116 CHAPTER 7 1962 Guide And Data Book Pressure Reducing Valves. Suitable single-seated valves are preferable. The valves should be selected from the manu facturer's rating regardless of pipe size. Pressure gages are necessary at valve and control points. Valves require some auxiliary source of power for valve positioning, if they are to be controlled from a remote point to regulate terminal pressure. (See Chapter 6 for detailed recommendations re garding pressure reducing valves.) Traps. To assure adequate drainage of piping, extra trap capacity and large drip pockets should be provided. Extra heavy or corrosion-resistant trap discharge piping is de sirable. On steep grades or in high-velocity steam special deflector scoops or baffles should be placed in the line to direct condensate into traps.u Supports. Due to humid conditions in conduit and man holes, it is desirable to use stainless steel supports. Instruments. The instruments required will be the mibr as for other steam systems as described in Chapters 13 and 16 of the 1961 Guide And Data Book, with modifications de pending on the records desired with regard to pressures temperatures maintained or the records of response of the system to varying load demand.0 Branch Connections. Branch connections should be made at or near anchor points; if not, ample clearance must be provided around the branch to take care of pipe movement. Insulation Insulating materials constitute a primary element of dis trict steam distribution structures and must be suitable for underground service. Insulation should be noncombustible, vermin-proof, moisture-resistant, durable, non-corrosive to steel pipe especially when wet, and able to retain its posi tion in relation to the pipe line. It should be of a type which, if flooded, will dry out and regain its original physical, chem ical and insulating properties. It should be relatively un affected by such chemicals as are usually found in ground or other contaminated waters. It should have the lowest practical heat conductivity consistent with the given re quirements. Insulating properties vary with soil conditions, weather variations, types of conduits used, and, if in tnnn^ the amount of ventilation. The selection of insulation to provide for the various conditions is covered in District Heating Handbook--Third Edition. Where underground insulation is applied directly to the pipe, copper wire is normally used to band the covering. Insulation may be poured as a mono lithic structure in a suitable duct-. Where insulation in an existing conduit has deteriorated the line may be reinsulated with a minimum amount of excavating by use of some of the materials used in monolithic conduits.1* Insulation is dis cussed further in Chapter 22 of the 1961 Guide And Data Book, and studies of heat loss from bare and insulated buried pipe are given in District Heating Handbook'* and in Piping Handbook. RETURN OF CONDENSATE If the condensate can be returned to the plant to be used for boiler feed water at an overall cost less t.ha.n that re quired to process raw water, the installation of return lines parallel to the steam supply lines should- be given considera tion. A typical analysis of comparative costs of returning condensate and processing feed water is given in District Heating Handbook.1* Return of condensate by gravity is desirable, but usu ally because of terrain conditions or user's return facilities; the condensate is pumped back under pressure. Pipes carrying condensate are more subject to corrosion than other parts of the system. Care must be taken to giv* proper pitch to the pipes and to provide proper venting of noncondensable gases. (See Chapter 15 of the 1961 Gome And Data Book.) BUILDING PIPING AND EQUIPMBsfT There are certain fundamental principles that should be followed in the design of a building heating system which is to be supplied from district steam mains. Some of these are unique to district heating and some, although tiiey may apply to any building have been demonstrated to'be par ticularly important when district steam is used. District heating companies have certain regulations regarding tile consumer's installation to safeguard the mutual interest of supplier and consumer and to insure satisfactory Anri comical service. When an installation is designed, local regu lations and code requirements1* should be observed. - Zoning. Where the hours of occupancy or heating loads differ in various sections of the building, it is good practice to install separate supply lines to the different sections. For example, in an office building with first floor stores or r&taurants open in the evening, a separate man supplying the first floor will permit the steam to be shut off from the remainder of the building in the late afternoon. The divi sion of the building into zones, each with a separatelycontrolled heat supply, is sometimes desirable, as it permits the heat to be adjusted according to variations in sunshine and wind. It is desirable, also, to provide separate lines for water heating and for various cooking or process appli ances. In order that zones may operate at the optimum pressure, it is often advisable to install a separate pressure- regulating v&lve for each. See Fig. 29 of Chapter 6 for typical service installation with separate lines to hating goties and process equipment. The heat supply should be graduated according to varia tions in the outdoor temperature. Because of the continuous availability and constant pressure of district steam, the .most economical operation and satisfactory heating can only be obtained by the use of automatic temperature con trol which, except in unusual cases, is well justified. The application of control equipment in various types of build ings is fully discussed in the book, Principles of Economical Heating.1* Various types of control equipment are d'**1"""**! in Chapter 13 of the 1961 Guide And Data Book. Rapid draining and venting, of the heating system should be obtained by means of suitable traps and air vents in order to obtain rapid circulation arid quick heating. This is particularly important with intermittent-type temperaturecontrol equipment. The selection of traps is dWncspH in Chapter 6. Suggested trap capacities are given in Table 4 of this chapter. To obtain efficient and economical opera tion of any system it is imperative that all traps be properly maintained. In a system supplied with district steam any Table A .... Suggested Capacity of Traps Ijrp* at Control Trap Capacity, lb/ (Hr) (Sq Ft of Pip* and Radiation*) ' Continuous or modulating operation, in termittent with on periods over 3 hr in duration Intermittent operation with on periods of H to 3 hr in duration Intermittent operation with on periods of 14 hr or less a H * 8qou* Feet EDR. Except lor drip tnpe on niin which should bn 1 lb pernq ft EDR. pistfict Heating 117 wfcsge through traps may prevent air removal from the --stem and otherwise impair its operation. Furthermore, etewm must be condensed and its condensate cooled before being discharged to sewer. This represents a direct traste of steam. Provision should be made for conveniently shutting off (he steam supply at night and at other times when heat is not needed. A considerable amount of heat can be saved by shutting off steam at night and other times when optimum fining temperatures are not required.'* Equipment is available which will automatically shut heat off at night for varying lengths of time, depending upon outdoor tem perature.** Residual heat in the condensate should be salvaged. This heat may be salvaged by means of an air-cooling coil, or as is more frequently done, by a water-heating economizer, shown in Fig. 2, which preheats the hot water supply to the buflding" The condensate from the heating system, after leaving the traps, passes through the economizer. The water supply to the heater passes through the economizer, absorbing heat from the condensate. If the hot-water system in the build ing is of -the recirculating type, the recirculating line should be connected between the economizer and the water heater proper,' not at the economizer inlet, because the recirculated hot water is itself at a high temperature. Since the heating-system load and the hot-water demand are not coincident a greater amount of.heat can be ex tracted from the condensate if storage capacity is provided for the preheated water. Frequently, therefore, the econo mizer coils are submerged in a storage tank. Where con densate is pumped, the pump should discharge into a re ceiving tank equipped with a thermostatic air vent and the condensate should be permitted to flow by gravity through the eeonomizer and meter. METERING The Condensate Meter was developed for the district heat ing industry and is an approved method of measuring condemate where all of it can be brought to a common point for metering purposes. Its simplicity of design, ease in test- 1. Main Return Line from gravity heating system with all re turns properly trapped or pump discharge from vacuum system. With vacuum system a receiving tank with thermo static vent should be provided at Point A. 2. Steam Supply to Water Heater 3. Hot Water Supply to Building 4- Recirculating line 5. City Water Line Pressure-Regulator Temperature Control Assembly With Bypass * thermostat Bulb and Tubing Pig. 2 .... Method of Installing a Water Heater and Economizer in a Gravity Heating System fig. 3 .... Condensate Meter Installation Details ing, accuracy at all loads, low cost, and adaptability to either high- or low-pressure-distribution have made it standard equipment with most beating companies. Condensate meters must not be operated under pressure; they are made for either gravity or .vacuum installations. Typical meter installations are shown in Fig. 3. In dia gram A a continuous-flow type trap is shown installed ahead of the meter, while in diagram B an intermittent type trap is used. In the latter case, a receiving tank must be placed between the trap and meter to prevent intermittent over loading of the meter. When measuring the discharge from a vacuum pump, a vented receiver should always be in stalled ahead of the meter. Installations of meters in a vacuum return line are shown in diagrams C and D. In diagram C a master, continuous-^ flow trap is installed immediately ahead of the meter to prevent steam from entering it in case of leaking radiator or fixture traps. Where individual traps are reliable, con nections may be made as shown in diagram D- Flow meters are generally used for measuring sendout from plants, high-pressure requirements in buildings, and in in stallations where all of the condensate cannot be returned to a central point. Further information on flow meters is available from publications of the Fluid Meter committee of the American Society of Mechanical Engineers and from the District Heeding Handbook," and are described in Chap ter 7 of the 1961 Guide And Data Book. HOT WATER DISTRIBUTION District heating in the United States is confined almost entirely to the use of steam as the heating medium. Hot water has been used and is being used today, where eco nomic conditions are favorable and good engineering prac tice dictates. The use of low-pressure hot water distribution below 200 F has been practically discontinued for district heating in the