Document DDBZ4pQVqgBZqJQya7qeqpwXM
Contact: Name: George Sillia Address: The Boeing Company, MC Si00-1195
^ P.O. Box 516, St. Louis, MO 63166 Phone: 314-233-0628 e-mail: george.p.sillia-jr@boeing.com
St. Charles Facilities
Company Information:
.
The Boeing Company in St. Charles, Missouri employs approximately 900 people directly, and purchases parts and services from a host of other local employers.
Acquired by McDonnell Douglas Electronics Company in 1966, the St. Charles facilities now focus primarily on design, manufacture, and support of missile systems. Boeing products manufactured in St. Charles are deployed throughout the world by the United States Armed Services and Allies.
Risk Management Planning
The United States Environmental Protection Agency (EPA) issued a regulation called Risk Management Program (RMP), as required by an amendment to the Clean Air Act. The RMP rule requires facilities with certain quantities of chemicals specifically listed by EPA to disclose particular information. The EPA list includes 140 chemicals that trigger a requirement for Risk Management Planning and reporting, if stored or used in a process in quantities or concentrations greater than the regulatory threshold. Boeing does not store or use any chemicals on the RMP list at levels above the regulatory threshold.
Boeing in St. Charles uses two chemicals named in the RMP list:
Hydrofluoric acid
.
Nitric acid
However, neither of these are stored or used above the minimum quantity and concentration regulated by
the RMP rule.
Because of the low quantities and concentrations of chemicals from the RMP list onsite, Boeing facilities in Missouri are not subject to the RMP rule. The facilities are, however, subject to a General Duty clause of the Clean Air Act. The General Duty clause requires Boeing to identify hazards, prevent releases, and minimize the consequences of accidental releases, regardless of RMP thresholds. Boeing's risk management program for hazardous chemicals is described on the following page.
The RMP rule requires reporting of certain accidental releases from processes subject to the rule. Boeing-^t. Charles had no accidental releases in the last five years that would be reportable under the RMP rule.
Year1994 Number of RMP Releases
1995 1996 1997 1998 0 0 000
Revised: 30 April 1999 DSW 138133
STLCOPCB4038090
General Duty Risk Management Program for Boeing St. Charles
Minimization of Quantities Stored/Concentrations Used Hydrofluoric acid used in St. Charles is received as a 70% solution, but Boeing minimizes the amount in storage to a quantity less than the RMP quantity threshold. When hydrofluoric acid is introduced to the metal finishing process tank, it is diluted to a concentration well below the RMP threshold. Nitric acid is received from suppliers at concentrations below the RMP threshold and is further diluted for use. Acids at lower concentrations pose lesser hazards. Non-RMP fuels and chemicals are stored at Boeing St. Charles, but on-site storage quantities are minimized through just-in-time delivery ofbulk fuels/chemicals, and a Chemical Management Services organization that delivers small quantities ofchemicals to end users two or three times a week. By minimizing quantities of hazardous materials stored, the possibility and severity of any incident is reduced, and the possibility of a release affecting adjacent Boeing operations or off-site persons is also diminished.
Spill Containment Storage tanks, process tanks, and bulk containers of liquid fuels/chemicals are located within permanent spill containment structures, including double-wall tanks, containment pits, dedicated tanks for overflow, berms, curbs, and portable containment buildings.
Inspections of Fuel and Chemical Storage In addition to electronic monitors and alarms on leak-detection systems, fuel and chemical storage areas are visually inspected on a recorded schedule. The inspection schedule requires a visual check on a daily to quarterly basis, depending on the particular area.
Prevention and Response Procedures. Training The Spill Prevention and Response Plan for Boeing St. Louis and St. Charles facilities describes spill prevention measures, response and reporting procedures, spill response equipment stored on site, and measures to mitigate the impact of an incident. Employee training and coordination with outside firstresponders are based on this Plan. The entire Boeing Fire Department and approximately 25 safety, health, and environmental professionals receive 40 hours of intensive training under the OSHA Hazardous Waste Operations and Emergency Response (HAZWOPER) rule. St. Charles pipefitters and other material handlers are provided with 24 hours of H.AZWOPER training. The Boeing fire and security departments are trained in release mitigation, isolation, and evacuation procedures. Boeing is also in regular contact with St. Charles municipal authorities and the Local Emergency Planning Committee to ensure a coordinated response to any incident.
Revised 30 April 1999
OSW 138134