460 Chapter 24. 1945 Guide in many theaters, restaurants, funeral' h"omes7 churches'and othertplaces where short hours of operation and- high peaks of cooling demand make this type of system desirable. A comparatively small quantity of ice,in the water cooling tank of such a system can release refrigeration at a relatively rapid rate. For instance, neighborhood theaters having a peak demand of 1,200,000 Btu per hour (100 tons refrigeration) have found 8 ton capacity ice bunkers satisfactory. In operation, the water in the air conditioning system is circulated Over ice placed in an insulated box and is cooled to the 38 or 40 F range or higher if desired. This cold waiter is pumped from the ice bunker to air cooling coils or spray type air washers. The blowers, coils, air washer or air handling sections are the same as those parts in any system employing cold water as a refrigerant. The ice water cooler or ice bunker is usually built at the installation in a location where it can easily be iced. It can be constructed of any desired material such as concrete, steel, or wood with an adequate amount of insulation to save the ice from one period of use to the next. The basic requirement is that the tank be durable and water tight. A typical bunker with connections to a coil type air conditioning system is shown in Fig. 9. About 60 cu ft of gross bunker volume are allowed per ton of ice capacity. The shape of the bunker usually conforms to the available space. The one illustrated has overhead sprays, but if head-room is lacking the ice is placed on the floor of the bunker with the water returned around the lower part of the blocks from a perforated distribution pipe run along one side of the bunker. To secure good circulation the supply water is extracted from a similar perforated pipe on the opposite side of the bunker. The temperature of- the water is controlled at a predetermined point by a thermostat in the supply line. If the temperature drops too low, a part of the return water is by-passed directly to the sump and is not cooled over the ice. In the larger systems it is customary to install an overflow control which, as the ice melts, discards the excess water through an economizer coil. The surface of the economizer is large in relation to the flow so that the water is warmed' to 60 F or more as it is discharged from the system. Refrigeration 461 STORAGE SYSTEMS In an attempt to lower initial equipment cost and operating expense, or increase the refrigeration capacity of an existing air conditioning system, storage refrigeration has been utilized in a few applications. Sop0*of the methods which have been adopted'include the storage of refrigeration in the form of chilled water, chilled brine, ice on evaporator coils2 and the'accumulation of thin sheets of ice on copper plates in a steel tank3. If the peak load factor is low as compared with a long period of operation, such as in a restaurant, or if the hours of operation are short but the usage factor high as in a church, then it is possible to con sider storage refrigeration. This method of accumulating refrigeration , frequently makes it possible to use low cost off-peak electric power. Power costs may also be reduced by installing a smaller refrigeration Table 10. Basis of Equipment Selection Capacity Tons 0 to 5 5 to 25 25 to 50 50 to 400 400 and Over Majority Used Some Used Few Used Unit systems in con Unit central systems Built up central sys ditioned space. using duct distribu tems. tion. Built up central sys tems using reciprocat ing compressors.. Unit central systems using duct distribu tion. Unit systems in con ditioned space. Built up systems using absorption and adsorption systems. Built up central sys Built up central sys Central systems tems usingreciprocat- tems using centri using adsorption ing compressors. fugal compressors. systems. Built up central sys tems usingreciprocat ing compressors. Built up central sys tems using steam jet and centrifugal com pressors. Built up central sys Built up central sys tems using centri tems using steam jet. fugal compressors. plant, augmented by a storage system, and by operating it for longer periods. EQUIPMENT SELECTION The selection of- proper refrigeration equipment for any air conditioning job is of utmost importance for satisfactory results. The most important -factors in the selection of the equipment are: 1. Loads (as determined by the conditions of the space to be cooled). 2. Economics (both initial and operating costs). 3. Codes (local safety codes must be adhered to and influence the type of system to be used). A broad division of equipment to be used for a particular installation or The Application of Storage Refrigeration to Air Conditioning,' by C. F. Boester (A.S.H.V.E. Trans actions, Vol. 45. 1939. p. 675). ,a ,L CS,d Accumulators in the Air Conditioning Field, by R. W. Evans and C. J. Otterhohn (A.S.H.V.E. Transactions, Vol. 48, 1942. p, 123). .