effective temperatures giving maximum comfort for persons working have been determined by the A.S.H.V.E. Research Laboratory24 for a rate of work which is considered hard labor. For this degree of work, 50 per cent were fairly comfortable for temperatures ranging from 46 to 64 deg ET, while the greatest percentage found maximum comfort at 53 deg ET. In hot industries, 80 deg ET is considered the upper limit compatible with efficiency, and, whenever possible, this should be reduced to 70 deg ET or less.
APPLICATION OF COMFORT CHART
The average winter comfort line (66 deg ET) applies to average American men and women living inside the broad geographic belt across the United States in which central heating of the convection type is generally used during four to eight months of the year. It does not apply to rooms heated by radiant energy, and has not been advocated officially for use in foreign countries where the climate, heating methods, and general living conditions are materially different from those in the United States, although several foreign workers have attempted to show that it cannot be so applied. Even in the warm south and southwestern climates, and in the very cold north-central climate of the United States, the comfort chart would probably have to be modified according to climate, living and working conditions, and the degree of acquired adaptation.
In densely occupied spaces, such as classrooms, theaters and audi toriums, somewhat lower temperatures are necessary than those indicated by the comfort line on account of counter radiation between the bodies of occupants in close proximity. In rooms in which the average wall surface temperature is considerably below the' air temperature, higher air tem peratures are necessary. The reverse holds true in radiant or panel heat ing methods. (See Chapter 37).
The sensation of comfort, insofar as the physical environment is con cerned, is not absolute but varies considerably among certain individuals. Therefore, in applying the air conditions indicated by the comfort line, it should not be expected that all the occupants of a room will feel per fectly comfortable. When the winter comfort line is applied in accordance with the foregoing recommendations, the majority of. the occupants will be perfectly comfortable, but there will always be a few who would feel a bit too cool and a few a bit too warm.. These individual differences among the minority may be counteracted by suitable clothing.
Air conditions lying outside the average comfort zone but within the extreme comfort zone may be comfortable to certain persons. In other words, it is possible for half of the occupants of a room to be comfortable in air conditions outside the average comfort zone, but in the majority of cases, if not in all, these conditions will be well within the extreme comfort zone as determined experimentally.
Strictly speaking, the only authoritative comfort zone on which accur ate data are available, is that for 15 to 25 fpm air movement or turbulance (often referred to as still air). In the past, the winter comfort
.. 'VVS.H.V.E. research paper entitled. Heat and Moisture Losses from Men at Work and Application to Air Conditioning Problems, by K. C. Houghten, W. W. Teague, W. E. Miller and W. P. Yant (A.S.H.V.E. J. RANSACTIONS, vOi.'37, 1931).
Chapter 2--Ventilation and Air Conditioning Standards
zone has often been superimposed on the thermometric chart or on effec tive temperature charts for various air velocities, on the assumption that air conditions of equal warmth are approximately equally comfortable. This may hold in hot industries where the workers are adapted to high temperatures and strong air currents, but it does not apply to sedentary conditions. To ascertain approximately whether a given industrial con dition is reasonably comfortable, it would be necessary first to compute the effective temperature from the thermometric chart (Fig. 1) and then to refer this effective temperature to the comfort chart (Fig. 2).
The summer comfort line (71 deg ET) is applicable to the same geo graphic area as the winter comfort line. It is further restricted to cases in which the human body has reached thermal equilibrium with its environ ment. As a general rule this takes place after 1)4 to 3 hours exposure. When a person from outdoors enters a room cooled to 71 deg ET on a hot day (95 F or over) an intense chill is likely to be experienced which is
Table 2. Desirable Indoor Air Conditions in Summer Corresponding to Outdoor Temperatures
Applicable to Exposures Less Than S Hours
Outdoor Temp (Deo Fahr)
Dry-Bulb
95 90 85 80 75 70
Indoor Aih Conditions with Dew-Point Constant at 57 F
Dbt-Bulb
Wet-Bulb
Effective Temp
80.0 78.0 76.5 75.0 73.5 72.0
65.0 64.5 64.0 63.5 63.0 62.5
73 72 71 70 69 68
unpleasant. However, after remaining in the room for about 2 hours, this fundamental optimum condition will prove satisfactory to the average person. The summer comfort zone, as well as the comfort line, makes proper allowance for these adaptive changes in the body, and thus applies to homes, offices, schools and other similar places where persons of sedentary occupations spend from 3 to 8 or more hours daily.
In artificially cooled theaters, department stores, restaurants, and other public buildings where the period of occupancy is short, the contrast between outdoor and. indoor air conditions becomes the deciding factor in regard to the temperature and humidity to be maintained. The object of cooling such places in the summer is not to reduce the temperature to the optimum degree, but to maintain therein a temperature which is tem porarily comfortable to the patrons who thus avoid sensations of chill and intense heat on entering and leaving the building. The relative humidity should be low enough (about 50 per cent or less) to give a sense of comfort without chill and to induce a rate of evaporation which will keep clothing and skin dry. For exposures less than 3 hours, desirable indoor conditions in summer corresponding to various outdoor temperatures are given in
Table 2.