Document By18ZYVJ1dmzkM6BjYrG32MNm

THE NEED FOR CONTINUED USE OF POLYCHLORINATED BIPHENYLS AS ELECTRICAL INSULATING LIQUIDS . January $, 1972 by Electrical and Nuclear Sub-Council National Industrial Pollution Control Council US. Department of Commerce Washington, D.C. 20230 V MONS 100167 THE NEED FOR CONTINUED USE OF POLYCHLORINATED BIPHENYLS .AS ELECTRICAL INSULATING LIQUIDS Introduction * In view of the questions which have been raised about the environmental impact of PCB's, it seems appropriate to examine the reasons why these materials arc employed by the electrical industry, and the public benefits associated with such use. * What are Polychlorinated Biphenyls (PCB's)? .* Polychlorinated biphenyls are derivatives of the hydrocarbon, biphenyl, which has`the chemical formula C^ Hjq consisting of mixtures of variously chlorinated isomers as seen in Table 1. They are usually identified by the weight percent of chlorine in the total mixtures, e.g. Aroclor* 1254 con tains 54% chlorine. Aroclors are characterized by stability - high flash points and even higher combustion temperatures essential to safe operation. How are PCB's used by electrical industry? The principle use of PCB fluid in the electrical industry is in trans formers and capacitors (both large and small) as an insulator and coolant. * %' Transformers are devices for converting electrical . povjer from one voltage and current level to another, and the conducting parts of these devices must be separated from each other by a suitable insulating -medium. . * ' Capacitors are devices for storing electrical energy through the physical separation of charged metal _ surfaces by an insulating medium. ' ' . # Monsanto Registered Trademark (Monsanto is the solo U#S. producer of PCB's.) Vt t -1- , MONS 100168 ' T&blc 1 . . '` Ccy?Qgibion of Different L-onid Chlorinated Blpncnyls \ Components _ riven ns i - Moasant0 Aroclcrs 1 m 1232 KCS-1C-3 1242 i-i'JS lOlo US 1254 IcOO Chlorine Biphenyl * :.:or.O`Chlorohipbenyl Si-chlerobipfcenyl Tri-chlorobiphenyl ' Totrn-chlcrooiphenyl ?:r,ta-chlorobiphenyl Hsxa-chloro&iohcnyl 21 '32 32 lU 55.5 22.2 26.9 ` *55' \ ?M 3.3 .06 te t2*. 48 5* .60 .02 .02 . ,n * .93 15.6 1$A 5^.5 6U.5 22.5* 15.0 v55 . 6.7* ; ,i5* # 0 > 60 ' 70 / , ^Includes bisber than penta-chlorinatcd isomers. MONS 100169 Because of the nonflammability (Table 2) of Aroclors, their vapors, and their arc-formed gaseous products, transformers filled with <PCB's are free of fire and explosion hazards and may be used in locations where failures of oil-insulated transformers would present a potential danger to life and property. In addition to improving the safety aspect of capacitors the use of `Aroclors also gives them the advantages of reliability, long life, and small size. ' * ' Table 2 * . . Underwriter Laboratory Flammability Rating . ' Fhri<l Flammability Rating Ether 100 Gasoline , . Ethyl Alcohol * 9 Kerosene (100 F. P.> ' 90-100 60-70 ' 30-40 Mineral Oil 10-20 Aroclor 1242 and MCS'10l6 2- 3** The need for PCBts in Transformers , PCB's are used in transformers wherever fire protection is particularly important -- for about 5% of all transformers, V* * .' . -3- MONS 100170 Most of these transformers are located inside public, commercial, or industrial buildings; on the roof tops of such buildings or in close proximity to such buildings, and require no special enclosures other than what are necessary to prevent accidental a hazardous mechanical or electrical contact of persons with the equipment. The amount of Arodor used in various types of transformers ranges from 40 to 500 gals. (516 to 6,450 lbs.) with an average of about 235 gals. (3,032 lbs.). During 1968, the last complete 'normal" year for the electrical industry, the total amount of PCB's used in transformers was approximately 1.3 million gallons (8.4 thousand tons). * The only present alternatives to Aroclor-insulated transformers are mineral oil-insulated transformers or dry-type transformers (either those open to the atmosphere or those that are gas-filled and sealed). A. Mineral oil-insulated transformers 1. If one disregards safety considerations, there are ' no technical* reasons why mineral oil-insulated trans formers could not be directly substituted for PCB- insulated transformers. The size of the unit would be * Unchanged; the weight and cost would be less. *' 2. But one cannot disregard safety considerations, which `. . are often embodied in legal codes, . Obviating the safety hazards involves serious economic a dnd space constraints, that would occur cither by - . * -it- HONS 100171 the use of protective vaults, or use of insulated buses (with the transformer located outdoors). Either solu tion, if the space is available, could cost $5,000 -- ' $50,000 per tran, sformer. Dry-type transformers . . * . In most locations, dry-type transformers (either those open to the atmosphere or those that are gas-filled and sealed) could not he directly substituted for PCB- insulated transformers. There ar6 several restrictions to such a direct substitution: . 1. The reliability-of dry-type transformers is less than , that of comparably rated liquid-insulated transformers, . An EEI survey of failures in network transformer banks showed a 7% per year failure rate for dry-type units compared to 0.2% for liquid-insulated units. 2. Furthermore,* liquid-insulated transformers have a much N greater overload capability. Many liquid-ihsulatcd units can sustain a 100% overload for 8 hours and a 200% overload for 2 hours. These transformers are able to maintain continuity of electrical service during periods of temporary malfunction of related equipment. 3. Some dry-type transformers are larger by 10 to 30% v .. than comparably rated*liquid-insulated units, and most are more expensive. * -5- MONS 100172 4. Dry-type transformers arc noisier by 5-10 dB than , . ' ar6 liquid-insulated transformers, 5. Open dry-type transformers, which are cheaper than sealed dry-type transformers, cannot be used in certain , corrosive or hazardous atmospheres, e, g. on.furnaces '' or on electrostatic precipitators near hot stacks. Clearly there is no substitute for PCB-filled transformers where fire protection is required, _ The need for PCB's in capacitors PCB's are used in more than 90% of the electric utility {large, power)type and. smaller industrial type capacitors made today. They are needed for safety, reliability and long life, and to achieve sizes compatible with equipment and installation requirements. The principal types of PCB-impregnated capacitors and their applications are high voltage power capacitors used primarily for ' power factor correction in the distribution of electric power; low voltage power capacitors installed in industrial plants at the load (typically large motors); ballast capacitors, to improve the efficiency of lighting systems; and 6mall industrial capacitors for power factor improve ment in such equipment as air conditioning units, pumps, fans, etc. Almost 80 million such capacitors are manufactured annually, most of t them for first-time use. -6MONS 100173 Capacitors used infighting and air conditioning applications ' contain 0.<005 to 0.09 gals, of PCB per unit. The largest power ' capacitors contain about 6.7 gals, of askarel. The most popular size contains about 3.1 gallons. The National Electrical Code requires that any installation of capacitors in which any single unit contains more than 3 gallons of combustible liquid shall be in a vault like that required for transformers. During 1968. the last complete "normal1' year for the electrical industry, the total axnount cf PCB's used in capacitors was Approximately 14.4 thousand tons. ^ . Possible alternatives to PCB-impregnated capacitors are capaci tors impregnated with mineral oil, or certain other liquids. .* Mineral Oil *1. Size The single most important property of a liquid to be . used in a capacitor is its dielectric constant (the ratio . of its ability to store electrostatic energy relative to . air). The dielectric constant of the capacitor-grade PCB (Aroclor 1242) is 5.85 while that of mineral oil is 2.25. (See Table 3) Reverting to an oil-paper * dielectric system would increase the average capacitor volume (size) by approximately 600%, the weight by 500% #, ' . ` -7- . * MQNS 100174 ' ' Alternate Insulating fluids- ' . #, ' Scse Significant Properties of Certain Candidate Insulating Fluids to Keplace Aroclor _ \ M' .toclor 1242 Aroelor-KS 101$ Arcelor K$ 1^3 Dielectric Constant, e',,. at 25 C 0 ' 5.85 ' Cleveland Oacn Cu? nubility Flash Point - WC - Firs Point Density ,0 333 1.38 Cost, {JL . lo ' 5.85 ' 191 319 ,1.35 . to 1 5.7 ; ' ISO 1.23 .13 Mineral Oil ' `2.25 . , ' r * ' .' * 150 * *. * . .9 `3 * . * * . . .* i ' MONS 100175 nd the cost by approximately 400%, At the present levels of demand for capacitor KVAR, 9, . there would be a shortage of electrical grade paper and a shortage of capacitor faetpry * * facilities further tending to increase the cost fV ' to the utility, and ultimately to the consumer,' ' . Reliability and life ' . pCB's are thermally and oxidatively more stable . than mineral oils, and discharges, which can occur in capacitors, are less likely to generate gases from * askarels than from mineral oils. The chemical stability of PCB's in the presence of capacitor tissue and plastic films and the favorable stress . distributions between solid and liquid have made it possible to design low-cost capacitors with a life expectancy of more than 10 years life in lighting applications and more than 20 years in electric % utility applications. In each application the fir6t-year failure rates are less than 0.2%. This level of life and reliability had not been achieved prior to the introduction of PCB's, . MONS 100176 >" V 3> Safety f The relative non-flammability of PCB'e significantly * reduces the fire hanard that might otherwise accom- pany those failures that result in rupture of the case. ,, B. ' Other Liquids , .. ' ' '* 1, Castor Oil. The dielectric constant of castor oil is 4.' 5 and this material is useful as an impregnant t' * . in D.C, energy storage capacitors. However. A.C. * .' capacitors filled with this liquid have relatively short . . ` lives and are not very stable under A.C, discharges and in the presence of water derivable from the cellulosic paper." . ' 2, Pibutyl scbacate. This ester is especially useful in high frequency parallel plate capacitors because of its low. flat loss characteristics over a broad frequency range. In this type of construction the liquid is the sole- dielectric material. When used in conjunction with paper, ' . . this ester is 'also unstable. ' 3. Silicone Fluids. These materials have a dielectric , ' ,constant of 2,7 and would generally be subject to the * same disadvantages as mineral oil. * ` . `10- MONS 100177 2nvthc interest of achieving a higher degree of environmental compatibility tho capacitor industry has switched during 1971 from ,# Aroclor 1242 to Aroclor MCS 1016, from which the higher-chlorinated V. . . persistent fractions have been substantially removed. Environmental Protection The advantages to the public in terms of safe, reliable, and efficient electrical equipment made possible by the use of PCB's have been documented. It is also clear that there are no present or pros pective substitutes for these materials and the functions they perform are essential. Thus the continuing need for PCB's in closed electrical * system applications is conclusive. The electrical industry well under. stands, however, that continued use of these materials requires unusual protective measures. These measures were the subject of recommenda tions made by a previous NIPCC Sub-Council report (The XJse and Dis posal of Electrical Insulating Liquids, June i971) and are judged to be well on their way toward implementation: witness the introduction of the new capacitor dielectric, the provision of facilities for the incinera tion of liquid and solid wastes, and the instructions to operating person nel and users regarding the need for care in waste disposal, an activity .now being further formalized and strengthened by ANSI's committee Cl07 The annual residual leakage to the environment from the continued use in transformers and capacitors has been estimated between one part in a thousand and one in ten thousand of the existing environmental PCB burden, . 11- MONS 100178