the transformer vault, Its exhaust system, and the exterior of the small building next to the vault. The criteria of cleanliness was established by Commonwealth Edison at 400 t>9 PCBs/ft* (4300 vQ/m1) when sampled by wiping with a Miter paper wetted with hexane. 4. DISCUSSION The data that has been developed In the laboratory and from the analysis of samples of combustion products from various fires Involving PCBs Indicates that the formation of polychlorinated dlbemofurans can be expected In cases where PCBs are exposed to air and elevated temperatures. A fire Involving a PCB transformer can generate 17 MQNS 214102 considerable smoke end the demege to surrounding property depends on where the smoke goes. Eleveted levels of PC8s have been found several hundred feet from the source of the fire; If the smoke gets Into a building through ventilating ducts, the elevated levels of PCBs and pyrolysis products will be found In the building. A review of transformer Incidents suggests several precautions that would limit the threat to human health and the envlronamnt resulting from the continued use of PCB transformers. First, the possibility of fire should be minimized by preventive maintenance of the various electrical components used In conjunction with the transformers (switchgear, breakers, cables, etc.) and the area around the transformers should be kept dear of flammable materials. Second, there should be a method or procedure for quickly disconnecting the power to the transformers If a fire should occur in the vault. The ^nstallatldn of circuit breakers on the high voltage side, perhaps activated by temperature. Infrared, or smoke alarms in the vault, would do much to reduce the duration of the fire and the generation of smoke and the Installation of network protector on the secondary side would prevent current from being fed back Into a failed transformer. The apparent advantage of the protective equipment should, however, be carefully balanced against the Increased likelihood of failure of a more complex installation, bearing in mind that the failure of a protector contributed to the severity of the Incident In San Francisco and the failure of a primary switch filled with PCBs resulted In the contamination of an office building recently In Syracuse, New York (Heath 19S3). Third, design features to seal off the vault from the adjacent buildings, and perhaps to seal off the normal vault ventilating ducts In the event of a fire, would decrease the dispersion of smoke and the resulting contamination. Fourth, since continued operation of the building HVAC system can contribute to the spread of smoke, the HVAC controls could be tied to a fire or smoke sensor In the vault to allow for automatic shut down In the case of a fire. ' 18 HONS 214103 5. REFERENCES Anonymous. 1979. Cat* study of contamination: pcb's in f**d. Scl*nc* Newt, Vol. 116, NO. 14 (Oct. 6, 1979), p. 229. Anonymous. 1993a. Summary of PCS air sampling results - On* Narket Plata. August IS, 1993. Anonymous. 19630. Sunnary of air sampling results for PC6*s and TCDF's - On* Narket Plata. September 12. 1963. Bartlett R, Solffer 6. 1963. Cleanup after S.F. explosion. San Fransdsco Chronicle, Nay 17, 1963, p. 1. Burks J. 1963. Downtown dioxin danger. Firehouse, November 1963, pp. 71-72, 114. , Buser HR, Bosshardt H-P, Rapp* C. 1976. Formation of polychlorinated dlbentofurans (PCDFs) from the pyrolysis of PCBt. Chemosphere, No. 1, pp. 1D9-119. , , ** * t: Choudhry 60, Hutlinger 0. 1962. Mechanistic aspects of the thermal formation of halogenated organic compounds Including polychlorinated d1b*nto-p-d1ox1ns. Toxicology and Environmental Chemistry, Vol. 5, No. 1. pp. 67-93. DOH. 1961. Background. (Attachment to agenda sent to the members of the Expert Panel for the Binghamton State Office Building prior to a meeting of the panel In New York City on April 3, 1961.) Albany, NY*. New York State Department of Health. Eadon 6, Aldous K, Frenkel 6, et *1. 1962. Comparisons of chemical and biological data on soot samples from the Binghamton State Office Building. Albany, NY: New York State Department of Health. Harch 1962. EPA. 1962. Polychlorinated biphenyls (PCBs) manufacturing, processing, distribution In commerce and use prohibitions; us* In electrical equipment. Federal Register, Vol. 47, No. 165 (August 25, 1962), pp. 37342-37360. Folx R, 1963. Hochglftlges Clophen sprlttt* aus den Trafos. Frankfurter Rundschau, Nay 9, 1963, pp. 13-14. Oelmann S. 1963. City crisis began after fir* ended. (Series of articles on th* fir* In the Binghamton State Office Building). Binghamton (N.Y.) Sunday Press, Binghamton (N.Y.) Evening Press. 3an. 30 - Feb. 5, 1963. 19 HONS 214104 S. REFERENCES (continued) dravltz N, Fan A. Noutra RR. 1963. Interim guidelines for accoptablo exposure lovtl* In office settings contaminated with PCS and PCS combustion products. Oerkeley, CA: California Department of Health Services. November 1, 1963. Heath T. 1963. Tests show PC6 danger unlikely at Chimes 6u11d1ng. The Post Standard (Syracuse, NY), vol. 155, No. 96 (December 23, 1963), p. A-l. Jansson 6. SundstrSm 6. 1962. Formation of polychlorinated dlbentofurans (PCOF) during a fire accident In capacitors containing polychlorinated biphenyls (PC6s). In: Chlorinated dioxins and related compounds - Impact on the envlronamnt. 0. Hutzlnger, ed. Now York: Pergamon Press, pp. 201*206. Kim NK, Hawley J. 1963. Revised risk assessment Slnghamton state Office Sulldlng. Draft Report submitted to the expert panel on the Dlnghamton State Office Oulldlng. Albany, NY: New York State Department of Health. June 7, 1963. Lees PSJ, 6reysse PN. 1963. Final report on Industrial hygiene* assessment: PC6 exposure of 6SA switchgear operators. Report submitted to Accident and Fire 6ranch, General Services Administration. 6a1t1more, HD: Center for Occupational and Environmental Health. The Johns Hopkins University. Jan. 20, 1963. Helnlck N. 1963. 100 PC6s leaks reported In downtown S.F. San Francisco Examiner, September 21, 1963, pp. Al, A12. Horlta N, Nakagawa J, Rappe C. 1976. Polychlorinated dlbeniofuran (PCDF) formation from PC6 mixture by heat and oxygen. Jull. Envlronm. Contam. Toxicol., Vol. 19. pp. 665*670. 06S. 1963. The 61nghamton State Office Oulldlng clean-up: a progress report update. Albany, NY: New York State Office of General Services. January 1963. Rappe. 1961. Rappe C, Narklund S, Oergqvlst P-A, at al. 1962. Polychlorinated dioxins (PCDDs), dlbemorurans (PCDFs) and other polynuclear aromatics (PCPNAs) formed during PC6 fires. Chernies Scripts, Vol. 20, pp. 56-61. Jr-*: . ___________ 20 HONS 214105 5. REFERENCES (continued) Repp* C, Narklund S, Bergqvlst P-A, et. 1. 1903. Polychlorinated dioxin*, dlbentofurens and other polychlorinated polynuclear aromatics formed during Inclneretlon end polychlorinated biphenyl fires. In: Chlorlneted dioxin* and dlbentofurens In the total environment. Boston. HA: Butterworth Publishers, pp. 99.124. Schecter A. 19B3. Contamination of an office building In Binghamton, Now York by PCBs. dioxins, furans and blphenylenes after an electrical panel and transformer fire. Chemosphere, Vol. 12. No. 4/$, pp. 669-680. Silverman MF. 19B3. Letter to Nr. Wynn Oliver, Tlshman West Building Management Corporation [sic] from Mervyn F. Silverman, Director of Health, City and County of San Francisco. November 17, 19B3. Simon S. 1903*. Summary of October 3. 1903, moet1n9 on clean-up of PC0 transformer fire at First National Bank Building. .. Simon S. 19B3b. untitled ms memo dated 12/13/B3, with summary of sampling results from First National Bank, Chicago. ^ Smith R, Solffer B. 1BB3. Big P6 I E explosion - S.F. hlghrlsd shut. San Francisco Chronicle, Nay 16, 19B3, p. 1. Smith RN, O'Keefe PW, Milker DL, et al. 1961a. Analysis of 2,3,7,6 tetrachlorobemofuran and 2,3,7,B tetrachlorodlbenio-p-dloxln In a soot sample from a transformer explosion In Blnghampton [sic]. New York Albany, NY: New York State Department of Health. Feb. 20, 1961. Smith RM, Milker DL. O'Keefe PW, et. al. 1961b. Analysis of a Binghamton soot sample for tetrachlorodlbencofurans and tetrachlorodlbenzo-p-dloxlns. Albany, NY: New York State Department of Health. Oct. 1. 1901. Smith RN, O'Keefe PW, Hllker DR, et. al. 1962a. Analysis for 2,3,7,8-tatrachlorodlbeniofuran and 2,3,7,B-tetrach1orod1bento-p-d1ox1n In a soot sample from a transformer explosion In Binghamton, New York. Chemotphoro, Vol. 11, No. B, pp. 715-720. Smith RN, Hllker DR, O'Keefe PW, et. al. 1962b. Determination of polychlorinated dlbentofurens in soot samples from a contaminated office building. Albany, NY: New York State Department of Health. Narch 1962. Smith RN, Hllker 0, O'Keefe P, et al. 1963a. Determination of TCOFs and TCDDs In air samples from the sixteenth floor of the Binghamton State Office Building. Albany, NY: New York State Department of Health. Narch 16, 19B3. 21 HONS 214106 5. REFERENCES (continued) . Smith RH, Nllker 0. O'Keefe R, ot al. 1913b. Determination of totra-hoxa COFt and tetra-COOs In air samples from tho 11, 14, la and 11th floors of tho Binghamton Stata Offlca Building. Albany. NY; New York Stata Department of Hoalth. Hay 16, 1983. Stalling. 19B1. varsar Now York Inc. 1982. Investigation of tha contamination remaining in tha Binghamton Stata Offlca Building following completion of tho preliminary cleanup. Report submitted to New York Dfflco of Benenl Services. Springfield, VA: Varsar New York Inc., October 20, 1982. Varsar Now York Inc. 1983a. Determination of toxic compounds In sprayad-on colling Insulation: sampling and analysis (RGBs, RCOQs, and RCOFs). Report submitted to New York State Office of general Services. Springfield, VA: versar New York Inc., July IB, 19B3. varsar Now York Inc. 1983b. Oetermination of the ratios of various toxic chemicals on vinyl wall surfaces In the Binghamton State Office Building. Report submitted to New York State Office of general Services. Springfield, VA: Versar Now York Inc., September 26, 1983. Vuceta 3, Harsh JR. Kennedy S, et al. 1983. State-of-the-art review: RCOOs and RCOFs In utility fluid. Ralo Alto, CA: Electric Rower Research Institute. Webber I. 1982. The degradation of polychlorinated bemanes in electrical equipment. Paper delivered at the IECE/RES Conference. New York, NY. Feb. 1-5, 1982. - wegars D. 1983. workers returning to RCB skyscraper. Sen Francisco Chronicle, Hay 26, 19B3, p. 4. i i 22 r HONS 214107