Document BRVzQpK8woRdekQ7EJgqDoGE
820
CHAPTER 75
1962 Guide And Data BooltW
Table 15 .... General Purpose Hof Wafer (140 F) Requirement for Various Kitchen Uses**b
fqt'pmrf
Gallon! per Hour
Pre-eerapper (open type)..............................
30 60
180
45
Lavatories (each).. .....................................
30 5
Value* extracted (ram Befete&ce *. Supply water premie at equipment ia cer.incd to be 30 po*. fc Dtahwaaher operation at 100 percent of mechanical capacity.
tive peak demand must be determined. This peak demand period will usually coincide with the dishwashing period dur ing and after the main meal and may last for 3 hr or more. Any hour in which the dishwasher is used at 70 percent of mechanical capacity, or more, should be considered as a peak hour. If the peak demand period lasts 4 hr or more, the value of a storage tank is small, unless extremely large sizes are used. In such cases instantaneous heaters should be used.
Automatic storage water heaters with storage capacities up to 100 gal should be sized on the hasis of the nummnm hourly demand, with the storage capacity being used as an extra capacity factor in the beater.
The following method of making allowances for the water in storage, should be used only when siring heaters and systems with more than 100 gal storage capacities.
Usable hot water from storage is calculated from the fol lowing equation:
where
Q, -- quantity of usable hot water from storage, gallons per hour.
8 -- storage capacity of tank, gallons. d ~ duration of peak hot water demand, hours.
The 0.7 factor in Equation 2 has been determined experi
mentally to be the maximum usable general purpose hot water
available from a storage tank after allowance for dilution
with cold inlet water, assuming the inlet and outlet connec-
.tions have been properly designed and located.
If a storage tank is used, the required quantity of 180 or
140 F water which must be supplied by the water heater is
determined from Equation 3.
^
0. - Q, - Q,
(3)
where
Qm -- net quantity of hot water required from the heater, gallons per hour.
Qi total quantity of hot water required, gallons per hour.
The required gas input to the heater is found from Table 13, using the value of Q* from Equation 3.
The National Sanitation Foundation Standard No. 5 rec ommendations for hot water rinse demand are based on 100
percent mechanical operating capacity of the m/hinw -j>.
data provided in Table 14 are also based on 100 percent on-
erating capacity. NSF Standard No. 5 states that 70 percent
of operating rinse capacity is all that is normally attain.^ ei_
cept for rackless-type conveyor machines.
Examples 6, 7, and 8 demonstrate the use of Tables 13 u
and 15.
*%
! '
I
Example 6: Determine the hot water demand for a oe'
water heating system in a cafeteria kitchen with one vegetable sink, 5 lavatories, one pre-scrapper, one utensil washer, and oat two-tank conveyor dimwasher (dishes inclined) with make-uo device. The initial fill requirement for the tank of the uteasd washer is 85 gph at 140 F. The initial fill requirement for the dishwasher is 20 gph for each tank, or a total of 40 gph, at Ho F. The maximum period of consecutive operation of the d&. washer at or above 70 percent capacity is assumed to be 2 hr He supply water temperature is 60 F.
Solution: The required quantities of general purpose (140 F) and rinse (180 F) water for the equipment, from Tables 14 tad 15, are shown in the following tabulation:
/ '
(teat
Quantity Required* Quantity Required*
at 140 f, gph
at ISO F, jpi
Vegetable sink..................... Lavatories (5)....................... Pre-scrapper......................... Dishwasher...........................
Initial tank fill................. Make-up water..................... Utensil washer......................
Initial tank fill.................
45 25 180 --
40 -- --
85
_
-- --
277 --'
139 75
--
Total requirements.........
375
491
Goerml purpose hot water eoosanipUoa, (ram TaMs IS. h Water consumption when diahwasher ia operated at 100 percent of median!cal capacity, (ram Table 14.
The total consumption of 140 F water is 375 gph. The total
consumption 180 F depends upon the type of heater to be used. For a heater having sufficient internal storage capacity to meet the flow demand, in gallons -per minute, the total consumption,
based on the recommendation of The National Sanitation
Foundation, is 70 percent of the total calculated from Table 15, or approximately 350 gph (0.70 X 491' = -344 gph). For an in
stantaneous-type heater, having no internal storage capacity,
the total quantity of 180 F water consumed must be based on the flow demand, gallons per minute. From Table 14, the quan
tity required for the dishwasher is 277 gph; for the makeup, 139 gph; and for the utensil washer, 480 gph. The total con
sumption of 180 F water is 277 + 139 + 480 -- 896 gph, or ap
proximately 900 gph.
Example 7: Determine the gas input requirements for heat
ing water in the cafeteria kitchen described in Example 8, by means of the following types of systems, which are <tmnn8 the
many possible solutions:
a. Separate self-contained storage-type heaters.
b. Single instantaneous-type heater, having no internal stor age to supply both 180 F wM 140 F water through a mixing
valve.
c. Separate instantaneous-type heaters, having no internal storage.
d. Combination of heater and external storage
for MO
F water, plus a booster heater for 180 F water. The heater
and external storage are to supply 140 F water for both the
genera] purpose requirement and the booster heater. The
booster heater is to nave sufficient storage capacity to meet
the gallon per minute flow demand of 180 F rinse water.
Solution a: The temperature rise for 140 F water is 140 ~
60 = 80 deg. From Table 13, the gas input-required to produoe
375 gph of 140 F water with an 80 aeg temperature rise 360,000 Btu per hr. One or more heaters' with thw total Btuh may be selected.
Services
821
a _ Table 13. the gas input required to produce 350 gph of with a temperature rise of 120 deg (180 -- 60) is
Btuh One or more heaters with this total Btuh re-
pement may be selected from manufacturers' catalogs,
s^&hliion b: The correct sizing of instantaneous-type heaters
-ufrvpndent upon the gallon per minute flow rate of the 180 F i? <teI~irer. From Example 6, the hourly consumption of 180 F
<*n?fr hosed on the gallons per minute flow rate is 900 gph. The consumption of 140 F water is 375 gph.
ewn Table 13, the gas input required to produce 900 gph of imF water with a 120 deg temperature nse is 1,296,000 Btuh.
input to produce 375 gph of 140 F water with a teroifiiSe rise of 80 deg is 360,000 Btuh. The total heater re^menfc is 1,296,000 + 360,000 - 1,656,000 Btuh. One or more
jitters meeting this total Btuh requirement may be selected manufacturers' catalogs.
' `Solution e: The gas input required to produce I40F water is the'fflme as for Sofutum b, 360,000 Btuh. One or more heaters
gating this total Btuh requirement may be selected.
The gas input required to produce 180 F water is also the as in Solution b, 1,296,000 Btuh. One or more heaters meet
ing this total requirement may be selected.
' j Solution d: The net hourly hot water requirement must be determined in order to size the heater required to supply 140 F
Water. From Equation 2, the quantity of usable hot water in
storage <3. is (0.70 X 500) -t- 2 = 175 gph. The total quantity of 140F water required is 375 + 350 -- 725 gph. From Equation 3,
the net hot water required Q, is 725 -- 175 = 550 gph.
From Table 13, the gas input required to produce 550 gph of MOF water with an 80 deg temperature rise is 528,000 Btuh.
For systems involving storage tanks it is assumed that' the
water in the storage
has been brought up to temperature
prior to the peak dishwashing period, and that sufficient time ipap before the next peak period to permit recovery of the
water temperature in the storage tank.
The booster heater is sized to heat 350 gph from 140 F to
180 F, a 40 deg rise. From Table 13, the gas input required is
168,000 Btuh.
Example 8: A luncheonette has purchased a door-type dish-
wisher which will handle 16 x 16 in. racks. The existing hot water system is capable of supplying the necessary 140 F water
to meet all requirements for general purpose use, plus supply to a booster heater which is to be installed. Determine the size
of booster heater required to heat 140 F water to provide suf ficient 180 F rinse water for the dishwasher, using:
a. Booster beater with no storage capacity.
b. Booster heater with sufficient storage capacity to meet the gallons per minute flow demand.
,, Solution a;.Since the heater is of the instantaneous type, it must be sized to meet the 180 F water demand at & rated flow.
From Table 14, this rated flow is 6.94 gpm, or 416 gph. From
Table 13, the required gas input, with a 40 deg temperature rise, is 204,000 Btuh. A heater meeting this input requirement may be selected from manufacturers' catalogs.
a. Solution b: In designing a system with a booster heater hav ing storage capacity, the hourly flow demand of the dishwasher
may be used instead of the gallon* per minute flow demand used in Solution a. The flow demand from Table 14 is 69 gph
vhen the dishwasher is operating at 100 percent mechanical ca pacity. However, The National Sanitation Foundation states
that 70 percent of operating rinse capacity is all that is normally
attained for this type of dishwasher. Therefore, the hourly flow demand is 0.70 X 69 = 48 gph. From Table 13, with a 40 deg
temperature' rise, the gas input required is 24,000 Btuh. A booster heater with this Input may be selected from manufac turers' catalogs.
Hot water requirements for kitchens sometimes are also estimated on the basis of the number of meals served (as suming 8 dishes per meal) as follows:
1- ISO F water for single tank dishwasher gph 0.8 (number of meals served) +- (hours of service) 2. 180 F water for two-tank dishwasher gph -- 0.5 (number of meals served) + (hours of service) 3. Hand washing, sink with gas burners
gph a* 3 X capacity of sink (15-in. depth)
4. 140 F general purpose water (add to above)
12 (number of meals served) " (hours of service) + 2
5. Soda fountains and luncheonettes--Use 75 percent of Items 1, 2, 3, and 4.
6. Hotel meals, or other elaborate meals--Use 125 percent of Items 1, 2, 3, and 4.
METHODS OF HEATING WATER
Hot water may be heated either by the direct combustion of fuel, by an intermediate carrier such as steam or hot water, or by electrically heated surfaces. The simplest method is to have the fire on one ride of a metal barrier and water on the other. In such a method, if the surfaces for transferring beat are small, and if the water carries a heavy proportion of prccipitable salts, the water passages may soon become clogged with resultant cracking or burning of the surface. A familiar example of such trouble is the water back in-the kitchen stove, or the pipe coil inserted into the firebox of a warm sir furnace or small boiler. The critical water tem perature at which the lime, magnesia, etc., collect on hot sur faces, varies with the character and proportions of the solids,. but generally such deposits are not serious below 140 F.
Direct-fired Water Heaters
Coal-burning, direct-fired water heaters may be constructed of cored cast-iron sections, or of steel. In some cases the-ex ternal appearance of the cast-iron sections is the same as in hmating boilers, but internally the cores are changed-to en able the sections to withstand the city water pressure. In amall capacity water beaters, efficiency is not considered so important as low first cost and ability to maintain a fire at a low -rate of combustion, and consequently, such heaters are generally built with a dry section or firebrick fining at' the base of the firepot to prevent too much chilling of the fuel. While mud and scale will eventually clog the waterways of any direct-fired heater, increased life may be obtained by providing a three-way cock in the return fine between the heater and the bottom of the storage tank, so that water can be blown through the heater or the tank separately, at full fine pressure, to clean out loose sediment. Cleanout openings in the bottom of the heater are advantageous, if used by op erators for periodic cleaning out of sediment.
Oil-burning, direct-fired water heaters usually are of steel, and operate with higher flame temperature and better effi ciency than commensurate sized coal-burning heaters. As they have the same tendency as coal boilers to accumulate lmt deposits, the water passages should be large in crosssection and accessible for periodic cleaning.
The most common types of gas-fired water heaters are: (1) automatic storage heaters, (2) circulating tank heaters, (3) multi-coil heaters, (4) multi-flue or booster heaters, and (5) instantaneous heaters.
Automatic Storage Type. In this type, the heater, the stor age tank, the insulation and the controls are all combined in a single unit.
Heaters of this type are available with storage tank capaci ties from 10 to 2000 gaL Recovery capacity ranges from 3.8 to over 4500 gal per hour based on a 100 deg rise in temperature. The smaller sizes, with storage capacities of 20 to 40 gal amLinputs up to 50,000 Btuh, are commonly used for private residences, while larger sizes are used in many small and medium-sized commercial applications. When used in mul tiple, they are satisfactory for restaurant installations.
Automatic storage heaters are usually encased in an outer
;i- !
': i j
1j.i
' ;i
i: si
! 1 si
t