Heating Ventilating Air Conditioning Guide 1938 Fig. 2. Floor Mounted Unit Heater, Housed Type Fan Fig. 3. Suspended Type Unit Heater, Housed Type Fan 438 Chapter 23. Unit Heaters, Ventilators, Air Conditioning, Cooling Units greatly the piping and loss of floor space due to the heating equipment. Propeller-type units, illustrated in Fig. 1, with outlet velocities of from 300 to 1000 fpm are usually placed from 30 up to 100 ft apart. Two methods of application of unit heaters are commonly used. Floor mounted units, shown in Fig. 2 are available either with or without the air by-pass, and withdraw the cold air from the floor and discharge the heated air above the working zone. Suspended type units are located in an elevated position withdrawing air from this higher level and dis charging the heated air down into the working zone. In closely occupied spaces where direct air drafts into the working zone are not permitted, the floor mounted unit will give more uniform temperature distribution. On the other hand, if opportunity is provided to deliver the heated air from suspended units down into the working zone, excellent'temperature distribution is possible. A suspended high-velocity type unit heater con nected to an outside air intake with damper to control the volume of ventilation is shown in Fig. 3. A wide variety of structural designs is available. All employ some form of convector, supplied with either steam or hot water, although occasionally equipped for gas or electric heat. Air is always forced over these con vectors by a fan of either the propeller or centrifugal type. Heating sur faces may be in the form of steel pipe coils, non-ferrous tubes or pipes with extended surfaces, cast iron, and pressed or built-up sections of the cart ridge or automotive type. AIR TEMPERATURES8 For recirculating heaters with intakes at the floor level, the temperature to be maintained in the room should be considered as the temperature of the air entering the heater. Where outside air is introduced, the tem perature of the mixture must be calculated and used as the entering air temperature to the heater. Where suspended heaters are used without any intake boxes extending down to the floor level, a higher entering air temperature should be used than that at which the room is to be main tained. With suspended unit heaters taking air at some distance above the floor, the temperature variation from floor to ceiling may reach as much as 1 deg for each foot of elevation during the periods when the maximum capacity of the heaters is required. Thus this allowance should be made in calculating the capacity of suspended heaters. High velocity discharge units (blower type) will maintain slightly lower temperature differences than will low velocity units (propeller type). Unit heaters taking in recirculated air at the floor level should maintain temperature differentials of less than 0.5 deg per foot of elevation when the maximum capacity of the heaters is required. This temperature difference per foot of elevation is less than the corresponding variations for spaces heated by direct radiation. `Temperature Gradient Observations in a Large Heated Space, by G. L. Larson. D. W. Nelson, and O. C. Cromer (A.S.H.V.E. Transactions, Vol. 39. 1933, p. 243). Tests of Three Heating Systems in an Industrial Type of Building, by G. L. Larson, D. W. Nelson, and John James (A.S.H.V.E. Transactions, Vol. 41, 1935, p. 185). 439