HEATING VENTILATING AIR CONDITIONING GUIDE 1941 Table 1. Flow of Steam in Pipes P = loss in pressure in pounds. D = inside diameter of pipe in inches. L = length of pipe in feet. d = weight of 1 cu ft of steam. W = pounds of steam per hour. P = 0.0000000367 ( 1 + 3.6 \ ) WL dlP Loss Ounces Col. 1 Pipe She 5220VkxJ Nominal DIniatemrentaelr Cou 2 Internal . Abba op 1 D> Sq Inches < Col. 3 Steam . bt Gaos rr V' Length or Pipe Fienet Col. a Jloo y~r 0.25 0.50 1.00 2 3 4 5 6 7 8 10 12 14 16 20 24 28 32 40 48 80 160 320 480 65.28 92.28 130.5 184.6 226.0 261.0 291.8 319.7 345.3 369.1 412.7 452.0 488.3 522.0 583.6 639.3 690.5 738.2 825.4 904.1 1167.2 1650.7 2334.5 2859.1 i 1.049 0.864 0.536 -1.0a 0.187 M 1.380 lH 1.610 2 2.067 1.496 2.036 3.356 1.178 --0.5a 0.190 1.828 0.0 0.193 3.710 0.3 0.195 VA 2.469 3 3.068 4.788 7.393 6.109 11.183 1.3 0.201 2.3 0.207 3H 3.548 9.887 16.705 5.3 0.223 4 4.026 12.730 23.631 10.3 0.248 4M 4.506 15.947 32.134 15.3 0.270 5 5.047 20.006 43.719 20.3 0.290 6 6.065 28.886 71.762 30.3 0.326 7 7.023 38.743 106.278 40.3 0.358 8 7.981 50.027 149.382 50.3 0.388 9 8.941 62.786 201.833 60.3 0.415 10 10.020 78.854 272.592 75.3 0.452 12 12.000 113.098 437.503 100.3 0.507 14 13.250 137.880 566.693 125.3 0.557 16 15.250 182.655 816.872 150.3 0.603 r.o\limn 1X2X3X4" lb of 8teaie 175.3 0.645 pipe for a given condition. 200.3 0.685 .. 2 in. pipe -- 1.3 lb press. -- 100 ft equivalent length <1V370o.5 X V A3h.71=0 XaafOt.8.Ws1o Xft ieainvalent ra"=dfia"tYio*"n.* Table 1 does not allow forJ^nedjyte, m low-pr=^e steam, conaensauon in wvw 20 2.240 40 1.580 60 1.290 80 1.120 100 1.000 120 0.912 140 0.841 160 0.793 180 0.741 200 0.710 250 0.632 300 0.578 350 0.538 400 0.500 450 0.477 500 0.447 600 0.407 700 0.378 800 0.354 900 1000 1200 1500 0.258 2000 0.224 268 CHAPTER 14. PIPING FOR STEAM HEATING SYSTEMS locations may be different than those which exist for appreciable periods at other locations and which under constant pressure may have conditions that are approximately the same. In designing piping it is of especial importance to arrange the system to preclude trouble caused by such pressure differences.' The systems which readily release the air permit uniform pressures to be attained in much shorter time intervals than those which are sluggish. Results are given in Fig. 1 from investigations1 to determine the rate of condensate and air return from a two-pipe gravity heating system.. Variations in the steam pressure during the warming up period when the rate of air elimination and condensation is high are clearly indicated in these curves. It is evident that the condensation flow during the initial warming up Air Elimination Rates period reaches a peak which is greater than the constant condensation rate which is eventually reached when the pressure becomes uniform. Moreover, the peak condensation rate is obtained when the system steam pressure is lower than that existing during a period of constant condensing rate. It will also be noted that the peak rate of air elimination does not coincide with the higher condensing rate. STEAM FLOW The rate of flow of dry steam or steam with a small amount of water flowing in the same direction is in accordance with the general laws of gas flow and is a function of the length and diameter of the pipe, the density of the steam, and the pressure drop through the pipe. This relationship has been established by Babcock in the formula given at the top of Table 1. In Columns 1, 2, 3, and 4 of this table, the numerical values of the factors for different pressure losses, pipe diameters, steam densities and lengths of pipe have been worked out in convenient form so that the steam flowing in any pipe may be calculated by multiplying together the proper factors in each column as shown in the example at the bottom of the table. JA.S.H.V.E. Research. Report No. 954--Condensate and Air Return in Steam Heating Systems, by F. C. Houghten and J. L. Blackshaw (A.S.H.V.E, Transactions, Vol. 39,1933, p. 199). 269 /