is converted into velocity head and a draft loss of some consequence, par ticularly in a short breeching, takes place. A sudden contraction should always be avoided where possible. At times, however, due to obstruc tions or limited head-room, it is necessary to alter the size of the breeching, but a sudden contraction may be avoided by gradually decreasing the area over a length of several feet.
The draft loss due to a sudden enlargement of an area (ho) is given by the equation:
0.000194Jro,,rc
ho =
a;bqwc
(20)
where
Ko = coefficient of sudden enlargement based
the ratio of the areas of the
smaller to the larger section ('
When the flue or passage through which the gases flow is suddenly enlarged, a portion of the velocity head is converted into static head in the larger section and, like the loss due to sudden contraction, a loss of some consequence, particularly in short breechings, takes place. A sudden enlargement in a breeching may be avoided by gradually increasing the area over a length of several feet. In large masonry chimneys, the area of the flue at the region of the breeching entrance is considerably larger than the area of the breeching at the chimney, and a sudden enlargement exists,
The draft loss through the economizer (hs) should be obtained from the manufacturer but for general purposes it may be computed from the following general equation:
where
6.6 W'NTC
He To5
(21)
WD = pounds of gases flowing per hour per linear foot of pipe in each economizer
section. N = number of economizer sections.
An economizer in a steam plant affects the draft in two ways, (1) it offers a resistance to the flow of gases, and (2) it lowers the average chimney gas temperature, thereby decreasing the available intensity. In the case of a natural draft installation, both of these factors result in a relative increase in the height of the chimney and, in the case of a large plant, they may add as much as 20 or 30 ft to the height. The decrease in the temperature of the gases after they have passed through the economizer has an extremely important effect on the performance of a natural draft chimney and also upon the performance of a fan.
CONSTRUCTION DETAILS
For general data on the construction of chimneys reference should be made to the Standard Ordinance for Chimney Construction of the
478
Chapter 26--Chimneys and Draft Calculations
Rational Board of Fire Underwriters. Briefly summarized, these provisions
are as follows for heating boilers and furnaces:
The construction, location, height and area of the chimney to which a heating boiler or warm-air furnace is connected affect the operation of the entire heating system. Most residence chimneys are built of brick and may be either lined or unlined, but in either case the walls must be air-tight and there should be only one smoke opening into the chimney. Cleanout, if provided, must be absolutely air-tight when closed.
The walls of brick chimneys shall be not less than 3J4 in. thick (width of a standard size brick) and shall be lined with fire-clay flue lining. Fire-clay flue linings shall be manufactured from suitable refractory clay, either natural or compounded,' and shall be adapted to withstand high temperatures and the action of flue gases. They shall be of standard commercial thickness, but not less than % in. All fire-clay flue linings shall meet the standard specification of the Eastern Clay Products Association. The flue sections shall be set in special mortar, and shall have the joints struck smooth on the inside. The masonry shall be built around each section of lining as it is placed, and all spaces between masonry and linings shall be completely filled with mortar. No broken flue lining shall be used. Flue lining shall start at least 4 in. below the bottom of smokepipe intakes of flues, and shall be continued the entire heights of the flues and project at least 4 in. above the chimney top to allow for a 2 in. projection of lining. The wash or splay shall be formed of a rich cement mortar. To improve the draft the wash surface should be concave wherever practical.
Flue lining may be omitted in brick chimneys, provided the walls of the chimneys are not less than 8 in. thick, and that the inner course shall be a refractory clay brick. All brickwork shall be laid in spread mortar, with all joints push-filled. Exposed joints both inside and outside shall be struck smooth. No plaster lining shall be permitted.
Chimneys shall extend at least 3 ft above flat roofs and 2 ft above the ridges of peak roofs when such flat roofs or peaks are within 30 ft of the chimney. The chimney shall be high enough so that the wind from any direction shall not strike the top of the chimney from an angle above the horizontal. The chimney shall be properly capped with stone, terra cotta, concrete, cast-iron, or other approved material; but no such cap or coping shall decrease the flue area.
There shall be but one connection to the flue to which the boiler or furnace smokepipe is attached. The boiler or furnace smoke-pipe shall be thoroughly grouted into the chimney and shall not project beyond the inner surface of the flue lining.
The size or area of flue lining or of brick flue for warm-air furnaces depends on height of chimney and capacity of heating system. For chimneys not less than 35 ft in height above grate line, the net internal dimensions of lining should be at least 7 x 11)4 in. for a total leader pipe area up to 790 sq in. Above 790 and up to 1,000 sq in. of leader pipe area the lining should be at least 11J4 x 11)4 in. inside. In case of brick flues not less than 35 ft in height with no linings, the internal dimensions should be at least 8 x 12 in. up to 790 sq in. of leader area, and at least 12 x 12 in. for leader capacities up to 1,000 sq in. Chimneys under 35 ft in height are unsatisfactory in operation and hence should be avoided.
CHIMNEYS FOR GAS HEATING
The burning of gas differs from the burning of coal in that the force which supplies the air for combustion of the gas comes largely from the pressure of the gas in the supply pipe, whereas air is supplied to a bed of burning coal by the force of the chimney draft. If, with a coal-burning boiler, the draft is poor, or if the chimney is stopped, the fire is smothered and the combustion rate reduced. In a gas boiler or furnace such a condition would interfere with the combustion of the gas, but the-gas would continue to pass to the burners and the resulting incomplete com bustion would produce a dangerous condition. In order to prevent incom plete combustion from insufficient draft, all'gas-fired boilers and furnaces should have a back-draft diverter in the flue connection to the chimney.
A study of a typical back-draft diverter shows that partial or complete