Electric Power
Research Institute
Topics: PCB Chtmlcsl analysis
Fires Transformers Pollution control Insulstlng oils
EPRICS/EL-4104 Project 2028 Proceedings July 1085
Workshop Proceedings: PCB By-product Formation
Pteparedtoy
Elaotrlo Powar Reeeareh Institute
Palo Alto, California
HONS 215556
REPORT SUMMARY
SUBJECTS Transmission: Substations / Distribution: Substations / Hazardous/tomc substances
TOPICS
PCB Chemical analysis Fires
Transformers Pollution control insulating oils
AUDIENCE Environmental scientists and managers _
Workshop Proooodlngs: PCB By-product Formation
Fires Involving PCB-fllled transformers occur Infrequently, but concern exists about the release of potentially toxic combustion by-products. Responding to proposed ERA regulations on PCBfifled building transformers, experts gathered to review current information on the partiai-oxfdatfon products of PCB.
EAR) C&/EL-4104I
BACKGROUND
In March t864, ERA announced Ita Intention of drawing up regulations to cover polychlorinated biphenyl (PCB) tires In electric transformers. A prelimi nary version of the proposed ERA rules was prepared, and public hearings ware scheduled for January 1985. Before final regulations were determined, EPRi sponsored a workshop to maks avallabla the moat current knowledge on PCB fires and research.
OBJECTIVES
to compile the latest information and review the current research on the effects of fires In PCB-flHed transformara--Including PCDF formation, chem ical analyses, risk assessment, and cleanup ttchniquea.
APPROACH
Twenty-seven papers dealing with PCB conversion were presented at the EPRI workshop In December 1984. The agenda called tor three background presentations and four halfday sessions focusing on ft) analysis of poly chlorinated dibenzofurans (PCOFa) and polychlorinated dlbenzo-p-d>oxins (PCDDe); (2) pyrolysis and combustion; (9 flies, pills, and cleanup; and (4) risk assessment. More than 70 representatives of ERA, EPRi. the chemicel Industry, major equipment manufacturers, utilities research organizations, and universities participated in the meeting.
RESULTS
The presentations covered a wide range of PCB conversion subject*.
Including improved approaches to sample preparation and PCDF analysis:
advances in decontamination techniques and preventive measures that would decrease accident response time and costs: and the implementation of risk assessment and risk minimization technique*. There was agreement that an improved understanding of PCB pyrolysis and combustion under varying conditions would provide Ineight Into designing Installation* tor minimum risk. Participants also agreed that battar methods of assessing risk would lead to the establishment of more realistic risk levels. As a result, substantial cost reduction* could be achieved.
HONS 215557
EPRI PERSPECTIVE
This workshop provided a useful opportunity lor experts in PCDF analysls, PCDO analysis, and PCB combustion problems to exchange cur rent. reliable information that should be of significant value to those charged with the responsibility of establishing PCB regulations. The discussions indicated that there is a naed for more accurate chemical analyaea. more realistic risk assessments, and more limeiy and efficient decontamination and cleanup following spills and fires.
A new report on a related EPRI protect Is now available: CS-4024, Design Manual tor Reducing Airborne PCB Contomlitttfon.
PROJECT
RP2028 EPRI Project Managers: Ralph Y Komal; Q. Addis Coal Combustion Systems Division; Electrical Systems Division
For further information on EPRI research programs, call EPRI technical Information Specialists <4i5j 56-2411.
RONS 215558
Workshop Proceedings; PCB By-product Formation
C$/EL>4>04 Research Project 2028
Proceedings, July 1965 Palo Alio. California December 4-6, 1964
Edited by R. Y. Korns*. Coal Combustion Systems Division
G. Addis. Electrical Systems Division
Electric Power Research institute 3412 Hiltview Avenue
Palo Alta California 94304
EPRl Project Managers R. Y Komai
Heat, waste, and water Management Program Coat Combustion Systems Division
G. Addis Ttansmisalon Substations Program
Electrical Systems Division
HONS 215559
ORDERING INFORMATION Requests tor copies o< tnis report should ba directed to Rasaarcn Raports Cantor (RRC), Box 50490, Palo Alto, CA 94303. (4151985-4001. Thora ia no Charge tor raport* roQuastod by EPfli member utlliua* and affiliates. U.S. ullllly associations, U.8. government agencies (fadaral, atata. and local), madia, and Foreign organiiattona with which EPftl ha* an Information exchange agroomont. On requoai, RRC will sand * catalog of EPW taporta.
Cmv Itas Claeiflc taw taeaereh Meiittaa. Me M rtfnta mmM
NOTICE
Thu noon im onsM ay it* Electric taw research Matituie. Me Utah Neither tXta. marneera el tta no> any person acting an inert Penan: (a) mease any warranty, enemas or aneaad. watt reeoect to eta uee el any tnlormeiion. apperstue. memo*. at pracees etactoaaC m tree report or that aver uaa may "PI tnaatpe etimiWy ewneaiifhia or(Maaaumaaanymwmmwithroeeictiemauaaai.erioroantapesisjumjtwmaiaimeei. any miotmatton. apparatus. malhod. or praceea Mctoaad at am report
HONS 215560
abstract
The EPR1 PCDF workshop was held to assemble current data on PCB fires, a subject of vital Interest to the Electric Utility Industry. It was ttmed to precede the public hearings on the EPA's proposed regulation on PCS ftres. It Is hoped that some of the ideas expressed were useful Input to those active at the hearing. Four half-day sesstons covered Analysis, Pyrolysts and Combustion, Documentation of Fires, Spills and Clean-up, and Risk Assessment.
MONS 215561
Ill
ACKNOWLEDGMENTS We would like to acknowledge the help or our session chatreen, Jacques Guerttn, Marcus Cooke, Brian Nest and Vic Nlemeyer, Ellen Lanua provided excel 1ant aeetlng arrangements. Other EPR1 personnel who helped were;
Gary Cobbley Barbara Cole Eleanor Keith Kay Kidd Thanks to all.
HONS 215562 v
contents
SactIon
PART 1: BACKGROUND
1. TPRl't PCB Intardlvlslonal Task Force Naratn Htngoranl (EPRI) (no paper available)
2. Regulation Development Process as tt Appltes to PCB Denise Keehner (USEPA) (no paper available)
3. Cost-Effectiveness Analysts of the Proposed Rule For Indoor PCB Transformers - Aaty Moll
Page 1-1 1-3 1-5
PART 2; ANALYSIS - JACQUES GUERT1N - MOOERATOR
4. Factors Affecting the Rellabtltty of Quantitative Analyses for Chlortnated Olbenzodtoxins and Dtbenzofurans In PCB-Contalntng Transformer flutd* and Their Products of Combustion T. 0. Tternan, M. L. Taylor, J. H. Garrett. H. 6. Solch, G. F. Vanness, D. J, Wage!, T. Mazer and 6. Renal Ingam
5. Mathematical Modeltng of the Physical Properties Used tn the Analysts of PCDFs F. D. Ktleman, M. 0, Hale, T. Mazer and R, W. Noble
6. Formation of PCDO and PCOF In Askarel and Contaminated Mineral Oil Equipment - Fred L. De Root, Marcus Cooke, G11 Addis, Ralph Konal and Jacques Quartin
7. Chiorodtbenzofuren Analysis Ustng Two-0tmenstonal Gas Chromatography-Mass Spectrometry - Moodftn v. Llgon, Jr. and Ralph J. May
8. PCOF Isomers and Isomer Levels Found in PCBs Christoffer Rappe, Lars-Owe Kjeiier and stall an Marklund
2-1
2-9 2-12 2-16
2-20
PART 3: PYROLYSIS AND COMBUSTION - MARCUS COOKE - MODERATOR
9. Format ton of Polychlorinated Dlbenzo-p-dloilns and Dlbenzofurans From Burning of StHcone Dielectric Fluid Spiked with Polychlorinated Btphenyls - Jon M. Swanson and Thomas 0, Tternan
3-1
HOMS 215563
vll
Section
Page
10. Simulated Building Fire Study Using RetroflUed Transformer
3-9
Dielectric Coolant - Marcus Cooke. Fred L. Oe Root,
Bruce Rlt.lng, William H. Mtrtin, Christoffer Reppe end John S leybeck
11. Fometion of PCDFs under "Optimized" Combustion Conditions _ From Low-Level PCB Dielectric Fluids - Mitchell 0. Erickson, ~ Christopher J. Cole, Jeirus 0. Flore, Jr., Peul G. Gormen, Clerence L. Haile, Gery o. Hinshew, Fred C. Hopkins, Stephen E. Swenson end Deni el T. Heggem
3*13
12. Leboretory Investigation of the High-Temperetur* Formation end Destruction of PCDFs - Berry Dellinger, Wayne A. Rubey, Dougles L. Hell end Sueenn L. Mezer
3-17
13. Products of Incomplete Combustion of Dielectric Fluids C. Clelr Clelborne
3-21
14. Pyrolysis end Cosfcustion of Minerel Oil, Tetrech lorethylene end Silicone Oil Mixtures Conteining Aroclor 1254 George Eedon
3-24
15. Formetion of PCDFs From PCBs - ChrlstOffer Reppe, Stellen Merklund end Lers-Owe Kjeller
3-2B
PART 4: DOCUMENTATION OF FIRES, SPILLS AND CLEAN-UP - BRIAN WEST MODERATOR
16. Decontemlnetion of Fire Fighters' Protective Clothing with
4-1
Trichlorotrifluoroethene John R. Komlnsky end Eugene T. Mcllveine
17. Avellebie PCDF Decontemlnetion Technology end Its Ability to Meet Stenderds - John Woodyerd
4-13
IB. Preventetive Meetures for PCB Risk Reduction In Buildings Brlen W. West, Werren G. Hensen end Weston A. Fenner
4-IB
19. Fires Involving PCBs: Effectiveness of Cleaning Procedures end Quelity Control Requirements - Robert West in
4-23
20. Fires in Electrlcel Equipment Containing PCBs; Recommendetions 4-31 for the Prevention of Contemlnetlon by PCDFs - Jeen M. Cerbonneeu
21. Correlation of Transformor/Cepadtor PCB Content with Soot Contaminants Generated In e Fire Incident - Paul E. des hosiers
4-46
22. Decontaminating Service Equipment Exposed to PCB Electrical Fires or PCB Liquids K. C. Ashley
4-4B
PART 5; RISK ASSESSMENT . VICTOR NIEMCYER M00ERAT0R
23. The Binghamton State Office Building - Nancy K, Kim end George Eedon
24. PCB Exposure Assessment end Spill Clean-up Stuart M. Brown end Scott H. Boutwell
$-1 5-6
vl 11 MOMS 2155*4
Section
25. Utlllzetlon of Quentietlve Risk Assessment Techniques In the Development of Decontenlnetlon Stenderds (A cse Study Sen Frtnclseo. Celifornle) * Rieherd L. Ude
26. The Use of Anelytic Models in Requietory Risk Menegement Anelysls of PCB Equipment - E. Victor Nlemeyer
~
27. Comptretlve Trensformer Fire Risk Assessment - Reymond f. Boykin end Nerdyros Kezeriens
Peoe S' 16
5-24 5-26
APPENDIX List of Pertlclpents
HONS 215565
lx
PART 1: BACKGROUND
HONS 215566
EPRI'S PCB INTERDIVISIONAL TASK FORCE NARAIN H1NGORANJ EPRI
Piper not mlliblt it tine of publication.
HONS 2155^7
REGULATION DEVELOPMENT PROCESS AS IT APPLIES TO PCS DENISE KEEHKER USEPA
Paper not available at time of publication.
HONS 21556a 1-3
COST-EFFECTIVENESS ANALYSIS OF THE PROPOSED RULE for iNbooft PC6 TRmSfffahEfiS -------------------
Amy Moll
USEPA - Office of Toxic Substances Regulatory Impacts Branch
EPA's Office of Toxic Substances preoared a cost-effectiveness analysis for the proposed rule regulating the use of indoor PCS trsnsformers. The analysis estimated the cost-effeotlveness of a number of regulstory alternatives to reduce the risks associated with Indoor PCB transformers.
The following alternatives were analysedi
- 15 year. 10 year, and 5 year phase-out of Indoor RCB askarel trsnsformers
- Retroflll of Indoor PCS askarel transformers within one year to less than 500 ppm PCBs
- Physical isolation of each Indoor PCS askarel transformer by 1937 and by 1939 (Isolation Is defined as the physical enclosure of a transformer In a sealed vault or smokeproof barrier)
- Inspection of Indoor PCB askarel trsnsformers for Incipient failure on a quarterly basis
- installation of increased electrical protection on each Indoor PCB askarel transformer
- Installation of external electrical switches st each Indoor PCB askarel transformer location
- Labeling each indoor PCB askarel transformer location for lndentlflcation by fire or emergency responee personnel
- Registration of each Indoor PCB askarel transformer with the local fire department.
The eetimated ooate include direct labor and capital costs ss well
as ehanqes in transformer operating costs. Benefits Include) 1) a reduction in the number of catastrophic events resulting from PCB transformer fires or failures. 2) clean-up costs associated with PCB transformer fires or failures, and 3) a reduction In PCBs released to
the environment. The only benefits measure which we attached a dollar
value to waa avoided cltan-uD costa. Costs and benefits were
estimated on an Incremental basis using a base case of an indefinite
use authorisation of PCB transformers with quarterly Inspections.
The cost-effectiveness measure used to summarise cost and benefits calculations west
Cost-effectiveness
Net Cost
Avoided Catastrophic Events
'
1-1 MQNS 215569
where; Net Cost Coat of Reguletlon - Cleen-up Coats Avoided
In addition, the reduction in PCBa ralaaaad to the environment was calculated for aach alternative where sufficient data was available.
There were many data gaps and uncertainties In the data used to estimate tha effectlvenesa of risk reduction alternatives, we did not attempt to estimate the effectiveness of the following regulatory alternatives because of a lack of data* 1) a requirement to Install Increased electrical protection, 2) a reculrament to lnetall external cut-off switches, and 3) labeling and registration of Indoor PCB transformers.
Following Is a summary of the results of the coet-effeetlvensss analysis! (See attached table)
- Total regulatory costa range from $5.2 million for registration of Indoor PC* transformers with local fire departments to $1.5 billion for retroflll of all Indoor PCB transformers,
- When avoided clean-up costs are considered, net regulatory coats are reduced from 4 percent (for the lnapectlon alternative) to 5$ percent (for the 3 year isolation program).
- For all indoor PCB transformers the cost-effectiveness of regulation ranges from $5.46 million per avoided catastrophic event for an Isolation program Implemented In 5 years to $166 million per avoided event for quarterly inspection.
- The estimated cost of the proposed alternative is $612 million. The proposed alternative Includes the following provlslone t
- Immediate registration of all (Indoor and outdoor) PCB askarel transformers with fire departments,
- marking of all (Indoor and outdoor)'PCB askarel transformers with labels on the exterior with labels on the exterior of the vault, grate, door, etc,,
' - Immediate registration of PCB askarel transformers In or near buildings with building owners,
- Installation of additional protective devices on PCR askarel transformers with higher secondary voltages, and
- Isolation of all PCB sekarel transformers In or near buildings over s three-year period, including preparation and retention.
Following are the major assumptions used to make these estimatesi
MONS 215570 1-6
The total annual fallura rata (Including catastrophic and noneataatrophle failures) la .2 pareant par year. Tha catastrophic fallura rata is .003 pareant par yaar. 47.7 pareant of noneataatrophle falluras raault In a spill of PCB fluid. 25 pareant ''I eontalnad voluaa Is lost In a spill. Tha claan-up cost for a catastrophic fallura la 520,000,000. Tha total number of Indoor PCB transformers at tha and of 1984 la 104,284. 50 pareant of tha Indoor PCB aekerel transformers operate at a higher secondary voltage (480/227 volte). Preparation and retention of a plan for Isolating each transformer was estimated to coat $280 par Isolation.
HONS 215571
*-l
fttt OHl
1H1 Ml
(Nlllw f Mlint
M.K
tlt i,m,47
l.ttl.M
417,1*
l*v toclftwt Mlw
4*4.79 Ut.tl
M.1T
7>.*4
m
Ut
WtAl
OHt IwlM (HIM
4 Mltnl
Mtflt mmw Util
WMf^tle tiM MlM
<*>11 4 IMUI
Mil 904 INImm
NM4 (MtM
OJI
19.41
>14,9*1
m.N
>4.41
M1.1M
1MM N5.M
ll.H 4T.44
1,19* 447. JM
m.ii
34,44
, IM
m.n 34* n
Nft
!t 4.77
m
i4. m 4
m
Nft m m
m mm
m mm
OMfc* ..............................
M (Mt
OlMtraftk
M CMt
h *Pt tiiliil
iMIliaM of ttllMil
mmiM of HlUwt/lHitl
341,43
13.77
3*1.7*
19.41
l.iil.H 1, 114,3*
194.44
IM5 31.M 9,4*
>14.14 7*1.34
m m m
4.44 144.14
-
m 4ft
INI prHMi
MlAf It pwe
HONS 215572
PART 2: ANALYSIS JACQUES GUERTtN - MODERATOR
HOMS 215573
FACTORS AFFECTIHG THE RELIABILITY OF QUANTITATIVE
analyses for chlorinated oibenzooioxins and
oibenzofurans in pcb-containing transformer
fluios ano their prooucts of combustion
T. 0 TIERNAH, M. L. TAYLOR. J. H. GARRETT, H. G. SOlCH, G. F. VANNESS. D. 0. UAGEL. T. MAZER AND B. RAMALINGAM
BREHM LABORATORY ANO DEPARTMENT OF CHEMISTRY UR1GKT STATE UNIVERSITY DAYTON, OHIO 454JS
The Sequence of analytical operations which Is usually applied In characterizing and quantitating polychlorinated dlbenzo-p-dloxlns (PCDDs) and dlbenzofursns (PCOFs) In PCB-contalnlng samples Is as described in the Following.
SPIKING OF SAMPLES
Reliable quantltetlve analyses to determine trace levels of PCOOs and PCOFs in any sample require the utilization of Internal standards which are added to the samples prior to analysis In known quantities. Ideally, itotoplcally-labelled PCOOs and PCOFs are used for this purpose, since they are expected to closely mimic the native PCOOs/PCOFs already present in the sample In terms of their chem. leal behavior and the efficiency with which they are extracted from the samples and ultimately recovered through the various clean.up procedures applied to the samples. At the same time, these labelled PCDOs/PCDFs give mass spectral responses at different ion masses than those monitored as indicators of the corre sponding native compounds. By using the observed signal responses for the native compounds relative to those observed for the labelled compounds at the basis for quantitation, much more accurate quantitative results are thus obtained. While Ideally, It would be desirable to utilize a labelled PCDO and PCOF Internal stan dard for each chlorinated class to be determined, this 1$ not practically possible at present because of the limited availability of such standards. A set of labelled standards which Is presently recommended for use Includes l3ClrZ,3,7,8-TCOD, l3Clz-2,3,7,8-TC0F, uCirl,2,3,4,7,8-HxC0D, 13Cirl,2,3,4,7,e-MKCDF, 13C1Z-OCOO and l3C1?-OCOF. With this approach, the labelled TCDD and TCDF are used as the representative standards for mono-, di-.
MOMS 2L5S7* 2-1
tM- and tetra-CDDs and CDFs, the labelled HxCDD and HxCDF are used at tne repre
sentative standards for penta- and hexa-CDDs and CDFs, and the labelled DCDD and
OCDF are used-at the representative standards for hepta- and octa-CDDs and CDFS.
In general, the fewer the number of internal standards utilized, the lets reliable
are the quantitative results obtained In such analytes.
'
EXTRACTION DF PCDDS AND PCDFs FROM THE SAMPLE MATRIX
Solid samples (solIt, combustion particulates, surface wipes) are generally extracted In a Soxhlet apparatus with toluene (or benzene). Tests of the effici ency of extraction of spiked samples have shown that the most efficient extraction It achieved with this solvent and an extraction period of 12-16 hours.
PRELIMINARY FRACTIONATION DF THE SAMPLE EXTRACT AND ELIMINATION OF PRELIMINARY MATRIX CONSTITUENTS AND OTHER CHLDR1NATED RESIDUES
Table 1 shows a series of fractionation and liquid chromatographic column proced ures which are efficacious for the concentration of PCDDs/PCDFs In the sample extract, while concurrently removing other major constituents of the matrix (oil, PC8s and other chlorinated compounds). In order to demonstrate that such proced ures yield good recoveries for PCODs and PCDFs, and that quantitative analyses using these methods are accurate. It Is necessary to process typical sample extracts which have been spiked with a representative set of these compounds through these procedures, Data obtained in such experiments Is also shown in Table 1, and indicates that with proper selections, good recovery of PCOOs/PCDFs representative of the entire chlorinated spectrum can be achieved.
GC-MS ANALYSIS OF SAMPLE EXTRACTS
6C-MS analyses of sample extracts to measure quantitatively the levels of PCDDs/ PCDFs are based on the premise that complete gas chromatographic separation of each chlorinated class of these compounds can be achieved, so that a unique set of mass spectral indicator ions can be monitored for each of the appropriate DC retention time windows. If the objective of the analysis is to obtain data on the concentrations of PCDOs/PCDFs by total chlorinated class (that Is, total tetra-, penta- and so on), then complete separation of the Individual isomers of each class is not required. For such analyses, a 60-meter fused silica Ob-5 capillary column has been shown to be a particularly good choice as the GC column, because when properly temperature-programed, this column yields resolution of each of
HONS 215575 2-2
the chlorinated groups of PCDDs/PCDFs from the other chlorinated groups and permits analytes of the entire tetra- through octa- groups from a single extract injection in about 75 minutes. The sequences of GC and MS operating parameters required for such analyses are shown In Table 2.
calibration standards
Rigorous quantitative analyses of PCDDs/PCDFs requires that GC-MS response factors be determined for an appropriate set of PCDD and PCDF Isomers using pure standards of known concentration. An appropriate set of such standards should Include representative isomers from each chlorinated group of PCDOs/PCOFs which Is to be determined in the analysis. Use of an appropriate group of Isomers for this purpose permits one to also simultaneously define the GC retention time windows for each chlorinated class of PCDDs/PCDFs.
CRITERIA APPLIED TO GC-MS DATA TO ENSURE RELIABILITY
In order to identify specific PCDO/PCDF in samples analyzed, the GC-MS data obtained mutt satisfy the following criteria:
a. Mass spectral responses must be observed at both the molecular and ' fregment ion masses corresponding to the ions indicative of each chlorinated class of PCDD/PCDF Identified (see Table 2) and Inten sities of these Ions mutt maximize essentially simultaneously (within t 1 second). In addition, the chrometographlc retention timet observed for each PCOD/PCDF signal must be correct relative to the appropriate stable-isotoplcaiiy labelled internal standard and must be consistent with the retention time windows established for the chlorinated group to which the particular PCDO/PCDF Is assigned.
b. The ratio of the Intensity of the molecular ion (M)+ signal to that of the (Mr2)+ signal must be within t 201 of the theoretically expected ratio (ror example, O.FF In the case of TCODs therefore the acceptable range for this ratio is 0.62 to 0.92).
c. The intensities of the Ion signals are considered to be detectable if each exceeds the baseline noise by a factor of at least 3:1. The Ion Intensities are considered to be quantitatively measurable if each ton intensity exceeds the baseline noise by a factor of at least 5:1.
d. For reliable detection and quantitation of PCDF it Is also desir able to monitor signals arising from chlorinated diphenyl ethers which, If present could give rise to fragment ions yielding ton masses Identical to those monitored as indicators of the PCDF. Accordingly, In Table 2, appropriate chlorinated diphenyl ether masses are specified which must be monitored simultaneously with
2-3 HONS 215576
the PCOF Ion-masses. Only when the response for the diphenyl ether ion. mess It not detected et the seme time el the PCOF ion men can the signal obtained for an apparent PCOF be considered unique.
e. Measurements of the concentration of the congeners In a chlorinated class using the methods described herein is based on the'assumption that all of the congeners are Identical to the calibration stan dards employed In terms of their respective chemical and separation properties and in terms of their respective gas chromatographic and mats spectrometrlc responses. Using these assumptions, for example, the 13Ci2-,3,7,8-TCD0 Internal standard Is utilized at the Internal calibration standard for all of the 22 TCDO Isomers or congeners. Furthermore, the concentration of the total TCDO present In a sample extract is determined by calculating, on the basis of the standard procedure outlined above, the concentration of each TCDO Isomer peak (or peaks for multiple TCOO Isomers, where these coelute) and these Individual concentrations are subsequently summed to obtain the concentration of "total" TCDO.
f. Frequently, during the analysis of actual sample extracts, extrane ous compounds which are present In the extract (those organic compounds not completely removed during the clean-up phase of the analysis) can cause changes In the liquid and gas chromatographic elution characteristics of the PCDO/PCOF (typically retention times for the PCOO/PCDF are prolonged). Such extraneous organic compounds, when Introduced Into the mass spectrometer source may also result In a decrease In the sensitivity of the MS because of suppression of Ionization, and other effects such as charge transfer phenomena. The shifts In chromatographic retention times are usually general shifts, that Is, the relative retention times for the PCOO/PCDF are not changed, although the entire elution time scale Is prolonged. The analyst's Intervention In the 6C-MS operating sequence can correct for the lengthened GC retention times which are sometimes observed due to the presence of extrane ous organics In the sample extract. For example, using the program outlined In Table 2, If the retention time observed for 2,3,7,8TCOD (which normally Is 19.5 minutes) Is lengthened by 10 seconds or more, appropriate adjustments In the programming sequence outlined in Table 2 can be made, that Is, each selected ion monitoring program Is delayed by a length of time proportionate to
. the lengthening of the retention time for the Z,J,7,8-TC00 Isomer, in the case of Ionization suppression, this phenomenon Is Inherently counteracted by the Internal standard approach. However, if loss of sensitivity due to ionization suppression is severe, additional clean-up of the sample extract may be required In order to achieve the desired detection limits.
QUALITY ASSURANCE/QUALITY CONTROL PROCEDURES
Quality assurance and quality control In these analyses are ensured by the
following provisions:
a. Each sample analyzed is spiked with stable Isotoplcally labelled Internal standards, prior to extraction and analysis. Recoveries obtained for each of these standards should typically be In the
HONS Z15577 2-4
range from 60-90*. Since these compounds ere used as true internal standards however, lower recoveries do not necessarily invalidate the analytical results for native PC00/PC0F, but may result in higher detection limits than are desired.
b. Processing and analysis of at least one method blank sample Is
accomplished for each set of samples (a set being defined as 20
samples or less).
'
c. tt is desirable to analyze at least one sample spiked with repre sentative native PCOO/PCDF for each set of 20 or fewer temples. The result of this analysis provides an Indication of the efficacy of the entire analytical procedure. The results of this analysis will be considered acceptable if the detected concentration of each of the native PC00/PC0F is within t SOX of the known added concen tration.
d. At least one of the samples analyzed out of each set (of 20 samples or less) Is analyzed In duplicate and the results of the duplicate analysis are Included In the report of data.
HOMS 215578 2-5
Table 1
RECOVERY OF PCOO/PCOF SPIKES FROM CONTAMINATED SOIL MATRIX CONTAINING PCNs, PCBs. CHLORINATED PARAFFINS, ANO HYDROCARBON OILS FOLLOWING APPLICATION OF VARIOUS CLEAN-UP PROCEDURES TO SAMPLE EXTRACT
PCOO/PCOF SPIKED
Base and Acid rrfwiinn
t OF SPIKEO RECOVERED
Acid, Base, Neutral Silica Colunr
Alualna CoIuac
PX-21 Carbon Carbopack C Carbon
ColiMn"
Coluan*
2,4-01C0f 2,7-01GOO 1,2,4-TrlCOO 2,3.7,8-TetraCDF 2,3,6,8-TetraCDF
1,2,4,8-TetraCOF
1.2.3.4-TetraCOO 2.3.6.8-TetraCOO 1.2,4,7,8-PentaCDF 1,2,3,7,8-PentaCBO 1,2.4,6,7,9-HexaCOF 1,2,3,4,7,8-MexaCOO
1,2,3,4,6,8,9-HeptaCDF OCDF OCOO
67 46 84 95 98 92 92 95 99 99 96 99 96 98 98
108 83 83 101 85 80 99 96 90 98 99 98 99 101 96 97 93 92 94 99 99 100 94 95 101 96 98 100 96 103 98 91 97 101 93 100 98 88 94
98 91 89 109 94 83
0 0 0 70
32 39
62 86 97
98 98
85 66 0 0
. Hexane extract In contact with 40X KOH for 1 hour, followed by contact with concentrated H^SO^ for 1 hour.
b. Colwn containing lg 8I0-SII-A (100/200 aesh) 2g 8I0-SII-A containing 30t (H/H) H,S04, 2g Blo-SIl-A containing 40X (N/M) KOH, and lg BIo-SIl-A eluted with total of 90 at of hexane; Olo-SlI-A Is activated at I80*C after series of solvent rinses.
c. Bio-Rad AG-4 Acid Attains, Activated at I90*C, eluted with 65 aL hexane, 20 aL POX aetbylene chloride-In-hexane, and 15 at aethylene chloride, collecting only last fraction.
d. 18t Amoco Px-21 activated carbon on (elite 545, eluted with 1 aL hexane, I aL aethylene chloride: Cycohexane (1:1), and 2 aL, 20X benzene In ethylacetate, then reverse eluted with 4 aL toluene.
e. Carbopack C alxed with Cellte 545, activated at I30`C, eluted with 2 al hexane, I at cyclohexane, aethylene chloride (1:1), 1 aL of aethylene chloride: aethanol: benzene (75:20:5) and 2 aL toluene, collecting last fraction.
HONS 215579
SEQUENCE OF OPERATIONS IN GC-KS-DS QUANTITATION OF COOs/COFs IN EXTRACTS OF ENVIRONfCNTAL SWLES
tiarsa* Tint (l) taant
o.oo lnjacttaa, nmtoss
1.00 in on vlll <hn 1.00 (apt* too*. pr*fm to OTC t.00 Qpaa cotoao f too to oott saactn 7.00 CslHO la^aratva OoM 14.00 Start Tatra 7ro*m; otaap
MO ppa; ttaa/aais * o.oo toe.
77.00 Stop Tatra Frofran 22.SO Start NtU Fraprn; otaap -
M K tlon/nats 0.17 sac.
71.00 Oaoto taop. tiara to 2' 74.00 Caiasn l^arttn OoM
17.00 Stop Mi Fraprn 17.10 Start Non Oiaorao; snap
MO pm ttae/aa 0.70 sac.
OC Colton taplulaii
t*e)
Iam Nanttorcd
Tnpcratw*
Frap B lilt (*C>tn)
kx Hass Spoctmeti
(/H
lamtttp at fraaaant Ion
ClMpOtP^S NanltaraO
appraxlnate Thcoratlc*)
(at to of lN|*;|n*2|*
ISO
ISO
ISO S
71S 5
770
740.SM 7S0.SM 301.S07
m-axir |N-C0tl|* |Nl* .
ICOf 1COO icor
0.77
J09.Pt*
31S.S47 31S.OI7
IWI* INI* ("1* ,,
S'*
0.77
121.OH 327.SOS
lour mi*
gU
111.S17
ini*
173.040
|N|*
770
770 7K
i
274. OSS
210.OM 117.041 nt.sto 1S1.0S0
iIoN--cCoOcCuII!* ini*\ |N7|* INI* ^
(tCOf HCSO FaCor MO FaCSO
0.41 0.41
MS.OSS 4(7.001
IlN"*I**
HCSO NpOFf*
275
110.0S7 124.017 171.071
m-eocii* in-cocil* INI* t
mar NaCOO near
l 1.21
375.071 3(5.041
|N2|* INI*
Sr*
as.su ai.su
(N|* IN.7I*
nans
1.21
411.054
|N|*
441.751
|N|*
215580 HQHS
Table 2 (Continued)
SEQUENCE OF OPERATIONS 1 COOs/CDFs IN EXTRACTS
(hpiri flat (N toant
SC CebM* Teeperatgre
rc)
ittra CC7W)
Ions Ntnltored kj Halt
batroKtr
Wi)
Idmttty of Fragout Ion
Monitored
dpproitmite Theoretical
Hello of mrjpbtr
JJ.00 30.00 47.10 43.00
Oette tao. poo* to lire
CoImm l^altoa kola Stef Haas Preprgi
Start tapla Propra; aeaap ISO k tOM/antt 0.30 soc.
13.00 Stop Ikpu Propr* 13.10 Start Orta Propeio; Mnp
MO ppa; t tat/nu 0.30 ttt.
14.00 Otf In tao. prr*o to 77r 10.00 Cam tapiritw kola
0.00 0.00 71.00
71.00
Stap Oct* Propr* imto ti. inr* or Caban u^rtfan laM
Col Cam to MO*
73$ ISO 710
210 0 710 7)0
770
344.010 310.013 4(7.707 4W. 7)9 473.7)7 471.774 477.770
370.740 314.774 441.717 443.740 413.777 417.710 410.711 400.771 471.774
111.Ml
Mt-cocn! IM-CKII* ir ~ |0*7|* im*. (0*71* l*I
m-cocti* IMKM* im*. |M*7|* mu* (Ml* f"*7|*
mu* |M*7|*
l"l*
NpCOF MpCSO NpCOF NpCOF MpCSO MpCSO WPt*
OCSf 0C00 OOF
1Jt17"oar ocoJ
VP
*U* OOPC*
1.03 1.03
0.44 0.M
%Mft, mt, aon. OOPF, OOPC oro akOrae latlont nktck ^ltyte (roofoctlroljr) koeathlaro-. Kepttrhlore-. rtln-i
amrklaeo-. and Paceckloroaipfcenrl ttfeert.
,
Ike pg--ten pltoa tor* or* applicant far a 40-oeter feted silica cool Karp SC Iimi coaled 1th DO S.
HONS
mathematical modeling of the physical PROPERTIES USED IN ANALYSIS OF PCDFs
F. D. Hileman, M. D. Hale, T. Mazer*, and R. W. Noble
Monsanto Company Dayton Laboratory 1515 Nicholas Road Dayton, Ohio 45418
INTRODUCTION
The analysis of polychlorinated dlbenzofurans (PCDFs) has always been difficult due to the many possible arrangements of chlorines about the two aroaiatlc rings which can yield 135 possible congeners. This analytical difficulty arises from the need to Identify a particular congener which may be present in a given matrix. The physical property most widely used to Identify a given PCOF congener Is Its gas chromatographic retention behavior. A variety of parameters have been used to characterize this behavior. These Include relative retention to 2,3,7,8tetrachlorodlbenzofuran (1,2), relative retention to lindane (3) and relative retention to various esters of 1,3,5-benzene tricarboxyl 1c acid (4). When analyzing for series of compounds with a wide elution range, such as the PCDFs, the use of a single reference compound is not as desirable at using a series of Indexing compounds which elute quite closely to the PCDF being Indexed. The Kovats retention Index system (0,6) Is based on a series of straight chain hydrocarbons and can be adapted"to temperature-programed conditions 0 which were used In this work to assign retention Indices to all the PCDFs tut had been prepared.
Once Indices were assigned to the PCDFs, a mathematical model was devised based on molecular structure to explain their elution behavior. Regression techniques were used to derive quantitative relationships between these structural parameters and the retention Indices. The model could then be used to look for PCDFs that were outliers, or did not agree with the predicted retention Index derived from other PCOFs. Furthermore, the model could also be used to predict the retention indices for PCDFs that had not been synthesized.
EXPERIMENTAL
The PCDFs were prepared by the carefully controlled oxidative degratlon of Indi vidual polychlorinated biphenyl (PCB) congeners (8). In certain Instances a selected PCOF was Isolated using normal and/or reverse phase HPLC. The Isolated PCDF could than ba alther chlorinated using antimony pentachlorlde or dechlorlnated using UV photolysis (9) to form additional PCOF congeners.
Retention indices were determined on e 30 meter JAW DB-5 ceplllary column. A Hewlett Packard 5 6C/H5 lyitW Wit used to diUet both tha alutlng PCDFs And norttl hydrocarbons. Tha column was progrenned in a fashion such that the hydrocarbons were alutlng linearly In the range of monochioro through octaehl orodl benzofuran.
MODEL DEVELOPMENT
The development of a mathematical modal began by dividing tha PCDF through blphanyl and athar llnkaga to form two synnatrlcal halvas. Tha retention Index would then be a sum of the derived Index for each helf. A similar ap proach has been used for modeling PCBs (10). To assist In this aodal develop-
2-9 HONS 215582
went, the PCOFs were renumbered replacing the convention*! 6, 7, B end 9 with 4', 3', 2` end T, respectively (11). This scheme emphasizes the sym metry of the molecule end greatly simplified the model development.
Through repeated data analyses, a series of variables were established repre sentative of various structural properties of the PCOFs. These variables included the number *d position of the chlorines about the aromatic rings and the relationship of these chlorines.to each other (i.e.. ortho, aieta and para), in the final model development It was necessary to include two varlables involving the 1 and 1` as well as the 4 and 4' positions to describe the Interaction of the two rings with each other. This type of Interaction was not accounted for in the simple model of two independent halves being combined to form a whole.
These variables were then assigned values dependent on the number of times that variable occurred in a given PCOF. The regression of these variables against the retention indices was carried out and the derived regression co efficients serve as a quantitative measure of the retentive effect of the molecular structural component represented by that variable.
RESULTS
Using the described variables and regression techniques an R1 value of 0.9995 and a standard deviation of 6.78 was obtained for the observed versus pre dicted retention Index for 110 PCOFs which have been synthesized to date. This standard deviation is quite acceptable in view of the feet that the error in the measurement of the retention index of PCOF Is t4 index units. The model has proven useful In detecting errors In the structural assignment given to PCOFs (12). Furthermore, It hes allowed retention Indices to be assigned to PCOFs which we have not yet synthesized.
At the present time the minimum number of PCOFs that would be necessary to accurately determine the regression coefficients Is being established. This is important In that, as the analytical conditions are changed (e.g., different chromatography columns or different analytical systems such as HPLC). It would only be necessary to run the subset of PCOFs to allow the retention charac teristics for all other PCOFs to be determined.
REFERENCES
1. T. Mazer, F. 0. Hi 1 amen, R. w. Noble and J. J. Brooks. Anal. Cham.. 55., 104 (1983).
2. H. Kurokl, *. Haraguchl end y. Masuda. Chemosohere. T3, 561 (1984).
3. S. H. Safe and L. M. Safe. J. Aqrlc. Food Cham,. 32, 68 (1984).
4. W. V. Llgon and R. J. May. J. Chrom,. 294. 87 (1984).
5. E. xovats. Hel_. Chlm. Acta. 41_, 1915 (1958).
6. E. KOVItS. H*1_. CMm. Act*. 42 , 2709 0 959).
7. H. Van Den Dool and P. 0. Kratz. J. Chrom.. 11. 463 (1963).
8. H. R. Buser end C. Rtppe. Chemosphere. 3, 157 (1979).
9. T. Mazer and F. D. Hllamen. Chemosphere. , 651 (1982).
2-10 MONS 215583
10. P. W. Albro, J. K. Haseman, T. A, Clemner and B. J. Corbett. J. Chrom .
136, 147 (1977).
-------------
11. T. Mazer, F. D. Hlieman, m. o. Hale. R. H. Noble and J. J. Brooks, in
"Chlorinated Dioxins and D1benzofurans In the Total Environment.", G.
Choudhary, L. H. Keith and C. Rappe, Eds., Butterworth Publishers, Boston,
1903. pages 23-58.
_
12. T. Mazer, F. 0. Hlleman, R. H. Noble and J. J. Brooks. Anal. Chm., 55.
164B (1983).
------- *----- --
* Present Address; T. Mazer, Brehm Laboratory, Wright State University, Dayton, OH 45435
HONS 215564 2-11
FORMATION OF PCOO ANO PCOF IN ASHAREl ANO CONTAMINATED MINERAL OIL EQUIPMENT
FRED L. DEROOS MARCUS COOKE
Battelle Memorial Institute Columbus, Ohio
GIL AOOIS RALPH KOMAI JACQUES 6UERTIN Electric Power Research Institute Palo Alto, California
ABSTRACT
The Electric Power Research Institute (EPRI) Is conducting a program to determine If polychlorinated dlbenzofurans (PCOF) end/or polychlorinated dlbenzo-p-dloxlns (PCDO) are present, or If they can be formed. In dielectric fluids used by the electric utility Industry. The program Includes the following tasks.
a Literature Review e Round Robin Analytical Method Evaluation Study e Survey of ln>Serv1ce Dielectric Fluids a Arcing/Corona Tests a Pyrolysis/Combustion Tests a Development of a Rapid MS/MS Analytical Technique
01SCUSSI0N
The Literature Review, prepared by SCS Engineers of Long Beach. California, summarizes much of the background literature on PCDD/PCDF. It describes accidents that generated PCOD/PCDF, degradation of PCOO/PCDF, toxicology, and future research needs. This review Is available from EPRI as publication number EPRI CS-3308.
The Round Robin Analytical Method Evaluation Study was daslgned to validate current methodologies and to determine the accuracy with which specific PCOO/PCDF Isomers can be quantified. Four sample preparation methodologies and three mass spectrometry techniques are currently being compared. The study Includes the synthesis of native and Isotoplcally labelled standards and the analyses of spiked sample matrices. Radian Corporation synthesized the standards, and prepared the spiked
2-12 HONS 213585
matrix samples, which will be analyzed by Battelle, the Illinois Institute of Technology Research institute (IITRI), Radian, and the University of Umea (Sweden). The Isotoplcally labelled standards will be used to show true recoveries and to provide accurate quantification within congener classes. Presently 1.2.3.7.B* pentachlorod1benzofuran*,3Ci2 has been prepared and purified. A labelled hexachlorodlbenzofuran Is also being synthesized. The native standards were used for spiking and to generate standard curves and response factors. The natlvt isomers that were synthesized Include 1,2,3,7,8-pentachlorodlbenzofuran, 1,2,3,4.7,8-hexachlorodlbenzofuran, and 1,2,3,4,6,7,8-heptachlorodlbenzofuran.
The Round Robin Analytical Method Evaluation Study Is presently In progress and a comparison of data fron the various laboratories will soon be completed to show reliability, accuracy, and ruggedness of the various analytical methods.
The in*$ervlce Olelectrlc Fluid Survey consists of developing a selection criteria document, obtaining samples of dielectric fluids, and determining the levels of PCDO/PCDF In selected fluids. General Electric (GE) completed the selection criteria document, while Battelle, IITRI, Radian, and the University of Umea are presently carrying out the analyses. This study will show the absence or presence of PCDD/PCDF In currently used dielectric liquids. Hopefully the study will evaluate a broad range of liquids and operating conditions that mirror the dielectric liquid usage of various utilities throughout the United States.
The Arcing/Corona Tests were designed to determine If arcing end corona discharges could produce PCDD/PCDF Isomers In dielectric fluids. The tests, which were carried out by GE, consisted of loading various mixtures Into a test vessel end producing a short duration arc with an energy of between S-10 kjoules. Aroclor 1254 at concentrations of 50*10000 ppm (w/w) In mineral oil, and a trichlorobenzene reference liquid containing SOS (w/w) of Aroclor 1254 were arced. The unarced mineral oil, as well as the trlchlorobenzene/Aroclor 1254 mixture, were also analyzed as positive controls. The preliminary results from these analyses, suemarized in Tables 1 and 2, show little difference in PCDD/PCOF levels between the arced and unarced fluids. This Indicates that arcing appears to have minimal effect on either the PCDD or the PCOF levels In dielectric liquids. These data show the type of Information that can be gained from this study.
The Pyrolysis/Combustion Tests were designed to characterize the production of PCDD/PCDF Isomers during pyrolysis. These tests are being carried out by the New York State Department of Health, and are presently In progress.
The goal of the Rapid MS/MS Technique Study Is to develop an analytical method that minimizes the need for extensive sample workup prior to analysis. The advantages of this approach would be a rapid and lower cost analysis as compared to conventional gat chromatography/mass spectrometry (GC/KS). ideally this technique will provide the same sensitivity and selectivity as conventional GC/MS.
SUWARY
This research program Is designed to evaluate the potential presence of PCDF and PCDD in utility dielectric liquids currently In use in the United States. The study is based on developawnt of well characterized methods to detect PCDF/PCDD in order to generate high quality data for the diverse class of compounds that are expected only at trace concentrations. The in-service fluid cheracterizatlon will show the relative magnitude of PCOF/PCDD background levels in fluids from various utility operations. The arcing and pyrolysis experiments are designed
MONS 215586 2-13
to show potential for production of PCDF/PCDD In unusuel situations or upset situations.
The overall program is i comprehensive ettempt to characterize the potentlel
presence of PCOF/PCDD in operating utility dielectric fluids end to Investigate
the potentlel for their production in unusuel situetlons such es catastrophic
failure, or overheating.
,
HONS 215587 2-14
Table 1
PCOD OATA FOR ARC STUDY SAMPLES (limit of detection), ppb (w/m)
Samples
Arced Aroelor 1254 Arced Aroelor 125* Arced Aroelor 1254 Arced 50/50
TCB/1254 Unarced Oil Unarced 50/50
TCB/1254 Method Blank
Tetra-CDD Penta-CDD Hexa-CDD Heota-COD Octa-CDD
(0.06) 0.20 (0.06) 23.9
(0.36) (0.14) (0.13) 12.1
(0.38) (0.09) (0.12) 1.7
(1.4) (1.6) (1.8) (1.0)
(1-7) (2-6) (1-4) (1.4)
(0.09) 21.2
0.11 (0.78)
0.05 (0.21)
1.04 (5.9)
1.00 (6-8)
(D.ID)
(D.09)
(0.07)
(0.65)
(0.52)
Table 2
PCDF OATA FOR ARC STUDY SAMPLES (Unit of detection), ppb (w/w)
Semoles
Arced Aroelor 1254 Arced Aroelor 1254 Arced Aroelor 1254 Arced 50/50
TCB/1254 Unarced Dll Unarced 50/50
TCB/1254 Method Blank
Tetri-COF Penta-COF Hexa-CDF Heeta-CDF Octa-CDF
0.69 (0.07) (0.07) 173
4.2 (0.19) (0.12) 1740
1.6 (0.10) (0.08) 1180 '
(1.7) (2.2) (2.6) 1360
(1.6) (1.7) (1.2) 171
(0.06) 367
(0.03) 1850
(0.01) 1790
(0.6) 2960
(0.71) 217
(0.08)
(0.08)
(0.04)
(0.35)
(0.48)
HONS 215588 2-15
Chlorodibenzofuran Am lysis Using Two-Dimensional Gis Chromatography-Mass Spectrometry
Uoodfln V. Ugon, Jr, and Ralph J, Nay General Electric Company
r.nmorate Research and Development Schenectady, N. Y. 12301
We have developed a two-stage gas chromatography system for sample cleanup prior to mass spectrometry. Schematics of this system In its three modes of operation are shown In Fios. 1,2,3.
GUAGE 0.0 psi
HONS 215589 2-16
GUAGE * 0.0 psi
GUAGE* 6~ pti
Figure 3. Schematic of the GC-GC system In the "SECONAftY SEPARATION* mode of operation.
2-17 HONS 215590
The system consists of two coupled yes chromatographs. The first chromatograph
uses a high capacity low resolution packed GC column (10 ft x 2 mm , 3t Siler iOC).
This column provides a preliminary separation. In the case of the
ch1or<jtben;ofurans, it serves to limit the number of isomers which must be resolved
in the secondary separation and it prevents the great majority of the matrix
comoonents from reaching the high resolution secondary column. This column is
essentially expendible and serves to collect Involatile residues before they reach
the secondary column. The condition of the primary column should be monitored
regularly because both absolute and relative retention times can change as residues
are deposited.
~
when the system is operated in the "save" mode selected portions of the primary chromatogram are stored in a cold trap. See Fig. 1. When the system Is operated in the "divert" mode unwanted components eluting from the primary chroeutograph are
vented from the instrument. See Figure 2. Changes in operating mode are accomplished by opening and closing valves--none of which is In a heated region.
After the primary separation is complete the system is switched to the "secondary separation" mode and the cold trap is heated to transfer its contents into the secondary chromatograph. See Fig. 3. The secondary chromatograph can contain any high resolution capillary which is compatible with ir.ass spectrometer operation. For the case of 2,3,7,8-TCOF analysis, this chromatograph is fitted with a capillary system which has been described previously. (J. Chrometogr., 294 (1984) 87). This capillary combination was arrived at using the method of Krupclk et al (J. Chromatogr., 213 (1981) 189. The computer model of the separation is shown In Fig. 4. This capillary combination provides baseline resolution of 2,3,7,8-TCOF from all isomers which co-elute from the secondary column. Using this system full baseline separation of 23478 tnd 123789 from their isomers has also been obtained using various secondary capillaries,
Figure 4. Predicted separations for 7 TCDF isomers using the (08-17)-<SP2330) capillary system as determined by computer modeling employing the Krupclk equations.
2-18 HONS 215591
A typical Quantitative analysis for a chlorodibenzofuran starts with addition of a labeled interru 1 standard to the sample. At GE standards have been prepared which are 99 atom-t lxC (R. A Bell and A. Gara). Full mass spectra of the standards have
been recorded in order to compare them with analogous spectra of the un-labeled materials. It was found that the t-total ionization for the molecular ion and its isotopomers was the same for the labeled and unlabeled materials. Therefore no correction is applied for enrichment errors or Isotopic effects'on fragmentation.
After addition of appropriate standards, samples are either analyzed by direct injection into the primary chromatograph or are subjected to a modified Stalling
clean-up procedure. Arochlors up to 1242 can be analyzed directly by injection of about 2 mg of Arochlor. Flyash extracts and IOC oil have also been analyzed successfully in this way. Larger Arochlors, fish, sediment, etc. require the
Stalling procedure.
The sample is co*injected with a retention index marker which elutes from the primary chromatograph just ahead of the component of interest. Collection of the component of interest is accomplished relative to this marker. After the primary chromatogram is complete the system is switched to the secondary separation mode and the cold trap is heated. The components eluting from the secondary chromatograph ar carried directly into the electron beam of the mass spectrometer ion source using a section of fused silica capillary.
The mass spectrometer operating conditions are as follows:
Mass Spectrometer:
Vg Zab
Ionization:
Electron Impact
Resolution (1 OX Valley): 3000
Acquisition by Selected ton Monitoring;
e.g. for 2,3,7,8-TCDF ions at 304,306,308,316.318,
320 and 328 are monitored using voltage switching.
Mass 328 Is generated as a lock mass signal using
a,4'd1aminooctafluorobiphenyl added at a very low
level from a heated inlet. The lock mass signal is
monitored in full profile mode.
Great care is taken to ensure that ion source focusing
does not change with voltage switching. Vary minor source
contamination can cause this effect in the Vg Zab,
Great car* is taken to ensure that Interfering materials do
not co-elute with the lock mass thereby shifting its centroid
and causing systematic errors In mass selection.
No data Is accepted which does not show the theoretical
, distribution of intensities for the Isotopomers of the
' respective molecular ions.
HONS 215592 2-19
PCOF ISOMERS ANO ISOMER LEVELS FOUND IN PCBs Chrlstoffer Reppe. Lers-Owe Kjeller end Stellen Merklund
Oepsrtment of Orgenlc Chemistry, University of Umee S-901 87 UMEA, Sweden
experimental
We htve developed e new cleen-up technique for the determinttlon of PCDFs in PCBs.
1. Dissolve PCB In CHjClj/c*hexene. 2. Add surrogete. 3. Column Cerbon PX 21 on fibers. 4. Reverse elution by toluene. 5. Eveporete toluene, 35*C, 20 mm Hg, 6. Olssolve In n<hexene. 7. Fluorosll column. 8. Reverse elution CHjClj9. Eveporete, edd known emount fin*! solvent. 10. Inject 1-2 I>1 In HRGC/MS using e 60 m fused si lice 5P 2330
column. The tempersture progrem ellows isomer specific enelyses The MS Instrument Is opereting with El or NCI (methene), SIM. 11. QuenttfleetIon of 2,3,7,B.substituted isomers es well es totel levels of PCDFs. 12. Celculetlon of recovery of surrogetes.
RESULTS
Hi hive analyzed a series of cowerclal PCS products and the results ere given in
Teble 1.
HONS 215593
2*Z0
oiscussion
Me have found contamination by PCOFs In all PCB products analyzed. The total level of PCBFs varied from a few ug/g up to 40 Hg/g. The chlorination pattern of the PCOFs was found to vary with the chlorination level of the PCI*. Discussing Individual Isomers, the toxic 2,3,7,B-subst1tuted Cl-, CI5- and Clj PCOFs were always middle or major constituents within each group of congeners. The 2.3.7.B- and 2,3,4,B-tetra-COFs are eluting very close together. The toxic effect of these two isomers is very different. The ratio of these two isomers was found to vary from 10:1 to 1:10. For a risk evaluation It is essential to have an analytical method where It is possible to separate between these two isomers (see Figure l).
HONS 215594 2-21
zz-z
Pa-typ
TUI-
TETRA-
Tot 2378
Tot
Table 1. PCOFs In coMerclal PCBs.
12348 12378
PENTA23478
HEXA-
Tot 123479 123678 123789 123478
234678
Tot
HEPTA-
To* Rec 2378 TCOO-t
Pyralene 700 S3
630
10
T 35
NO NO NO
NO NO
NO
79
A1254
63 19 1400
A1260
10 13
110
A30
$00 35
573
A40 1300 180 2600
ASO 7400 3300 20000
A60 770 840 6900
T64
47 23
360
Clophen c 710 54 1200
Blank
HD NO
NO
Blank
NO NO
NO
690 48 14 96
760 1100
97 34 NO NO
490
56
28 8
1100 990 122
30 NO NO
4000 260 160
1700 8000 8100
840 270 NO NO
2500 500 50 79 700
1600 520
NO NO NO
2100 120 59 68 360 330 390 T NO NO
190 190 NO NO
18 170 58 NO NO NO
130 10000 27 1500 HO 220
T 310
98 3100
330 6800 41 2600 NO T NO NO NO NO
960 1300
T NO 75 2000 220 NO NO NO
78
88
79 79 95 95 72 79 90 87
HONS 215395
1270
1237
2370
1260
U46 1246
14 70 1369
1238 1467
i 2466
1239 2347
M 1236
NUt
1379 1370
A 1340 JLaa. 7
1
I l
V.
---A________1
T
i
HONS 215596
PAST 3:' PYROLYSIS AND COMBUSTION MARCUS COOKE - MODERATOR
HONS SI*597
FORMATION OF POLYCHLORINATED DIBENZO-p-DIOXINS AND
DIBENZOFURANS FROM BURNING OF SILICONE dielectric FLUID
SPIKED WITH POLYCHLORINATED BIPHENYLS
-
Jon W. Swenaon Dow Corning Corporation
Thome* 0. Tlarnan, Ph.D.
Braha Laboratory Wright Stata Unlvartlty
INTRODUCTION Since 1982 Dow Corning Corporation haa had a prograa of ratrofllllng PCB containing tranaformera, ualng lta alllcona fluid RatroSll'" proceaa. Tha concarn* over tha conbuatlon of PCB'a haa lead to tha daalra to batter underatend tha by-producta formed during tha burning of alllcona ftulde containing aaall amounta of PCB'a which oay remain aftar tha RatroSllTM proceaa. Thua a contract to etudy thin natter wee initiated with tha Brahm Laboratory of Wright Stata Unlverelty under the direction of Dr. Thomae D. Tlernen.
Tha atudy had 2 objective*. One waa to determine'amounta and apeclaa of polychlorinated dlbamodloxlna (FCDD'e) and polychlorlnatad dlbemofurana (PCDF'a) formed, whan a alllcona fluid aplked with varloua lavala of PCB waa pyrolyzed. In addition, tha affect of pyrolyala temperature on thla eeme ayaton waa to be evaluated. Thla paper dlacuaaaa tha raaulta of theae atudlaa.
METHODOLOGY
All aplked aamplaa wara praparad at Dow Corning. Burning atudlaa ware conducted at tha Brahm Laboratory, at Wright Stata Unlverelty under the direction of Dr. Thomaa Tlaman. Sample* of 30 centlatoke polydlaethy lalloxena (DOW CORNlNOD 561 Fluid) wara aplked with 3. 50, 500 and 11,300 ppm of PCB from Arochlor 1260. The 11,300 ppm aampla waa Initially atudlad at A different tamparaturaa to datemlna which tamparatura produced tha maximum amount of PCDD'e and PCDF'a. Thla waa datarmlnad to ha 600*C, Than tha aamplaa aplked with varloua amount* of PCB wara burned in air at thla tamparatura and tha by-product* analyzed.
MONS 215598 3-1
Tha burning apparatue la ehown In Flgura I. It conalated of a high temperature tube furnaca containing a quartz tuba raactor, a cooled aaaiple Injection ayatem and a aerlaa of three trapa to cotlact the volatile combuatlon producta. Five at. of aaaptc were uaad for each teat with an average realdance time In the burning zone of two eeconda. Tabla I on--arlzea the weight a of the combuatlon producta baaed upon the 5 ail (4.7 g.) Maple Injected. The combuatlon producta lneluda any water produced In the burning reaction. Thue tha total valght of the roabuatlon producta could, and Indeed did. at tlaea exceed the aaount of eeaple lajactad.
Prapnratlon of the pyrolyale producta for enalyele conalated of eoxhlet extraction In toluene for 16 houre and a aarlaa of vaehlng atapa ualng KOH, BjSO^ and enhydroua aodlua aulfeta, concluding with a haxana alutlon through a column packed with alllca. and then concentrated by evaporation of the haxana. Thle waa than tranafarred to a laboratory prepared liquid chroaiatogrephy column packed with Woela baelc alumina which waa prevloualy activated at 600*C. After conducting a eerlaa of methylene chlorlda/haxana alutlona. tha eamplee ware evaporated to drynaee end atorad In a freezer until anelyale. Thaaa a--plea ware then raconatltuted by adding trldecane before injection of tha appropriate allqnot Into tha analytical teat lnarrumant.
Analyaea of tha extract were dona ualng a Parkin Elmar Sigma III C.aa Chromatograph coupled through a cuatom fabricated Interface Including a alngla-ataga glaea Jet aaparator to a Kvatoe MS-25 Meaa Spectrometer equipped with a DS-SOSM Data Syatam.
RESUITS 0? ANALYSES
Tha raaulta of tha analyaea of the combuatlon producta from tha burning teata for chlorinated dlbenso-o-dloxlna (CDDa) and dlbaniofurene (CDPa) are au--arliad in Tablea II end III. Aleo ehown are tha raaulta of enalyeaa of a method blank, of a aampla of polydlmethylallomane containing 11,300 ppm of PCBa (which waa not pyrolyiad), and a aampla of the polydlmethylelloxana containing 130 ppm PCS which had bean prevloualy eubjectad to electrical arcing.
HOMS 215599 3-2
Aa can ba aean froa tha data preaentid In Tabla II, tha Initial aarlaa of taata. In which aaaplaa of polydlaathylalloxana fluid containing 11.300 ppa of PCBa wara burnad at tenpereturaa of 400'C, 600*C, BOO'C and 1000*C raapactlvaly, ravaalad that chlorinated dlbenzofuran waa forced In the 600' and 600* taata. In particular, tha tetra-. panto- and hexa-CDFe wara produced at thaae tanparaturaa. All data la preaentad In the concentration of total COD I CDFe In nenograas/graa of total coabuatlon producta or Perta Par Billion. Klnlaua Detectable Concentretlone are given In peranthaeee. While tha praaanca of aeveral leoaare of each of theaa chlorinated claaaaa can ba dlecerned froa tha aiaaa ehroaetograaa obtained In tha analyaea, It la noteworthy that tha tetra-CDfa appear to Include 2, 3, 7. 6-TCDF (or at laaat a TCDP laoaar which coalutaa with the 2, 3, 7, B-TCDF), No CDDa other than 0CDD ware detected In tha eoabuetlon producta froa any of theaa Initial taata. Thera were eaeantlelly no detectable CDFe in tha producta froa tha BOO'C and 1000*0 burning taata.
It waa clear froa tha Initial aarlaa of taata that the quant Itlea of CDFa produced froa burning of tha PCB-contaalnatad alllcona fluid wara greater whan tha taaperatura waa 600*C. After thaaa raaulta had been reported to Dow Corning and ravlawed, tha Braha Laboratory waa requaatad to conduct aavaral additional taata In which aach of three aaaplaa of the alllcona fluid containing 500 ppa, 50 ppa and 5 ppa, raapactlvaly, of PCBa, were to ba burnad at a taaperatura of 600*C, The raaulta of enalytlng tha eoabuetlon producta froa thaaa taata for CDDa/CDFa are ahovn In Table 111. Aa thaaa data Indicate, tatra-, pante- and hexe-CDFa ware datactad In all of theaa coabuatlon producta, elthouBh the quantltlea of thaaa CDFe ware clearly directly related to tha concentration of PCBa In the fluid pyrolyied. That la, the greater tha concentration of PCBa In tha field, tha greater tha concentratlona of CDFe In tha pyrolyala producta, Thla trend la, of , couraa, an expected If tha PCBa are tha praeureore of tha CDFa which are forced In tha eoabuetlon proeeaa. Table 111 alao ehowe that tha aecond aarlaa of taata found no CDDa (except eoae 0GDD, Which any be queatlonabla) whan tha alllcona flulde containing 500, 50 and 5 ppa of PCBa wara pyrolyzed.
Tha analytical raaulta obtained for tha polydlaathylalloxana fluid containing 11,300 ppa PCBa which wae not pyrolyted, aa wall aa for tha fluid aeapla containing PCBa which had baan pravloualy aubjactad to electrical arcing. Indicate
HONS 215600
3-3
that thaaa aaaplaa contain aaaantlally no datactabla CDDa/CDFa. It will ba notad that tha datactlon llnlta raportad for thaaa aaaplaa ara for tha fluid aaaplaa thamaaVvaa (and not for coabuatlon producta), alnca thaaa aaaplaa wara not pyrolyzed. CONCLUSION Burning atudlaa of polydlaathylall oxana aplkad with varloua lavala of PCB ahow that no polychlorlnatad dibanzo-p-dloxina ara datactad but that tatra. panta and haxa apaclaa of chlorlnatad dibanzofurana ara datactad. A aaapla of FCB aplkad polydlaathylalloxana fluid which had baan aubjact to alactrlcal arcing ahowad no datactabla PCDD'a or FCDF'a foraad. Maxima formation of FCDF'a appaarad to occur at 600*C.
HONS 215601 3-4
t vent
I I 10 hood
PYROLYSIS TESTING APPARATUS
|-- l$.Z<a> "I*
nrnC*/ouTJ
quants
t ouat MM. COMMSTTON
n*c
30.5<%
ItaCC'&MC ACCUUhTCO TCMftJUTVIC Tgc rwwici
I
J*1- l)tn --I*-" lOt* ""|
(ftsuunmc M.KNUOS
N.COOUM 0U1LCT
see injeenw
0C1L ((LOW
COMMISSION 10NC
N. COOLING InlCT
(a) DETAIL Of SAMPLE injection system cn
smee MOUNT CC rLCCTNOMiCM.LT WwTAOLLfO
JTNMCC PUMN
CM OP MJCCTON LOCATCO PS NAY INTO WOMIATKM ZONC IWCI
NCt TOIOLC
APPARATUS FOR TESTING PYROLYSES OF SELECTED CHEMICALS FOR PRODUCTION OF CDOs/CDFs Figure 1.
HONS 215602
TABLE I
WEIGHTS OF COMBUSTION PRODUCTS FORMED FROM PYROLYSIS OP POLY DIMETHYLSILOXANE FLUIDS CONTAINING POLYCHLORINATED BIPHENYLS*
PCS Laval (PP")
Burning Taaparatura
Total Walght of Cowbuatlon Produeta
(iraw)
11,300
400*C
4.6
11,300
600 *C
5.3
11,300
BOO'C
4.6
11,300
1000*C
5.1
500 600*C
4.6
50 600 *C
4.6
5 600*C
4.5
*' In aach axparlaant, 5.0 *L of tha alllcona fluid vara bttrnad. Slaca tha danalty of tha fluid la 0.9428 /L, 4.7 of fluid vara pyrolytad In aach caaa. Tha ceabuatlon produeta lncluda any watar producad In tha pyrolyala raactlon, aa wall aa lncoaplataly pyrolyiad fluid In caaaa whara cowbuatlon vaa not coaplata (lowar taaparaturaa).
HONS 215403 3-6
TABLE U
THE EFFECT OF TEHPFEATURE OH THE PYROLYSIS PRODUCTS OF PDMS SPIKED WITH 11.300 ppa PCB (Data in part* par billion)
t 57cV i.s.i.05
tamal rmm
tlMMl KM
m
bCBti
htM .p. M.
SAX a. a.
ink
(.)
(.) (.10) (a.AO) (0.S0)
PK Fyr#- .. ..
All
lfiW
(*.W) (.AS)
(1.0) (1.0) (l.S) o.s)
aaa*c l.na .a. rax 1.1U PaPa 1.A0C Pa Pa
(l.S)
(IT)
)
M'C
w.tu .a. ()
AU 1I.SA0 .a. 3.406 aa
<)
(10)
MO'C 1000`C
M. (*.)
(!.)
s.a. .n
.a. (i*n
SOX
(S.a) (in (is)
111 PaP* a.a. Rl <!> (10) (TO)
(is)
* (TO)
litwtty
f* ITaC-tl.*
i.uA
7,0-*K*0 loCtnal
>Mvr7 iscir
acara acm Italatl
ocvr ocno i4ar4
411
M. a.a*
Ml
(.10) (0.20)
(0.A0) (0.10)
(l.S) (l.S)
All
IJa PaPa
401
(1*5) (14)
(l.S) (l.S)
SIX a.a, IP 411 (44)
a.a-
a.a.
ux
-A. A.O
11
()
(U)
on
aax Sa a*
an
(5.*) (S.a)
(4Z) on
a.a. a.a. sal a.a. 11 ASl
) (S.0)
(44)
WHS 219*04
TABLE III
pyrolysis fbooucts or rats spiked wits various concentrations of pcb (Kiti In part* par billion)
Kacovarjr
Kacovcry
of 57C1,-
of 37C1 -
1.2.1,4,6.
PCB 7CD0
7.8- H|
Laval
Burning
lataioal
Intam
(PP*)
Tav*
TCDFa TCOOa Standard PCDFa FCDDs ItxCDF* HxCDDa HpCDFa HpCDDa Stands
uoio
11,300 600*C 46,215 N.D.
681 11,500 N.D. 3600
N.D.
N.D.
N.D.
822
(24)
(20)
(10)
(10)
(10)
500 600*C
2,77$ N.D. (7.0)
602
450 N.D. (15)
142
N.D. 05)
N.D. (10)
N.D. (10)
1002
50 600*C
138 N.D. (4.0)
581
12 N.D. (*.0)
N.D. (38)
N.D. (30)
N.D. (10)
N.D. (10)
862
5 600* C
12 N.D. (3.0)
632
2.0 N.D. N.D. (*.0> (10)
N.D. (10)
N.D. (10)
N.D. (10)
712
Arcad Not fjrro- N.D.
N.D.
532
N.D. N.D.
N.D.
N.D.
N.D.
N.D.
lytad
02)
(20)
(4.0) (10)
(25)
(25)
02)
02)
172
I HONS 215605
SIMULATED BUILDING FIRE STUDY USING RETROFILLED TRANSFORMER DIELECTRIC COOLANT
MARCUS COOKE FRED L. DEROOS
BRUCE RISING Battalia Manorial Institute
Columbus, Ohio
WILLIAM H. MARTIN Union Carbide Corporation
Tarrytown. Now York
CHRISTOFFER RAPPE University of Umea
Umea, Sweden
JOHN SLAYBACK Oneida Research Services
Oneida, New York
ABSTRACT In this program a model combustion system was built In the Battalia pilot plant facility. The unit was a 40.000 Btu per hour vertically fired tube furnace with a combustion tone 4,3 ft (131 cm) in length with a 5,5 in. Internal diameter (14 cm), A schematic diagram of the combustion system used In this study Is shown In Figure 1, The combustion experiments were designed to produce conditions favorable for production of polychlorinated dlbanzofuran (PCDF) end polychlorinated dlbenzo-p-dloxln (PCDD).
HONS 215606
3-9
PROJECT SUPMART Tha tasts wars conducted using keroslna with IX (w/w) silicons coolant addad to ganarata condansatlon nuclal-for catalytic production of PCDF/PCDD. Tha ktroslna-sllIcons mix was Injactad through tha primary Injection port. Tha tast dlalactrlc liquids wars atomized and sprayad Into tha naar flams ragion of tha combustor whara contact temperatures of 700-900 C wars obtalnad at tha point of Injactlon. Tha dlalactrlc fluid was Injactad through tha sacondary Injactlon port, rasultlng In an opposad flams condition. Tha prlmarysacondary Injactlon ratio was approxlmataly 2 to 1 for all -tests. Tast conditions wars malntalnad to product a combustion gas oxygan concantratlon of 3 to 5 volume parcant.
FIGURE 1 SCHEMATIC DRAWING OF THE COMBUSTION TEST APPARATUS Prior to Injactlng tha dlalactrlc fluid, tha coafcustlon gas oxygan concantratlon was approxlmataly 8 to 9 parcant. Hence tha dlalactrlc fluid was injactad Into a high taaiparatura. oxygan daflclant anvlronmant similar to that axpacttd In an uncontrollad firs. Samplas wars collactad by EPA Modified Mathod S train sampling (MM5).
MONS 21560? 3-10
Th* test liquid* were simulated ritroflll dielectric fluid* with SO ppm (w/w) Aroclor, and residual trl/tatrachlorobansan* (TCB/TTCB) diluents, In a liquid *Hlcona solution. Thraa Aroclor* 1260, Aroclor 1254, A roc lor 1242, TCB/TTCB bland,and a blank with silicon* only wars combustad.
Sampias wart axtractad by Battalia (BCL), and submlttad to thraa participating laboratories; th# Unlvarslty of Lima* (thraa), Onalda Rasaarch Sarvlcas (0R$). and BCL, for blind analysis of PCDF/PCDD, Each laboratory ustd thalr standard praparatlon and analysis procaduras. Battalia and Onalda usad high rasolutlon mass spactromatry(HRMS), whlla tha Unlvarslty of Umaa usad a quadrupol* mass spactromatar (QMS), for analyta datactlon. All thraa laboratory* usad high rasolutlon capillary gas chromatography(HRGCC). Th* thraa laboratorlas split th* sam* samples whlla preforming blind analyses, This Independently verified results and showed tha variability In reported data. An Illustrative chromatogram of a total Ion mass spectrum (TIMS) from th* Aroclor 1254 burn Is given in Figure
FIGURE 2
AROCLOR 1254 PR00UCT TIMS CHROMATOGRAM (COURTESY OF C. RAPPE)
Um* and QRS analyzed all furan and dioxin congener clattat for four to alght ehlorln* substitution (tatra through octa isomers), and both laboratories reported the 2,3.7,8tatrachlorodlbanzo Isomer concentrations for both the furan (2,3,7,8-TCDF) and dioxin (2,3,7,8-TCDO) class**. BCl analyzed and reported th* tatra furan/dioxin congener concentrations, 2.3,7,8-TCDF, and 2.3.7,8-TCDD concentrations in tha W15 combustion samples. In addition Umaa analysed and reported tha Individual Isomer concentrations of all tetra and panta Isomers, of both furans and dioxins found In these samples.
HONS 215608 3-11
Th# three laboratories showed good agreement In overall
results and found no detectable dioxin Isomers In any
congener class for the four tests reported} a system blank,
the Aroclor 1260 test, the Aroclor 1254 test, the Aroclor
1242 test. The averages for the three laboratories reporting the four test burns are given below (PnCDF represents
pentachlorodlbenzoburans):
-
TEST Blank
1 2 3
QUANTITIES PRODUCED [ppb (w/w) dielectric consumed basis]
DOPANT
TCDF
2.3.7.B-TCDF
PnCOF
None
0.003
<0.002
NO
1260
0.43
<0.15
0.31
1254
0.3B
<0.08
0.14
1242
0.08
<0.01
0.04
From these data the polychlorinated biphenyl (PCB) conversion rates were calculated. Conversion of Aroclor 1260 to TCDF ranged from 0.9 to 17 parts per million (ppm) on a weight basis. Conversions of Aroclor 1254 [4 - 11 ppm (w/w)] and Aroclor 1242 [2.4-2.6 ppm (w/w)] to TCOF gave similar values, and were consistent with pyrolysis conversion rates reported In the literature (1). Trl and tetrachlorobenzanes at concentrations up to 1.5S (w/w) In the silicone burned, were found to produce no measureable PCDD or PCDF.
In this study the measured furan concentrations produced by combustion of retroflll dielectric liquids tended to decrease as the degree of chlorination of the spiked PCB decreased. Aroclor 1260 spiked Into silicone resulted In higher levels of PCDF than found In the experiment with Aroclor 1242. In all cases, the PCDF levels were extremely low (ppb) on a dielectric fluid consumed basis.
REFERENCES
1, Chlttlm, 6. G., !i >1.. Chlorinated Oibanzofurans and
>1benzo-p-d1ox1ns: Detection and Quantitation in Electrical Equipment and Their Formation During the Incineration of PCSs. Wellington Science Associates, Rockwood, Ontario, September 1979. [Referenced In
pw t Pgvlfwt PCOOf ani PQPfs In Utility PCB 3308, Project 126]Pn,Hnet Report, November 1983, p. 3-18],
MONS 215609
3-12
FORMATION OF PCDFs UNDER "OPTIMIZED" COMBUSTION CONDITIONS FROM LOW-LEVEL PCS DIELECTRIC FLUIDS
Mitchell D. Erickson, Christopher J. Cole, Jalrus D. Flore, Jr., Paul G. Goman, Clarence L. Halle, Gary D. Hlnshaw, Fred C. Hopkins, Stephan E. Swanson
Midwest Research Institute 425 Volker Boulevard
Kansas City, Missouri 64110
Daniel T. Heggem U.S, Environmental Protection Agency
Office of Toxic Substances Field Studies Branch, TS 79B
401 M Street, S.W. Washington, DC 20460
The Environmental Protection Agency (EPA) Issued a final rule on August 25, 19B2, authorizing Indefinite use of certain electrical transformers containing poly chlorinated biphenyls (PCBs). This rule Is known as the PCB Electrical Use Rule. At that time. Information available to the EPA Indicated that fires Involving electrical transformers were rare, Isolated Incidents. However, several recent transformer fires In buildings have brought Into question EPA's earlier assump
tion. The Agency has therefore Issued an Advance Notice of Proposed Rulemaking (ANPR) (USEPA 1964a) and proposed rule (USEPA 1984b) to gather data on the spe cific risks posed by fires Involving electrical transformers that contain PCBs and also on mechanisms for mitigating or eliminating these risks. Depending upon the results of EPA's analysis of these data, the Agency may proposa further control measures on the use of this equipment.
This abstract describes the methods and results of a study, conducted In support of EPA's data gathering activities under the ANPR, of the potential for forma tion of polychlorinated dlbenzofurens (PCDFs) and polychlorinated d1benzo-dloxlns (PCDDs) from uncontrolled fires Involving PCB-contalnlng dielectric fluids.
At high temperatures, such as those In transformer fires, polychlorinated bi phenyls (PCBs) raact to form polychlorinated dlbenzofurens (PCOFs) and other toxic by-products. The purpose of this study was to optimize conditions for PCDF formation In order to examine the potential for formation of PCOFs and poly chlorinated dlbanzodloxlns (PCDDs) from combustion of selected PCB-contalnlng dielectric fluids.
Tha study was conducted In three phases. In Phase 1, a bench-scale thermal de struction system, developed by MR1, was refitted with specific components In stalled to accommodate this study as shown In Figure 1. Then, a few test runs
3-13
MQNS 215610
were made under preliminary temperature and oxygen conditions to ensure en ac ceptable system blank. The concentrations of CO, C0a, and 02 In the effluent were monitored continuously. The entire effluent from the thermal destruction system was passed through an XAD-2 trap to collect PCDFs and other semivolatlle organics. The XAD-2 trap and a rinse of connective tubing were Soxhlet-extracted and cleaned using column chromatography to isolate the PCDFs and PCDDs. All sam ples were analyzed for PCDFs (and PCDOs In Phase 3), using high resolution (capillary) gas chromatography/electron impact mass spactrometry (HRGC/EIMS) in the selected ion monitoring (5IH) mode. No PCBs or PCDFs were detected In the Phase 1 samples.
The Phase 2 experiments were conducted to determine the optimum temperature, oxygen, and residence time conditions for PCDF formation. The feed into the system was mineral oil spiked with three Individual PCB congeners which form PCDFs by the four known reaction mechanisms. A statistical analysis of the re sults for 33 runs Indicates that both temperature and oxygen have significant effacts on tha PCOF yield and that the Interaction between temperature and oxy gen Is synergistic. The results indicate that the optimum values are a tempera ture of 675C and an excess oxygon concentration of 8X. The residence time did not significantly affect the yield In tha range of 0.3 to l.S s, although lower times appeared to yield less PCDFs. Since residence time does not appear to significantly affact the PCDF formation, 0.B s was chosen as convenient for tha Phase 3 runs.
In Phase 3, duplicate test runs were conducted with mineral oil and silicone oil dielectric fluids contolnlng PCBs (Aroclor 1254) at concentrations of 0, 5, 50 and 500 ppm. A PCB askarel containing 7OX Aroclor 1250 and a non-PCB askmrel, containing mostly trichlorobenzene with some tatrachlorobanzene, were also tested In duplicate. PCDFs were found In all samples, except blanks, as shown In Figure 2. PCDDs were found In the samples from the trichlorobenzene runs and occasion ally at low levals In some of tha other samples. Up to 5,700 ng total PCOFs/mL of spiked feed oil or 4X conversion efficiency (PCBs to PCDFs) was observed for the mineral oil and silicone oil runs. The PCB destruction efficiencies calcu lated for tha 5, SO, and 500 ppm runs ranged from 79 to > 99%. Up to 19,000,000 ng total PCDFs/mt feed oil (19 mg/mL) or 3% conversion efficiency was observed for tha askarel fluid. Statistical analysis showed a linear ralatlonshlp for PCDFs formed versus the emount of PCBs (Figure 3). Although not statistically different, about twice the quantity of PCDFs was formed from PCBs In silicone oil than from the corresponding mineral oil samplas. All eight PCOF homologs 'were detected in the askerel runs with a maximum at the penteCDF (Figure 4). With a few exceptions, only tri- through hoxaCDFs were observed In the lower level runt, with e maximum generally at the trICOF homolog.
PCDFs end, to a letter extent, PCDDs are formed from the trichlorobenzene di electric fluid under the optimum PCB-to-PCDF conversion conditions. Up to > 110,000 ng total PCDFs/ml feed oil (> 0.004% yield) and 1,900 ng total PCOO/mL feed oil (0.0001% yield) were observed for the trichlorobenzene runs. The homolog distribution of PCDFs Is similar to that found from feeding PCBs. The amount of PCDFs formed It one to two orders of magnitude lower than for the askarel, but substantially higher then that for dleiactrlc fluid containing 500 ppm or less PCBs.
The results of this work Indicate that tha optimum conditions for PCOF formation from PCBs ere near 575*C for 0.8 s or longer, with 8% excess oxygen. (Mar these
3-14 MONS 215611
condition*, PCDF* art forntd from mineral oil or silicone oil contaminated with PCBs at S ppm or greater. PCDF* are alto formed from a trlchlorobenzene di electric fluid which contained no detectebla PCS*.
Further work is focusing on identification and quantitation of other product* from combustion of these samples, and on running samples of other.dloltctrlc fluids, including paraffinic hydrocarbons, ester hydrocarbons, end tatrechloroethylene.
The work was supported by the U.S. Environmental Protection Agmncy under Con tract No. 66-02-3938. A more detailed report was published at EPA Report No. 560/5-64-009.
REFERENCES USEPA. 1964a. Polychlorinated biphenyls (PCBs); menufacture, processing, distribution In commerce and use prohibitions; use In electrical transformers. Advanced notice of proposed rulemaking. (49 FR 11070-11063). USEPA. 1964b. Polychlorinated biphenyls (PC6s); manufacture, processing, distribution In commerce and use prohibitions; use In electrical -transformers. Proposed rule. (49 FR 39966-39969).
THERMAL COMBUSTION SYSTEM TO MODEL PCS FIRE CONDITIONS
ImtfChSWfMUt taftplinf
Figure 1
3-15
MONS 215612
TCTU COFt
PCDF FORMATION VERSUS PCS CONCENTRATION
91 -C
. lilk
Figure 2. Tetrachlorodibenzofurans fonmd from various Matrices. Note stellar Isoawr distribu tion for the TCDFs forned fro* PCBs. Consistent patterns Mere noted for the other hotaologs.
Figure 3 PCS A3XAREL
(70% Arador 1200, 30% '
KDf fOUwIM* MOte NO UnML
HONS 21*613
LABORATORY INVESTIGATION OF THE HIGH TEMPERATURE FORMATION AND DESTRUCTION OF PCOFt
Barry Dellinger, Wayne A, Rubey, Douglas L. Hall, and Sueann L. Maier
University of Dayton Research Institute
Environmental Sciences Group Dayton, Ohio 45469
The formation of polychlorinated dlbenzofurans (PCDFs) as a result of the thermal degradation of polychlorinated biphenyls (PCBs) has become an area of Intense Interest due to the reported toxicity of these partial oxidation products. Reports of their formation as a result of fires In PCB containing transformers, has caused the United States Environmental Protection Agency (US-EPA) to consider expanded regulations to reduce the risk of accidental combustion of PCB containing material
Most previous studies of the formation of PCOfs have been concerned Mlth the opti mization of conditions for their formation from PCBs. In this study, we have Inves tigated the effect of temperature and oxygen concentration on the rate of formation and destruction of PCDFs as well as the thermal stability of the parent PCB. Additional objectives were to identify other degradation products and provide some Information to elucidate the mechanism of PCB destruction and PCOF formation In a flow reactor system.
The thermal degradation of a single PCB Isomer was conducted under four reaction atmospheres at a constant gas phase residence time of 2.0 seconds, The Isomer selected for study was 2.3',4,4' ,5-pentachloroblphenyl (2,3',4,4',5-PCB). The oxygen availability In the reaction atmosphere Is described using the equivalence ratio, phi. Phf Is defined as the ratio of fuel to oxygen actually In the reactor divided by the ratio of fuel to oxygen required for complete combustion. The values of phi used In this study were 3.0, 1 .0, 0.2, and 0,05 which range from oxygen starved to very oxygen rich conditions as the values of phi become progressively smaller. A phi of 1.0 means there Is exactly enough oxygen available for complete combustion; thus, the percent excess air is zero. Thermal degradation experiments were conducted at various temperatures ranging from 500-1000C.
3-17
MOWS 215614
The thermal decomposition profiles and reaction products were determined using the Thermal Decomposition Unit-Gas Chromatographic (TDU-GC) System and the Thermal Decomposition Analytical System (TDAS). Both pieces of laboratory Instrumentation are dosed continuous systems that contain a narrow-bore quartz tubular reactor which Is capable of subjecting gaseous species to controlled there*,!'exposures with precise control of residence time and other reaction variables. Mixtures of oxygen and nitrogen were used to obtain the various reaction atmospheres tested In this study. A 40ug sample of 2,3,,4.4`,5-PCB was used In all experiments.
Following thermal exposure, the remaining parent material and the various thermal reaction products were cryogenlcally trapped. The numerous trapped samples were Subjected to In-line chromatographic analysis using a capillary column, IS m length by 0.75 am ID and possessing a 0.25 micron DB-5 film thickness. On the TOU-GC, a hydrogen flame Ionization detector was used for detection of the various solutes, and the data were processed and displayed using a Varlan CDS 401 chromatographic terminal. The Identities of the thermal reaction products from the decomposition of the PCB were tentatively determined from their electron Impact Ionization mass spectra obtained on the TDAS which Incorporates an LKB 2091 GC/MS. The reaction products examined were generated from the degradation of the PCB at BOOT and phi 0.2. Sample handling and chromatographic conditions were the same as those used for the TOU-GC testing.
Table 1 lists the major thermal reaction products tentatively Identified for the thermal degradation of 2,3* ,4,4` ,5-PCB. A variety of pyrolysis and partial oxldatlon products have been formed, with PCOF congeners representing the majority of the oxidative products. Significant quantities of partially dechlorlnated biphenyl con geners are formed along with dichlorobenzenes and trichlorobenzenes. Tetrachloroblphenylene Isomers were also observed. These are of particular Interest due to their suspected toxicity. The formation of tetrachloronapthalene Is Important because of Its apparent thermal stability. At 1000C for phi - 1.0, the reaction product tentatively Identified as tetrachloronapthalene exceeded the concentration of the parent PC8. As one might expect, the yield of pyrolysis products decreased with Increasing oxygen levels. However, the Increase In PCDF concentration with Increase In oxygen concentration was far more striking.
Table 2 presents the yields of observed PCDFs at various equivalence ratios. As the oxygen concentration Increased by a factor of BO, the yield of total PCDFs Increased by a factor of ID. The percentage of total PCDFs Identified as tetra Isomers ranged from 62-721. Thermal formatlon/destruetlon profiles for observed PCDFs for ph1*l,0 are depicted In Figure 1 .
MONS 215615 3-18
TABLE 1
MAJOR THERMAL REACTION PRODUCTS TENTATIVELY IDENTIFIED FROM THE THERMAL DEGRADATION OF 2 .3' .4 ,4 ' ,5-PENTACHLOROBI PHENYL
Product Class
Number of Major Peaks
Tetrachlorodlbenzofursns Trlchlorodlbenzofurans Pentachlorodlbenzofurans Tetrachloroblphenyls Trichl orobl phenyl Trichlorobenzene 01 chlorobenzene Trtchl oronaphthalene Tetrachl oronaphthal ene Trlchlorophenyl ethyne Diehl orophenyl ethyne Tetraehloroblphenylenes CgHaOCl
C1 0h3C13
2 2 1 5 1 1 1 1 1 2 1 2 1
1
TABLE 2 MAXIMUM WEIGHT * YIELO OF PCOFs AS A FUNCTION OF REACTION ATMOSPHERE
0.05 0.2 1.0 3.0
TEMPERATURE OF MAXIMUM YIELO (C)
750 800 900 850
TRI-CDFS
0.66 0.34 0.13 0.068
WEIGHT X YIELD TETRA-C0F5 PENTA-CDF5
4.3 1 .7 1 .3 0.71
2.0 0.56 0.25 0.21
TOtAl-PCDfS
6.9 2.6 1 .7 0.99
The relative yields predicted for PCDF Isomer production may be estimated by examine-
tlon of the reaction enthalpies for the global reactions. Calculations reveal that an overall reaction Involving elimination of a hydrogen atom and a chlorine atom
from ortho positions to form either 2,3,7,8-TCDF or 2,3,6,7-TCDF and HCl, has a
reaction enthalpy of *29.7 kcal/mole. Elimination of ortho hydrogens to form either 1 ,3,4,6,7-PCDF or 1,3,4,7,8-PCOF and H2 has a reaction enthalpy of -14,2 kcal/mole.
Using these values as a "zeroth" order approach to the reaction kinetics of PCOF formation, one would predict that the two tetra Isomers would be the predominant
reaction products. Two major TCOF peaks were, In fact! observed that accounted for
60-70t of the total PCOF formation. Further Isomer specific Identification work Is
strongly Indicated.
MONS 215616 3-19
Figure 1. PCOF Formation/Destruction Profile* In summary, the results of this study show that the yields of PCDFs formed from the thermal degradation of 2,3',4,4' ,5-PC8 are on the order of a few percent; and these yields Increase as the oxygen concentration Increases (^*3.&+4a0.05), The predomi nant mechanism for their formation is HC1 elimination. For equivalent combustion conditions. It appears that PCOFs can be destroyed at temperatures that are sufficient to destroy the parent PCB. However, there Is evidence for formation of pyrolysis products such as tetrachloroblphenylenes and chlorinated polynuclear aromatics that are major reaction products at very high temperatures.
This work was performed under partial sponsorship by the US-EPA under Cooperative Agreement CR-810783 and has not been subjected to the Agency's peer review process.
HONS 215617 3-20
WESTINGHOUSE ELECTRIC CORPORATION TRANSMISSION AND DISTRIBUTION BUSINESS UNITS
SHARON, PENNSYLVANIA 16146
RP-2028-11
'
PRQOUCTS OF INCOMPLETE COMBUSTION OF OIEIECTRIC FLUIDS
BY
OR. C. CLAIR CLAIBORNE
INTRODUCTION
Increasing publicity concerning transformer related fires and the resulting public concern over the hazards associated with these fires has prompted governmental act* ion. The Environmental Protection Agency (EPA) consequently issued a request for Information as a first step in promulgating a rule concerning transformer fires (1).
Although this rule is primarily directed at transformers which may contain some PCB's, there have been Instances such as the BART tunnel fire In San Francisco and the underground fire In New York city In which partial combustion products of miner al oil were suspected of harmful Interactions. The growing public concern over combustion products from plastic seat cushions, plumbing materials and other cnmnon1y encountered Items will likely expand to Include electrical Insulating materials.
In the advance notice of proposed rulemaking mentioned above, the EPA requested In formation on the partial and complete combustion products of several transformer in sulating materials. The fluids Identified were chlorinated hydrocarbons, fluoro carbons, high temperature hydrocarbons, non-PC8 askarels, mineral oil, and silicones. Although some Information Is available on the products of complete combustion, 1,e., with an excess of oxygen present, data Is lacking on the products of partial com bustion. In many fires, partial or Incomplete combustion may be the predominant mode of combustion.
When fires occur In confined areas such as a building, tunnel, or vault, the flow of air may be limited or restricted while the rate of burning may be so rapid that the oxygen Is consumed faster than It can be replaced. This may result in the for
mation of many toxic substances such as carbon monoxide, hydrogen cyanide, hydrogen
chloride, halogens, or carcinogenic organic compounds.
The objective of the project described In this report was to examine the products formed from either complete or partial combustion of fluids commonly used as die lectric materials, particularly In transformer applications.
HONS 215618 3-21
EXPERIMENTAL
Five liquids were selected for evaluation In this program: Tetrachloroethylene tCjCI^), trlfluorotrlchloroethane (C^Cl^F^), polydlmethylslloxane, a mineral oil, and a high temperature hydrocarbon. The particular tradenames of these materials are, respectively: WECOSQL*, Freon 113, Dow Corning 561 Silicone Transformer Liquid, Wemco C, and RTEmp. In order to characterize the reacting materials In the mixed compounds, mineral oil and the high temperature hydrocarbon, high performance liquid chromatography was carried out on a Oupont 650 liquid chromatograph. The best separations were achiev ed for Wemco C utilizing gradient elution with methanol and water; for RTEmp, with tetrahydrofuran (THF) and methanol In the gradient elution mode. To establish boundary levels of likely products of partial combustion to be found In analytical Investigations, thermodynamic equilibrium concentrations were calcu lated from 300 to 1500 K (27 to 1227C) at 100 Intervals for each of the fluids mixed with ZOX and 60S air by volume. For C^Cl4 calculations with IS H?0 were also made to approximate atmospheric conditions and evaluate the potential for for mation of KCl. These calculations were performed on a main frame computer and the major species of Interest were displayed In semllog plots. Two experimental arrangements were selected to evaluate the combustion process and the resulting products. In the Materials and Manufacturing Technology facilities, the combustion was carried out In Dupont thenoogravlmetrlc analysis (TGA) equipment The material to be Investigated was placed In a platinum boat and dry air was ad mitted to the combustion chamber at a controlled rate In order to achieve the de sired levels of 30X and 70* of the air that would be required for theoretical total combustion. The Instrument was then programmed to heat the combustion chamber from room temperature to 1000C at 30/m1n. A trap containing Ice water was located at the exit of the chamber. In order to contain the reacting material In the combus tion chamber. The combustion products were collected In cold traps placed In two separate Dewar flasks, containing a mixture of dry-ice and Isopropanol (-900C), on the one hend, and methyl butane and liquid nitrogen (-160C), on the other hand. The materials collected In each of these traps were analyzed by gas chromatography. The other experimental arrangement was located at the Research and Development
HONS 215619
3-22
Laboratories of Westlnghouse. This apparatus consisted of a stainless steel tube which was heated to 1000C. The reactant was then admitted to the tube. The amount of material Injected Into the preheated tube was varied In order to achieve the desired levels of 305 and 705 of the air required for theoretical total combustion, The combustion products were then withdrawn with a microliter syringe and Injected Into a Hewelett Packard 5935 GC-MS (gas chromatography-mass spectrometry) system for analysis. (* Westtnghouse trademark)
RESULTS: The decomposition of C^Cl^ at 1000C In varying levels of air generated substantial quantities of C1^ and CO^. Phosgene was not detectable either by gas chromatography or mass spectrometry. These results are consistent with the thermodynamic predic tions. In the Materials and Manufacturing Technology department apparatus, a small amount of HC1 was found. The MCI was likely produced from sorbed water on the In terior surfaces of the combustion apparatus, because this system Is heated from ambient temperatures. The silicone fluid generated copious amounts of SlO^ which tended to plug the tub ing leading to the traps, thereby Influencing the capture of the product gases. Aside from COj. the products of the decomposition were methane, carbon monoxide, and water, on the order of 15 by volume, with amounts of ethylene, acetylene, and ethane between 0.01 and 0.15 by volume. Tentative results from partial combustion of CjCI^Fj, Indicated six compounds separable by gas chromatography, besides CO^, The thermodynamic calculations In dicated that likely products of the decomposition of CjCl^F^ would be CF^, Cl^. COFj, CO, CCIF^, and phosgene. However, the Identification of these compounds will necessitate confirmation by mass spectrometry, as some of these materials are not readily available as standards. The determination of the combustion products of the mineral oils Is currently under way, and will be reported at a later date.
REFERENCES:
1. Federal Register, March 23, 1984, Page 11070.
MONS 215620
3-23
PYROLYSIS AND COMBUSTION Or MINERAL OIL, TETRACHLOROETHYLENE AND SILICONE OIL MIXTURES CONTAINING AROCLOR 1254
George Eldon tfadaworth Canter for Laboratoriet and Raaearch
New York Stata Department of Health
Thia laboratory haa initiated, with Elactric Powar Reatarch Inatituta tupport, a major ttudy of tha tendency of varioua fluida, aithar neat or contaminated with Aroclor 1254, to fora polychlorinatad dibencofurana (PCDFa) and polychlorinated dibentodioxina (PCDDa) whan aubjectad to high temperature! > Although a broad range of fluidt of potential or currant uaa aa dialaetrica will eventually be atodiad, thia report praaanta praliainary data obtained froa atudiaa of aineral oil, tatrechloroethylana, and ailicona oil during pyrolyeie and coabuation.
For purpoaaa of thia work, two diatinct heating ragiaana wara atudiad, Saaplea ware either pyrolytad (heated in tha abaenca of a flaae) or coabuated (aithar injactad into a flaae or haatad under condition! raaulting in aalf-ignition). Fyrolyaaa wara conducted uaing a aiapla tharaoatatically controlled apperetue, capable of acconaaodating glaaa or quart! tubaa of diaaetare up to i a within itt 9 cm-long haatad region. In order to ainiaiaa hatarda and diepoeel probleae, yat perait eufficient product formation to facilitate detection of PCDDa and PCDFa, pyrolyaaa wara parforaad on 100 ul aaaplee. In an attempt to diffarantiate thia work froa other earlier and ongoing invaatigationa, aa wall aa to aiaulata aora accurately certain ceteetropfalc incident!, pyrolyaaa ware conducted at ataoapharic preaeura. The naeaielty of containing tha atarting Mtariala and non-gaaaoua pyrolyeie product! in an open ayataa led to tha uaa of I w IS t 0.5 K glaaa tubaa, aealad at one and, and mounted vertically. Tha material to be pyrolytad waa dapoaitad at tha aealad end, than inaartad into a tight-fitting preheated natal block in tha heating apparatua. Typically, tha liquid refluxed up tha inner walla of tha tube; tha length of tha tuba and ita comparatively large unhaatad volume
* kept tha reflux laval wall below tha open and in all axpariaenta. To aaaura containaant, tha topaoat 5 ca of tha tuba wore chiliad in dry ica and tha and of tha tuba waa connected to a charcoal trap. No vialble material waa trapped in tha chiliad region and excellent noae balancaa warn generally obaervad.
3-24 HQMS 215621
The dee ifn of the coabuetion epperetue wee eonetreined by the neceeeity of eeeurint that ell discharged geee* pace through a trapping eyetea capable of efficient removal of FCBe end any potentially toxic producta. The coabuetion chaaber coneiete of a 'l H quart* tube with a 22 m lid. One and of the chaaber accommodate* a modified blaet burner and inlet tube through which the end of a 1/16" x 24" syringe needle ie introduced via airtight connection*. The inlet tube end needle era mounted to allow aeaple introduction into the flea* of the bleat burner. Semple addition 1* accoapliahed ueing a 10 al eyring* mounted in a worn eyeing* drive. The combuetion chaaber ie mounted in e pyrolyei* furnace capable of maintaining temperature* of 100 - 1100C in three independently controlled eona*. The effluent of the coabuetion chaaber i* peeeed through * water filled iapinger, then an XAD-2 packed edaorbent tub* idilch in turn 1* attached through an orifice to * vacuum line. XAD-2 he* been ehown her* end aleatrtiere to be en efficient trapping agent for dibaneofurane end dibenaodioxine.
Preliminary experiment* to refine experimental epperetue, to develop naceeeary
technique* and to optiait* reaction condition* were conducted ueing eingl* biphenyl
congener*. Thi* approach ainialted expoaur* of laboratory peraonnel to potentially
dangerou* materiel* and einplified analytical procedure*. It we* anticipated that
capillary CC/FID or CC/lC would permit quantitation of the on* or a few PCDF
congener* produced in eueh reaction*. Thi* expectation wa* reel ifed with on*
exception; pyrolyei* of ainerel oil, even in the abeance of biphenyl*, produce* a
very eoaplax aixtur*. Deepita elaborate eaapl* cleanup, reliable data could not be
produced without reaort to GC/MS technique*.
,
Before diecuaeing reeult* end interpretation* it ehould be anphaeieed that thee* tudiee are on-going and eubatantial data remain* to be gathered. Further, data interpretation i* coapliceted by the nature of the atmoapheric preeeure pyrolyei* expariaant. Thua, actual teaperature* in*id* the pyrolyei* epperetue in the heated tone ere not well defined, aince the reflux procea* may provide an efficient heet-tranefer aechgniea. Further, the fraction of a particular biphenyl eongener in the heated eon* verau* the fraction in the cooler reflux region will be a complex function of that congener'* phyeical properties, and those of the other constituent* of the bulk liquid,
Aroclor 1264 he* bean pyrolytad neat, and a* $,000 and $0 ppm aineral oil solution* *t $00, 550, and 600C, and the extract* analyted for tatra end pent* CDF* using high resolution CC/KS. Pyrolyei* of the 50 ppu aixtur* gave concentration*
HONS 21S622 3-25
of 2,3,7,8-TCDF, total TCDF and total pente-CDF below detection Unite (0.4, 1 end 1 ng/g, reepee lively) at all three temperature#. Concentrat lone of PCDFe produced on pyrolyeie of naat Aroclor and 5.000 ppm eolutione wara moderately eaneitlve to
o nominal pyrolyeie temperature, with maximum formation at 550 C. All data are coneietmt with the propoeition that tatra and penta CDF yialda are'roughly proportional to PCS concent retione in tha etarting mixture. However, the detection limit for tha SO ppa mixture# wee about an order of Mgnituda higher than tha concent ret ione expected baead on thie aeeuaption. Lower detection Unite will be lought for theee eeaplae.
An interacting feature of tha Mineral oil-Aroclor 1254 data ie the clear and reproducible diffarancee between the pattarne of tatra-CDPe and pente-CDPe formed by pyrolyeie of neat Aroclor 1254 vereue thoea formed by pyrolyeie of tha 5000 ppa mixture. For example, 2,3,7,6-TCDf and co-elutere compriee 16-211 of tha tetra CDF mixture formed from neat Aroclor, but 45-551 of the mixture from mineral oil/Aroclor. Other diffarancee are apparent whan chromatographic tracae are compared.
preliminary experimente to eeeaee the tendency to form PCDFa from the pyrolyeie of
biphenyl-containing tetrachloroathylene (TCE) have been completed. Thue, 5,000 ppm eolutione of biphenyl, 2-chlorobiphenyl, and decachlorobiphenyl were pyrolyaad at
verioue temperature#. No evidence for the formation of the expected dibenxofuran product# wee obtained with detection limita eorreaponding to 0.11 convereion for dibenxofuran iteelf and 0.0011 for octachloro dibenxofuran. However, literature
.
data euggeete that pyrolyeie of TCE generatea free Clj ae well ae chlorine redicele. Thue, the poeaibility that biphenyl and 2-chlorobiphenyl were inetaad forming a complex mixture of chlorinated dibentofurane not readily identified by
einpla gee chromtography required inveatigation. Scanning CC/HS ahowed that if any PCDFe were formed, their concentratione wara below detection limit. It confirmed that chlorination of biphenyl did occur, but yield# wore low (ce. 11). Inetaad, three much larger peeka with empirical formula C^H^Cl^ were obaarvad. A
reaeooable atructure for thie compound poatulete ortho, mete end pare eubetitution
of a CjClj group on the biphenyl atructure. Effort# are underway to confirm
tha identity of thie compound. However, if thie reaction repreaente a facile reaction pathway for biphenyl daetruction, FCDF formation My be miniMl in thie Mtrix, Pyrolyeie of TCE (neat) and TCE containing 5,000 ppa Aroclor 1254 warn conducted in duplicate at 500, 550, and 600 and aubmitted for high
reeolution CC/NS analyeie.
3-26 HONS 215623
Pyrolyaia of 2-ehlorobiphenyl and 2,3,4,5,6>pentaehlorobiphenyl $000 ppm eolutiona in ailicona oil euggeeted that tha optimal temperature for PCDF formation wan ca. 5S0C. Scanning CC/H5 expariaanta damonatratad tha formation of aignificant concent rationa of fluorana from 2-chlorobiphenyl Ccorraaponding to CHj inaartion and CL loaa) and varioua conganara of mathylatad/chlorinatad fluoranaa from pentachlorobiphanyl Duplicata aamplaa of Aroclor 1254 (5000 and $0 ppm) in ailicona oil hava baen pyrolytad at $00, 5$0, and 400 and eubmittad to CC/HS for analyaia. Soma interaating general obearvationa hava baan mada on tha combuation proceaa. For example, combuation of biphanyl in TCE produced dacraaaing net dibantofuran aa tha raaidanca time waa varied from 1ft aac to 6 aac and tha wall temperature maintained at 450C. la contraat, at S50C1 there ia a net ineraeaa in dibantofuran yield aa raaidanca time dacraaaaa; thia auggaata that at tha higher temperature, eignificant dibantofuran daatruction ia occurring, Thera era alao large affaeta on dibanaofuran yield in tha praaanea of different aolvanta: typically yialde obtained on combuation in TCI are much higher than thoaa obtained in ailicona or mineral oil. Soma aharp diffaraneaa on tha affaeta of particular variable parametere on dibantofuran yielda hava alao baan noted.
HONS 215624 3-Z7
FORMATION OF PCOFs FROM PCBS
Christoffer Rappe, Stellan Marklund and Lars-Owe Kjeller
Department of Organic Chemistry, University of Umei, S-901 87 UMEA, Sweden
In 1978 it was found in our group that PCBs can be converted to PCOFs under pyrolytic conditions. The pyrolysis of PCBs in sealed quartz ampoules in the presence of air yielded about 30 major and more than 30 minor PCOFs. The optimal yield of PCOFs was about 10* calculated on the amount of PCB decomposed. Later we studied the pyrolysis of 15 individual synthetic PCB Isomers. This study showed that the formation of PCOFs can follow several competing reactions. The reactions involve the loss of ortho-C^ and ortho-HCl with and without a Z,3-Chlorine shift or loss of ortho-H^. In the present report we are discussing identification and quantification of PCOFs in the following samples: a. used PCBs b. PCBs after sparking experiments c. samples from thermal PCB degradation d. samples from PCB fires
The analytical method used is described earlier.
Results
(Jsed_ capaci torj
We have opened some used and swollen capacitors, collected and analyzed the drained PCB. The levels of PCOFs was approximately 2 ppm, mainly tetra-CDFs which is similar to the levels we found for the new and unused PCB.
Examination of the paper layer reveaked dark points, probably caused by
electrical arcing. The PCB around these dark spots was extracted and ana
lyzed. The levels were similar to the levels found in the drained PCB or
new PCB.
'
No increase in PCOFs (approx. 2 ppm) could be found after up to 7 sparks (18 kV, 2 yF) in pure PCB. In another experiment 1* of 1-epoxyethyl-3,4 -epoxycyclohexane (Union Carbide ERL 42 06) was added before the sparking (4 sparks, 15 kV, 2.5 pF}. In this experiment the PCDF levels increased, see isomers the increase was 30 times, for others no increase was found.
IbsnPSj.degradati9n_of.P5g
Ue have analyzed samples taken from the thermal degradation of PCB in special incinerators including rotary cement kiln. The critical parameters are minimum temperature minimum residence time excess of oxygen
A test-burn was performed In a Swedish rotary cement-kiln (>1500C, >5 sec) obviously with oxygen deficiency. A series of PCDFs were found in the emis sions, Figure 2 illustrates the hexa-CDFs found in these samples, 15 of the 16 isomers could be found.
PCB.fires
During the period 1981-1984 a series of accidents have been reported in Scandinavia and the United States that can illustrate this risk. These acci dents can be subdivided into three different categories,
a) PCB fires with mineral oil as the external energy source b) PCB fires with electrical energy as the external energy source c) Explosions in PCS filled capacitors These accidents all resulted in the formation of PCDFs, in some cases also polychlorinated dioxins (PCODs), biphenylenes (PCBPs) and pyrenes (PCPYs).
MONS 215626 3-29
3-30
Figure 1. Tetra-CDFs found in a normal PCB
HONS Z15627
No Hexa-CDF 374
Figure Z. Hexa-CDFs from a PCB test burn.
Hexa CDPs Cement Kiln PCB Test Bum
234678
3-31
215628 MOHS
PART 4: DOCUMENTATION OF FIRES, SPILLS AMO CLEAN-UP
SR1AM WEST - MODERATOR
HONS 215629
DECONTAMINATION OF FIRE FIGHTERS' PROTECTIVE CLOTHING
KITH TRICHLOROTRIFLUOROETHANE
'
John R, Komlnsky, M.Sc., C.I.tl. National Institute for Occupational Safety and Health
Cincinnati, Ohio
Eugene T, Hcllvalne, M.Sc. Quedre* HPS Inc
Gainesville, Florida
ABSTRACT
A United laboratory study was conducted to eveluate the efficiency of a l,I,2-tr1chloro-l,2,2-tr1f1uoroethane-based system to decontaminate Hornex? protective clothing worn by fire fighters during a fire at an electrical transformer oil reclamation facility. Ooth garments contaminated at the site of the fire and garments that were contemlnated In the laboratory with a known concentration of polychlorinated biphenyls (PCBs) were laundered using the l.l,2-tr1chloro-l,2,2-tr1fluoroethane-based system. The removal efficiency of the system was determined by the ratio of the after to before PCB concentrations In terms of mlcrograma of PCB per gram of fabric. Overall, the PCB removal efficiencies ranged from 66 to 99*. Until permissible fabric concentration levels for PCBs are established. It can not be determined whether this system Is adequate to allow the safe reuse of the clothing. Research Is urgently needed to define decontamination end-points for reusable protective clothing, l.e., "how clean Is clean".
HONS 215630 A-l
I HTrrOD UCTI ON
Uncontrolled fires Involving polychlorinated biphenyl (PCB) containing fluids produce a complex and potentially highly toxic mixture of chlorinated products In the soot* Including polychlorinated dlbemofurans and polychlorinated dlbenzo-p-dloxlns (1*6). In some of the Incidents, there also has been the formation of polychlorinated derivatives of blphenylene, chrysene, end pyrene (4,5,7). These Incidents have resulted In the contamination of fire fighters' protective clothing and equipment with PCOs (8-10) and most probably the polychlorinated pyrolysis products.
In early 1984, a fire occurred tt an electrical transformer oil reclamation facility In Jack son villa, Florida (11). The fire destroyed the building and several storage tanks containing PCB-transformer fluids and various organic solvents. A sample of the soot contained 1460 mlcrogrtms PCB (as Aroclor 1260) per gram (ug/g). and samples of liquid that hed pooled on the site contained 67 to 5330 ug/g Aroclor 1260 (11). Neither the soot nor the liquid simples contained detectable concentrations of polychlorinated dlbenzofurans. or dlbenzo-p-dloxlns (tetra-through octo-chloro horologs), or the respective 2,3,7,8-tetra Isomers (11).
The protective clothing worn by the approximately 40 fire fighters, Nomex* turnout coats In combination with bunker pants, was assumed to be contaminated with PCBs. An attempt by the on-site cleanup contractor to decontaminate the garments with a common method (l.e., detergent-water wash with a water rinse) showed a mean residual KB
HOMS 215*31 4-2
concentration of 239 ug/g (S.D. 1 411, range 15 to 1060, n5). These levels of contaminatlon renilnlng In the protective clothing after the detergent wash prompted a limited laboratory study to evaluate the efficiency of a I.l,2-tr1ch1oro-l,2,2-tr1f1uoroethane based system to remove PCBs from ti Home** fabric protective clothing. This paper describes the results of the laboratory e va 1 ua tl on,
METHOOS ANO MATERIALS
Oecontamlnatlon Process Description
A RAOKLEEN* Model 1550 Clothing Decontamination System* was used to remove the PCS contamination from the protective clothing (12). The RAOKLEEN* System Is a l,l,2-tr1chloro-l,2,2-tr1f1uoroethane (Freon* 113)-based dry cleaning machine (Figure 1). The contaminated clothing Is placed In the cleaning cheater which consists of a sealed, rotating drum that will cause the garawnts to tumble .through the solvent. Solvent Is puaiped from the solvent reservoir through the filter adsorber set and then flows through the cleaning chatter. The contaminated solvent then returns to the solvent reservoir. Freon* 113 vapor and vapor pressure buildup within the sealed system are controlled by vapor recirculation across a condenser coll, with condensate returning to the solvent
Mention of company names or products does not constitute endorsement by the National Institute for Occupational Safety and Health.
4-3 MONS 215432
reservoir. Periodically, the advent It regenerated and purified by a built-in distillation process. Contaminants are removed from the system as still bottoms and materials trapped on replaceable filter-adsorber cartridges.
Fabric Sampling Protocol
The test protocol consisted of decontaminating *oth site-contaminated and laboratory-contaminated garments. The site-contaminated garments are those that were presumably contaminated during the fire. The laboratory-contaminated garments are those that were site-contaminated, but also were contaminated In the laboratory with a known concentration of PCB at Aroclor 1242. The PCB test concentrations of 2.4, 9.0, 33* (volume-to-volume In dielectric grade mineral oil) and 100* were applied via a brush to selected areas on the garments to the point of saturation. The voluem of PCB applied was approximately 20 milliliters.
The fabric sampling technique consisted of marking an area five Inches square (12,7 cm) and within that are* marking off five one-inch squares (2.54 cm). Four of these five one-inch squares were located at the four corners of the larger square, with the fifth located at the canter. To determine the pre-decon-amination concentration, each of the five one-inch squares were cut from the larger square to form * composite sample. To determine the post-decontamination concentration within the same area, the remaining fabric within the marked off section was removed. This checkerboard technique was used to average out or minimize
4-4 HONS 215633
concentration variations within the temple arte. To eliminate variation! bated on cutting errort and unequal treat being removed, all resultt were normalized by reporting the contaminant concentration In terms of micrograms of PCB per gram of fabric (ug/g). The authors assured that bulk density variations In the fabric and substrate were minor. For comparison consistency, fabric sections were removed from the same approximate location nn each turnout coat and bunker pant saapled.
The removal efficiency of the system was determined by the ratio of the after to before PCS concentrations In terms of tig PC8/g fabric. The pre-and post-decontamination changes In PCS concentration were compared using a paired t-test.
The Nomex* fabric samples were extracted with toluene and analyzed by gas chromatography with electron capture detection. The presence of Aroclors 1242 and 1200 was determined by comparison with standard samples of same obtained from U.S. Environmental Protaction Agency. Quantitation was performed by summing the heights of the five major peaks of the standards, and comparing that to the sum of the tame peaks In the sample. The Instrumental limit of detection was 0.5 ug/g for both Aroclors, Since no recovery studies were performed on the Nomex* fabric, the results are considered to be the minimum amount of Aroclor present.
HONS 215634 4-5
RESULTS AND DISCUSSION
Table .1 presents the pre-and post-decontamination concentrations of PCBs and percent removal for the site-contaminated garments.. The PCB concentrations prior to laundering ranged from 5.3 to 490 ug/g (mean 85, S.D, - 130). By comparison, the pnst-deeonteml nation concentrations ranged from 1,1 to 25 ug/g (mean '.9, s.D. - 6.4), The percent of PCBs removed ranged from 66 to 99*, with a mean of BB* and a 95* lower confidence limit of B2S removed.
Table 2 presents the pre-and post-decontamination concentrations of PCBs and percent removal for the laboratory-contaminated garments. Although the PCB concentrations applied to the garments ranged from 2.4 x IQ4 to 1.0 x 10 ug/g (2,4 to 100S, volume-to-volume), the actual concentration In the fabrics ranged from 1.6 x 104 to 9.9 x 10s ug/g (1.6 to 99*. welght-to-welght). The post-laundered concentrations ranged from 5.4 to 230 ug/g (mran 63.5, S,0, 64,2), The reduction In PCD concentration exceeded 99* for all of the garments tested.
Post-laundering Inspection of the garments revealed that the tumble-wash action of the machine did not appear to cause any physical damage to the garments such as cuts, abrasions, or alteration of the retro-reflective trim. Tests are currently being conducted hy an Independent laboratory to determine If solvent^ashed garments still meet key performance criteria specified In the national fire Protection Association (NFPA) 1971 Standard on Protective Clothing for Structural Fire Fighting (13).
HONS 215635 4-6
CONCLUSIONS This limited *tudy Indicates that relatively high pereentege of fire-borne and liquid PCB contamination can be removed fro* fire fighters' protective clothing using a trlchlorotrlfluoroethane-based system. The toxicological significance of the PC8 contearination levels remining In the garments Is uncertain. However, until permissible fabric concentration levels of PCBs are established. It cannot be determined whether this technique is adequate. The discarding and replacement of fire fighters' protective clothing and equipment can be very costly (10,11). The Incident descrlhed In this paper resulted In the replacement of approxlmtely 40 sets of bunker gear (Including turnout coats, pants, and boots) with a replacement cost of approxlmtely 820,000. Research Is urgently needed to define decontamination end-points for reusable protective clothing. I.e,, "how clean Is clean*.
4-7 HONS 215636
REFERENCES
1, U.S. Environment*! Protection Agency. Polychlorinated Biphenyl* (PCBs) Manufacturing, Processing. Distribution In Commerce and Die Prohibition*: Die in Electrical Equipment Transformers. 40 CFR 761 Federal Register VolT 49, April 19, l9B4, pp.
11070-110B3.
2. Schecter, A. Contamination of n Office Building In Binghamton,
New York, by PC6s. DIoxTnsT FuransaiuTdlphenylenes after an
Electric*Pane I ind ElectHcaMransforamr Indent.
1
Chemosphere, Vol. 12, No. 415, pp. 669*660, 1983.
3. De* Rosier*, P.E., PCBs. PCDFs. and PCDOs Resulting from ^tnsformer/Ctptcltor-Fire*: An Overview. In; Proceed!not: 1983 PCB Seminar. Electrical Power Research Institute. EPRI EL-3SB1, June 1984.
4. Rappe, C., Marklund, $., Bergqvlst, P., et al. Polychlorinated Dioxins (PCODs), Dlbemofurans (PCDFs) and Othcr'Tolynuclear Aromatics (PCpnasI Formed During"PCWires." themca Serfpta. Vol. 20. pp.'S-51.1WJ.---------- 3----------------
5. Williams, C.H., Prescott, C.L., Stewart, P.B,, et al. Formation
of Polychlorinated Dlbeniofurans end Other Potentially Toxic'..... Chlorinated Pyrolysis Product* in PCB Fire*. In Chlorinated Dioxins and Dlbeniofurans In the Total Environment, Keith, L.H., Editor, Butterworth Publishers, Stoneham, Massachusetts, 1984,
8, Kominsky, J.R, The Chemistry of Electrical Transformer Fire*. Presented at the American Public Health Association fleeting, Anaheim, California, November 11-1$, 1964,
7. Stallings, D.L. Chlorinated Dlbeniofurans and Related Compounds In Soot Formed In a Transformer Fire in Binghamton, lieu Tort.' Preliminary Report, Columbia national Fisheries Research Laboratory, U.S, Fish and Wildlife Service, Columbia, Missouri, March 31, 1961.
6. Orris, P,, Kominsky, J.R., Melius, J.H., t al. Exposure to Polychlorinated Biphenyls from an Overheated Transformer. Submitted for publication, l9B4.
9. Kosrtnsky, J.R. Health Haiard Evaluation No. HETA 84-490. National Institute for Occupational Safety and Health, Cincinnati, OMo, 1984,
10. Komlnsky, J.R. and Melius, J.M. Health Haiard Evaluation Ho. 84-372, National Institute for Occupational Safety and Health, Cincinnati, Ohio, 1C84,
4-8 HONS 215637
11. Komlnsky. J.R. Health Hatard Evaluation Ho. 84-169. National Inttltute for Occupational Safety and Health, Cincinnati, Ohio,
1984.
12. RADKLEEH* PC Model [550, Ope rati no and Maintenance Manual.
Guadrex HPS Inc, Gaines vine. Florida 32663.
"
13. National Fire Protection Association. MFPA 1971; Standard on Protective Clothing for Structural Hre Fighting. 1981 Ed.. National Fire Protection Association, Ouincy, Massachusetts,
1981.
MOMS 21S63S 4-9
Table 1 PC6* Removed from SIte-Contaminated Garment*
uo PCB/g fabric
Pre*0econ
post-oecon
480 25 240 13.3 200 1.8
68 1.3 60 5.4 6 3.5
37 5.1 35 4.2 35 2.4
15 1.1 14 2.9 10 1.2
7.6 1.3 6.7 2.2 5.3 1.8
p<0.05, t2.4C
I Removal
C5 95 99
98 91 94
86 88 93
93 79 88
83 67 66
4-10
HONS 215639
Table 2 PCBt Removed from Lab-Contaminated Carmenti
ug PCB/q fabric
pre-Decon
Pott-Decon
9.9 x 10s 9.4 x 10S 6.3 x 10 6.3 x 10$
5.4 x 10s 2.5 x 10 1.8 x 10s 1.8 x 10
7.2 x 104 6.1 x 104 5.8 x 104 5.7 x 104
2.0 x 104 1.8 x 104 1.7 x 104 1.6 x 104
24 ICO
60 53
230 no 97
62
13 8.2 63.1 63.5
If.4 5.4 18
11.9
p<0.05, t3.34
X Removal
99 99 99 S9
59 99 99 59
99 99 99 99
99 99 99 99
MQNS 215640 4-11