Document BoG9JyNZmJGejv7oZMbrR5Bj
Boilers
InTERn/mon/iL Heater Cocop/my
Utica, N. Y.
BRANCHES:
CHICAGO
NEW YORK
NASHUA, N. H.
CLEVELAND, O.
1933-35 Wentworth Ave. Broadway & 57th St. 369 Main St. 1441 Davenport Ave., N. E.
Manufacturers of Heating Apparatus
InTERn/mon/iL
No. 8-47 International Economy Steam Boiler
Economy Boilers
On the following pages we present condensed data on the
International Economy Sectional
Boilers.
Both the Regular and the Smokeless patterns have the fol lowing distinctive features in com mon : They will absolutely deliver dry steam to the system without the use of a special header. The grate bars have their connections entirely outside the boiler and shaking attachment may be placed on either side. They have a low water line. The water gauge is tapped directly into the section. Large doors give easy access for cleaning from the front.. They have a high evaporative power and they are conservatively rated from actual tests according to the A. S. H. & V. E. Code.
In the regular pattern boilers provision is made so that tongues of flame pass up; between the sections of the crown sheet and thoroughly ignite the gases in the mixing chamber, as the lower row of flues is called. This is the well known carburetor principle which has always been a feature of Economy Boilers.
The International Economy
Smokeless Boiler
is an up-draft boiler. It is built on the Kent Wing Wall principle so that the smokeless feature is entirely outside of the fire box and practically independent of the fireman. It has no special grates or arches in the fire box, holds several hours' supply of coal and requires the least possible attention. Excess air is al ways under control,--an im portant feature that pro motes fuel economy.
Cutaway View of No. 130-47 Smokeless Boiler 228
International Heater Co.
Boilers
InTERn/mon/iL He/tter Cocop/my
STANDARD SPECIFICATION FOR SMOKELESS BOILER INSTALLATION
Low pressure up-draft smokeless steam located that all heating surfaces ex
boilers, of the push nipple sectional cast
iron type, shall be furnished complete; boiler to be equipped with an all metal automatic damper regulator, water gauge,
posed to the fire and hot flue gases shall be backed up by water and not steam. The boiler shall be capable of delivering dry steam at the boiler outlet when sub
try cocks, pressure gauge, safety valve, firing and cleaning tools, etc.
jected to overloads of 50 to 100 per cent, for short periods when forced to the limit in cold spells. Boiler construction
In burning bituminous coal of high features such as accessibility for keeping
volatile content of over 30 per cent, the the heating surfaces clean, the absence qf
smoke density produced by the boilers soot pockets, the direction of the flue
shall come within the regular smoke travel and its effect on the. positive
ordinance requirements of not to exceed water circulation within the boiler sec
10 per cent, in density per hour accord tions, dry steam conditions, quality of
ing to Ringlemann's standard. To meet heating surface, etc., shall be considered
this smoke requirement special exacting before any boiler is accepted as meeting
methods of firing and special expert skill the requirements for this particular in
shall not be required of the fireman in stallation.
charge, and the excess air required over
the fire shall be under convenient con
An ashpit twelve inches deep of good
trol of the fireman.
concrete or hard brick construction shall
Boiler, when operating under standard
code conditions, shall be capable of pro ducing at least four thousand pounds of dry steam per hour, an equivalent of sixteen thousand square feet of direct steam radiation. The rated capacities of the boiler shall have been determined according to the Testing Code of the A. S. H. & V. E. and the soft coal rat ings shall not exceed that -of the hard coal ratings for the same size boiler of similar overall dimensions.
be placed under the entire grate of the . boiler. In-mounting the boiler, as each section is pulled up" into position it shall, be thoroughly cemented with boiler cement (not regular asbestos covering) or joints packed with asbestos rope to pre vent short circuiting of the hot gases within the boiler. After the boiler is mounted and the push nipples made water tight under 15 pounds water pres sure, the space between each section around the outer edge shall be thorough ly cemented with boiler cement (not as
To minimize the frequency of firing fuel, fire box shall contain ample fuel to develop the rated capacity of the boiler for at least two and one-half to three hours, and the depth of the fuel on the grates shall in no place be less than sixteen inches, with the top of the fuel bed at. least four to six inches below the lower projection of the crown sheet.
A fuel capacity of one ton is ample in . the largest size boilers and the length of the fire box shall not exceed 80 inches. The fuel capacity and evaporative power of each boiler at the rated, capacity given shall be stated in the bid.
bestos covering), also along base of sec tions and around smoke box, to prevent air leakage into the fire or flue travel, and the nuts on the tie rods shall be . loosened up to allow for expansion of the sections. No rigid flow or return headers shall be allowed. During tem porary heat none of the condensed water shall be permitted to return to the boiler until all oil, grease, sand, etc., shall be eliminated from the system. The boiler,
piping and radiation shall be free from oil, grease and foreign matter before the plant is. accepted. A durable damper, with quadrant adjustment shall be placed
in the smoke pipe from boiler and an
The height of the water line shall not other in the main breeching near the
exceed sixty-four inches and shall be so I chimney.
229