Document ByaZ0OQv7v3w2gbjER0o1bDZm
570
CHAPTER 21 .
: 1958.Guide
ferent.,; Eor example; a 10 deg temperature drop may be used ,in the main with a-20 deg drop through the radiation.
_ Example S: A one-pipe system'is to be designed for the residence discussed in Example I. :Fig.\ 10 shows the piping arrangement for the one-pipe system. The size of the .convectors is determined on the basis of a 210, F design supply, water temperature and a 20 deg design .temperature drop as in Example 1.
Solution: For initial selection of pump use a 1-in. .pump having a capacity of 5
gpm at 4.7 ft head. The measured pipe length is 140 ft which establishes an equiva
lent length of 140 x.1.5. = 210 ft.-. The preliminary design friction loss is then found
in Table 1, as,in Example 1, to be 2\i ft/per 100 ft or. 270 mi/ft., At this average
design friction loss, see Table 1, a 1-in. main will be used for the required flow of 5
gpm.
...............................
From manufacturers' data at 5 gpm flow, the pressure drop from a 1-in. fitting is established at 3000 mi or 0.25 ft. If any heating units are located below the main
ao MBH
2.5 MBH
6.0 MBH
the gravity head due to temperature difference should be subtracted from available fitting pressure drop. In this example, the riser and convector friction pressure drop should not exceed 3000 mi or 0.25 ft.
The friction loss through the I-in. risers to the 9.8 Mbh convector was calculated
to be 0.28 ft.or 3450 mi in Example 1. This loss plus the 0.1 ft (1200 mi) loss in the
convector, equals 6.38 ft (4650 mi) which exceeds the capacity of the fitting. If %-in-
risers are used, however, the riser pressure drop is considerably reduced. For 9.8
Mbh flow the pipe friction drop is 0.34 ft for 100 ft (40 mi per ft). The equivalent
length changes from 22 to 26 ft. The riser pressure drop is then 26 X 0.34 or 0.09 ft
(26 X 40 or 1040 mi). The head loss through the convector circuit is then 0.09 +.0-1
or 0.19 ft (2240 mi).. Since this is below the available fitting pressure drop, the riser
size is satisfactory.
,,
Other upfeed risers are similarly sized.
The downfeed riser is sized as follows:
'
. i. .The,design,conditions are 200 F water in the supply main and a 70 F room tempera ture. The centerline of the convectors is 5) ft below the main. The thermal head initially caused by 200 F water in one riser and 70 F water in the other opposes circu lation. From Chart Fig: 1 this negative gravity head is shown to be 420 mi per foot420 mi-X' 5.5 ft -- 2300 mi total negative gravity head. Subtracting this from the 3000 mi fitting pressure drop leaves 700 mi available to start circulation. The com-
Hot Water Heating Systems
571
bined convector and riser pressure drop equals 1380 mi even when a l-in..riser isnsed. Since the convector and riser pressure drops are greater than the available fitting head - a change must be made. The total fitting pressure drop could be increased by adding a supply one-pipe fitting, or by increasing fitting pressure drop through use of a larger pump. In this case, the riser.is sized on the basis of an added fitting. In accordance with the sizing procedure followed in this example, a %-in. riser is ade
quate.
-
The pipe sizes selected should be recalculated at the design flow rates either in
milinches as shown in the upper part of the following table or in feet per hundred
feet as shown in the lower part of the table.
Section
Pipe Size In.
Load Mbh
Loss PBB
Foot op Pipe Mi
Lineab Pipe
Length Ft
Elbow Equiv. Length
Ft
Total Equiv. Length
Ft
Total Friction
"Loss Mi
Main . .. i
50
240 . 140
87*
227 54,500 :
8 one-pipe fittings at 3000 mi** ................................... ..............: 24,000
Total.......................................... >................................................
78,500
= 6.55 ft
Section
Pipe Size In.
Load Mbh
Loss per 100 Ft op Pipe Ft
Linear Pipe -
Length Ft
' Elbow 'Equtv. - Length
Ft
Total Equiv. Length
Ft
Main . .. i
50 2.0 140 87* 227
8 one-pipe fittings at 0.25 ft head**.......................... .................
Total -Friction Loss Ft
4.54: 2.0
Total ............................................... ............ .........................
6.54,
* The elbow equivalent length is based on: 8 elbows, 2 tees, 2 gate valves, 1 flow check valve and 1 boiler. ** The actual value for resistance of the one-pipe fittings should be obtained from the fitting manufac turers. They are frequently lower than the value assumed in this example.
The pump capacity required is 5.0 gpm at 6.54 ft head. The 1J^ in.pump shown in Fig. 9 would meet the requirements of the system based on the assumptions stated for the problem.
Series-Loop System--Description and Design
This system, illustrated in Fig. 11, consists of one or more loops or cir cuits. In each circuit, as the same water is circulated through the heat ing units in succession, the size of pipe should not vary materially in any portion of a circuit. The system circuit length thus becomes very impor tant because it influences directly the water flow rate, pressure drop, and temperature drop. Since the water temperature in each successive heating umt decreases progressively, some designers consider it necessary to in crease progressively the size of heating units sufficiently to compensate for the drop in temperature. If a small design temperature drop, such as 20 deg or less is used, it may not be necessary to increase the heating units toward the end of the circuit.
Various considerations affecting the design of a series-loop system are given in the following paragraphs:
, , ' ma>' be possible to eliminate all or large sections of the distribution main and nereby reduce cost. In large buildings it may be necessary to use a partial two-pipe
the budd'm^'nii*,'0n
the series-loop system for certain sections or divisions of
circi i^^-Pf^ticability of the system will depend upon the quantity of water to be nine * i " through the heating units and the friction loss. Baseboard or finned-type nine ,, ements for series-loop systems are usually manufactured from standard steel p or copper tubing. The friction loss can be determined from Figs. 3 and 4.
DeratiV a series-loop system Berves more than a single space, and if the design tem-
be dele6 t -roh/or tne system is in excess of 20 deg, the size of the heating unit should heatinrmif on basis of the temperature of the water entering the particular
g unit and the temperature drop across the unit. The temperature drop