Document BjMqR5LKgzvOOG3BNKjvxdn8
524
CHAPTER 48
1962 Guide And Data Boole
Due to the evaporative cooling effect from the moist surface of
the washed lemons plus the moisture loss from the fruit itself (81,200 Btuh in the previous Latent Heat Load calculations), the air range may be considered as only 5 F deg and the supply
air temperature raised to 53 F:
330,635 - 81,200 249,435
xemo ranee =------------------------- ----------------= 5 F dec
(60) (0.24) (3440) . 49,600
"
58 F room temp -- 5 F deg range = 53 F supply or dew-point temp
The total moisture gain in the storage room from the latent IH of 95,660 Btu per hr will be:
(95,660) (7000 gr per lb)
(60 min)(1060 Btu per lb)(3440 lb per min)
= 3.06 gr per lb of supply air
Moisture content at 53 F supply air dew point -- 60 gr per lb.
Moisture gain in room
= 3 gr per lb
Moisture content of storage room air
= 63 gr per lb
By reference to a psychrometric chart, it is found that 63 grains per lb corresponds to 54.5 F dew-point temperature. The
final storage room condition is 58 F dry-bulb and 54.5 F dew point, corresponding to 88 percent rb.
This process may oe readily visualized on a psychrometric chart
as follows: From 53 F dew point on the saturation line proceed along the dew point line 7 deg to intercept the 60 F dry-bulb
temperature. Follow the wet-bulb line from thin point to intersect the room condition dry-bulb temperature of 58 F at the
point 54.5 F dew point and 88 percent relative humidity.
Refrigeration Loan
Total beat at 65 F outdoor wet-bulb Total beat at 53 F apparatus wet-bulb
For outdoor air, apparatus must absorb Total heat at 56 F room wet-bulb Total heat at 53 F apparatus wet-bulb
For return air, apparatus must absorb
Outdoor air load = (380 Ib per min)(8.0) Return air load = (3,060 lb per min}(1.9) Add for washer spray pump = (10 hp)(42.4)
Subtotal Add 5% for apparatus and piping losses
Total Refrigeration Loan
Btuh
-30.0 = 22.0
8.0 = 23.9 = 22.0
1.9
Btu per min -3040 = 5814 - 424
-9278 - 464
= 9742 = 48.7 tons
48.7 tons
Refrigeration per carload
0.7 tons
70 cars
17,329 sq ft
Floor area per ton >
356 sq ft
48.7 tons
_.
45,600 cfm
Outdoor air - ------------- = 035 cfm per ton
48.7 tons
Refrigeration Equipment
The required cooling effect may be obtained by using direct expansion coils in the air washer, or by circulating chilled water from a central cooling system. The refrigerant temperature will generally be between 33 and 40 F. The chilled water require ments and a central system will be about 200 gpm for a 6 F deg range of water temperature, calculated as follows:
(48.7 tons) (200 Btu) <6 F deg range) (8 H Ib per gal)
' 81)111
The difference between the air and water leaving the washer
varies with the washer design, but is usually between 1 and 2 F deg.
53 F washer dew point -- 2 F deg -- 51 F water leaving 51 F water - 6F range = 45 F entering water
Select the refrigerant temperature about 10 F deg below the water temperature:
45 F water -- 10 F deg = 35 F refrigerant temperature
Air Supply Nozzles (96 nozzles used; required air travel -- 35
_____ _________ .. 46,500 cfm_
_
For an air travel of 35 ft. use about 0.10 in. nozzle pressure or
1250 fpm nozzle outlet velocity (see Table 6).
'
. . 477 cfm
aTM, per no..le -
- 0.406 sq ft
Therefore, make nozzle outlet 8K in. diameter = 0.418 sq ft
area. Make nozzle about 24 in. long. For a nozzle converging at
about a 14 degree included angle, the inlet diameter will be I4$4
in. diameter (Fig. 11).
*
Example 4: Illustrate calculations for the storage basement of Example t for a combination system using low air quantities and auxiliary humidification.
A combination system uses about half as much air as a conven tional system and therefore must operate with a lower apparatus dew point or supply air temperature. This tends to give too low a humidity in the room, so auxiliary humidifying sprays are pro
vided. The auxiliary sprays in the room will produce evaporative cooling which lowers the sensible load while increasing the relative humidity.
Solution:
Air Temperatures
For a 58 F dry-bulb and 88% rh storage condition, the appa ratus dew point may be set at 50 F. The supply air quantity may be calculated as though the air range is 14 F instead of 58 F -- 50 F or 8 F as indicated.
This may be explained by referring to a psychrometric chart. From 50 F dew point on the saturation lina proceed 14 dry-bulb degrees to intersect the 64 F dry-bulb temperature and 56 F wetbulb line. Follow the 56 F wet-bulb tin* to intersect the final room condition of 58 F dry-bulb where the dew point is 54.5 F and the relative humidity 88 percent.
Air Quantities
For a combination system using about half the air quantity of
the conventional system of Example 8, assume a 10 hp fan
motor.
Total room sensible load
= 279,735 Btu per hr
(from Example f)
Add for 10 hp fan motor: (10) (2,545) -- 25,450 Btu per hr
Gross sensible heat load
305,185 Btu per hr
Supply air
305,185 (60 min)(14 F range)(0.24 sp ht) 1510 lb per min (1510)(13.23) = 20,000 cfm
Outdoor air * 380 lb per min -- 5,040 cfm (from Example 8) Return air -> 1510 -- 380 = 1,130 lb per min
- 20,000 - 5,040 = 14,960 cfm
20,000
Supply air per car =
286 cfm
70
Apparatus Selection
Supply fan: Required for 20,000 cfm. Assuming the resistance
of the apparatus and duct system is 1% in. water, the fan motor needed will be 10 hp.
Air washer; Required for 20,000 cfm at 500 fpm face velocity:
Face area
20,000 cfm 500 fpm 20,000 500
40 sq ft face area
Make washer 7 ft wide X 6 ft high above the pan. Assinmal an 18 in. deep pan, the air washer will be 7H ft high X 7 It wide X 8 ft long. With two spray banka, a circulating pump
Citrus Fruit Storage
525
jbout 200 gpm capacity at 65 ft head wiQ be required. A 5 hp pump motor is necessary.
Refrigeration Load
Total heat at 65 F outdoor wet-bulb temp =30.0 Btu per lb Total heat at 50 F apparatus wet-bulb temp =20.3 Btu per lb
For outdoor air, apparatus must absorb
9.7 Btu per lb
Total beat at 56 F room wet-bulb temp.
=23.9 Btu per lb
Total beat at 50 F apparatus wet-bulb temp =20.3 Btu per lb
For return air, apparatus must absorb
3.6 Btu per lb Btu per min
Outdoor air load = (380 lb per min)(9.7) =3,686 Return air load = (1,130 lb per min)(3.6) =4,068 Add for washer spray pump = (5 bp)(42.4) = 212
Subtotal
=7,966
'Add 5 percent for apparatus and piping losses = 398
Total Refrigeration Load
=8,364 =41.8 tons
., Refrigeration per carload
41.8 tons = -------------- = 0.6 tons
70 cars
. 17,328 sq ft Floor area per ton refrigeration = ----------- = 415 sq ft
41.8 tons
,,,
20,000 cfm __,,
.. .
Supply air --------- ---------= 480 cfm per ton refrigeration
41.8 tons
Refrigeration Equipment
The required cooling effect may be obtained by using direct ex pansion coils in the air washer, or by circulating chuled water from a central cooling system. In either case, the refrigerant temperature will generally be between 33 and 40 F. The chilled water requirements from a central system will be about 170 gpm for a 6 F deg range of water temperature, calculated as follows:
(41.8 tons) (200 Btu) -------------------------------------- = 167.2 ram (6 F range)(8H lb per gal)
Assuming a 2 degree temperature difference between the air and water leaving the air washer:
50 F washer dew point -- 2 F deg -- 48 F water leaving 4S F water -- 6 F deg range = 42 F entering water
Select the refrigerant temperature about 9 F deg below the water
temperature:
42 F water -- 9 F temperature difference = 33 F refrigerant temperature
Air.Supply Nozzles (48 nozzles used; required air travel = 35 ft)
.. .
. 20,000 cfm
Air supply per nozzle = ------ ;-- = 417 cfm
48 nozzles
Design nozzles for 0.10 in. nozzle pressure (1250 fpm outlet velocity) for 35 ft throw (see Table 6).
Nozzie area ----------0.94
cfm = (0.94) (velocity) (area)l
, 417 cfm Afea "(0.94) (1250)
0.356 sq ft
Therefore make nozzle outlet 8 in. diameter = 0.349 aq ft area. Make nozzle about 20 in. long. For a nozzle converging at about
a 14 degree included angle, the inlet diameter will be 12W in. diameter.
Auxiliary Humidifying Nozzles
Moisture content at 54.5 F room dew point = 63 gr per Ib Moisture content at 50 F apparatus dew point = 54 gr per lb
Moisture pick-up required in room
= 9 gr per lb
Tots] moisture required = ^
^ " 1-94 lb per min
= 118.4 lb per hr
Moisture pick-up from room latent load = --
y*
1,060
= 90.2 lb per hr
Therefore, moisture required from auxiliary sprays = 116.4 -90.2 = 28.2 ib per hr
Auxiliary nozzles should be provided for at about 75 percent of the total moisture requirements, as a factor of safety:
(116.4 Ib per hr) (0.75) = 87.4 Ib per hr Provide one spray nozzle for each two air nozzles:
48/2 = 24 spray nozzles
87.4 Ib per hr 3.64 lb moisture per nr per nozzle
The sizes of nozzles can be selected from manufacturers' catalogs.
TRANSPORTATION
Since the bulk of the California citrus crop is sold in distant markets, the transportation problem and factors affecting quality are of great importance to the citrus growers. All other factors being equal, the maintenance of grade and quality is dependent upon time in transit, the refrigerator car and its cooling equipment and the class of service requested of the carriers.
Least loss in quality occurs when fruit is first precooled to 39 to 40 F and then loaded into pro-iced, fan equipped cars. Further information on the railway transport of refrigerated and frozen foods can be found in Chapter 56.
BIBLIOGRAPHY
H. B. Addington: Air conditioning problems in the citrus fruit industry {Heating and Ventilating, December 1937, p. 53).
Agricultural Code of California: (Bureau of Fruit and Vegetable Standardization, California Printing Office, 1949).
J. B. Biale and A. D. Shepherd: Identification of acetaldehyde among the volatile products of citrus fruits (Proceedings, Ameri can Society for Horticultural Science, VoL 37, 1939, p. 543).
J. B. Biale and A. D. Shepherd: Respiration of citrus fruits in relation to metabolism of fungi. I effect of emanations of penirillinfn digitatum, sacc. on lemons (American Journal of Botany, VoL 28, No. 4, 1941, p. 263).
H. Campbell: Handling raw materials for food processing(Refrigerating Engineering, November 1946, p. 428).
H. S. Fawcett: Citrus Diseases tend Their Control (McGrawHill Book Co., New York, 1936).
W. Grierson and W. F. Newhall: Degreening conditions for Florida citrus (Proceedings, Florida State Horticultural Society; VoL 66, 1953, p. 42).
W. Grierson and W. F. Newhall: Tolerance to ethylene of various types of citrus fruit (Proceedings, American Society for Horticultural Science, VoL 65, 1955, p. 244).
W. Grierson and R. Patrick: The sloughing disease of grape fruit (Proceedings, Florida State Horticultural Society, VoL 69, 1956, p. 140).
M. H. Haller, D. H. Rose, J. M. Lutz, and P. L. Harding: Respiration of citrus fruits after harvest (Agricultural Research, VoL 71, p. 327).
P. L. Harding, M. J. Soule, and M. B. Sunday: Storage Studies on Marsh Grapefruit--1955-56 Season. I Effect of Nitrogen and Potash Fertilization on Keeping Quality. II Effect of Different Temperature Combinations on Keeping Quality (USDA, AMS202, July 1957).
P. L. Harding and J. S. Wiant: Terminal Market Storage of Florida Oranges (USDA, HT&S Office Report No. 218, 1949).
E. M. Harvey, et al: Terminal Market Storage Teste on Cali fornia Lemons (USDA, HT6S Office Report No. 238,1951).
E. F. Hopkins and K. W. Loucks: The Dowicide A-Hexamine treatment of citrus fruits for the control of mold and stem-end rot decay (Citrus Magazine, 1951, p. 22).
E. F. Hopkins and K. W. Loucks: Value of Dowicide AHex&mine treatment in the cold storage of oranges (Citrus Magazine, June 1956i p. 16).
E. F. Hopkins ana A. A. McCormack: Effects of ammonia treatments in fibreboard cartons on the stem-end rot and mold decay in Florida oranges (Citrus Magazine, November 1957).
C. W. Mann and w. C. Cooper: Refrigeration of Oranges in
%