Document DDOmDLVOgB2Q1qrb6d5b0ZVVB
American Society of Heating and Ventilating Engineers Guide1, 1934
for this service. When coils are used, the miter type assembly is to be preferred as it best cares for expansion in the pipe. Cast manifolds or headers, known as branch tees, are available for this constriction.
OUTPUT OF RADIATORS
The output of a radiator can be measured only by the heat it emits. The old standard of comparison used to be square feet of actual surface, but since the advance in radiator design and proportions, the surface area alone is not a true index of output. (The engineering unit of output is now the Mb or 1000 Btu). However, during the period of transition from the old to the new, radiators may be referred to in terms of equivalent square feet. For steam service this is based on an emission of 240 Btu per hour per square foot.
Table 1. Variation in Dimensions and Catalog Rating of 10-Section Tubular Radiators Made by Several Manufacturers
345 6 7
Width of Radiator Length per Section----------
___ Inches --Inches
4.6-5.1 2.5
6.0-7.0 2.5
8.0-8.9 2.5
9.1-10.4 2.5
11.4-12.8 2.5-3.0
Height with Legs--Inches
Heat Emission-- Equivalent Square Feet
13-14
16-18 20-21
22-23 25-26 30-32
36-38
20 28.5
15.0-17.5 20.0-22.5 25.0-31.2 30 20.0-21.3 25 30.0-33.9 35 20.0-26.7 25.0-27.5 32.5-39.8 37.5-40.0 25.0-30.9 33.3-35.0 40.0-48.6 50 30.0-36.7 40.0-42.5 50.0-56,5 60
25.0-32.5 30.0-38.3 36.7-45.0 40.0-45.2
50.0-53.5 63.3-62.5 70.0-75.4
Output of Tubular Radiators.
Table 1 illustrates the difficulty in tabulating tubular radiator outputs since there is so much variation between the products of the different manufacturers. Only on the four-tube and six-tube sizes is there any practical agreement in output value. The heat emission values appear as square feet but are entirely empirical, being based on the heat emission of the radiator and not on the measured surface.
Output of Wall Radiators
An average value of 300 Btu per actual square foot of surface area per hour has been found for wall radiators one section high placed with their bars vertical. Several 'recent tests1 show that this value will be reduced from 5 to 10 per cent if the radiator is placed near the ceiling with Hie bars horizontal and in an air temperature exceeding 70 F. When radiators are placed near the ceiling, there is usually so noticeable a difference in temperature between the floor level and the ceiling that it becomes dif ficult to heat the living zone of a room satisfactorily.
University of Illinois, Engineering Experiment Station Bulletin No. 223, p. 30.
408
Chapter 30--Radiators and Gravity Convectors
Output of Pipe Coils
The heat emission of pipe coils placed vertically on a wall with the
pipes horizontal is given in Table 2. This has been developed from avail
able data and does not represent definite results of tests. For such coils
the heat emission varies as the height of the coil. It is customary to use
an average emission of 100 Btu per linear foot of
pipe, 10 ft high.
The heat emission of each pipe of ceiling coils, placed horizontally, is about
126 Btu, 156 Btu, and 175 Btu per linear foot of pipe, respectively, for
1-in., lJ4-in., and 1%-in. coils. .
Table 2. Heat Emission of Pipe Coils Placed Vertically on a Wall (Pipes Horizontal) Containing Steam at 2X5 F and Surrounded with Air at 70 F
' Btu per linear foot of coil per hour (not linear feet of pipe)
Size or Pipe
Single Row.............................. ............. Two..........-............................................ Four............................................... ..... Six... .......... ..... .................................... Eight.................-.................................. Ten____ ________________ ______ ___ Twelve:................ ......... ......... ..... ........
l In.
132 252 440 567 651 732 812
1KI.
162 312 545 702 796 907 1005
IM Ik
185 348
616 793 907 1020 1135
.
Effect of Paint
The prime coat of paint on a radiator has little effect on the heat output, but the finishing coat of paint does influence the radiation emission. Since this is a surface effect, there is no noticeable change in the convection loss. Thus, the larger the'proportion of direct radiating surface, the greater will be the effect pf painting on the radiation. Available tests are on oldstyle column typie radiators which gave results shown in Table 3.
>/
Table 3. Effect of Painting 32-in. Three Column, Six-Section Cast-Iron Radiator*
Radiator
No.
i 2 3 4
/'
Finish
Bare iron, foundry finish___ ______ One coat of aluminum bronze Gray paint dipped. ___ __ _____ One coat dull black Pecora paint_
Area Sq Ft
27 27 27 27
Coefficient of Heat Trans.
Btu
Relative Heating Value
Pee Cent
1.77 1.60 1.78 1.76
100.5 90.8 101.1 100.0
^Comparative Tests of Radiator Finishes, by W. H. Sevems (A.S.H.V.E. Transactions, Vol.'33,1927).
HEATING EFFECT
For several years the heating effect of radiators has been considered by engineers in order to use it for the rating of radiators and in the design of heating'systems. Heating effect is the useful output of a radiator, in the comfort zone of a room, as related to the total input of the radiator2. :
P 33)Seating Effect of Radiators, by Dr. Charles Brabble (A.S.H.V.E. Transactions, Vol.33, .1927,
409