868 CHAPTER 34 1958 Guide low pressure. In many cases these sprays are set at an angle with the air flow. Air washers of this type not . only perform necessary heat transfer functions, but also remove some dust and dirt from the air stream. Essential requirements in the air washer operation are: uniform distri bution of the air across the chamber section; moderate air velocity of from 250 to 600 fpm in the washer chamber; an adequate amount of spray water broken up into fine droplets throughout the air.stream;, sufficient length of travel through the water spray and: wetted surfaces; and the elimination of entrained moisture from the outlet air. Expected performances, physical size, length, number of sprays, etc., vary greatly, depending upon the functions of the installation. In * the width and height of an air washer are dictated by the space available. Washers of nearly equal height and width are desirable from an air no and economic standpoint, although not necessary. The length of wasne varies considerably. A space of approximately 2% ft between spray panas is used, and the first and last banks of sprays are located about 1 ft to i3 from the entering or leaving end of the'washer. In addition, aar waS~, are very often furnished with cooling coils or heating coils within the war"_ chamber, and the use of these coils affects the overall length of the wasn Where increase of overall heat transfer between the air and water is required, multistage washers are used. These washers are equivalen a number, of washers in series, and the water is often pumped from stage to the other where conditions permit. The resistance to air flow through an air washer varies with of eliminator, and wetted surfaces, number of banks of spray ana Spray Apparatus 869 direction, air velocity,' size and type of other resistances such as cooling and heating coils, and other factors such as air density. Resistances vary from as low as j in. to higher than 1 in. water column, and it is therefore necessary that the manufacturer be consulted in regard to the resistance of any particular washer design involved. HUMIDIFICATION WITH AIR WASHERS Air humidification can be accomplished in three ways with an air.washer. These are: (1) use of recirculated spray water without prior treatment of the air; (2) preheating the air and washing it with recirculated spray water; and (3) using heated spray water. In any air washing installation the air should not enter the washer with a wet-bulb temperature less than 35 F in order to eliminate danger of freezing the spray water. Method 1. Except for the email amount of energy added from'outside by the recirculating pump in the form of shaft work, and for the small amount of heat leak from outside into the apparatus, including the pump and its connecting piping, the process would be strictly adiabatic. . Evapo ration from the liquid spray would therefore be expected to bring the air immediately in contact with it to saturation adiabatically; and, since the liquid is recirculated, its temperature would be expected to adjust to the thermodynamic wet-bulb temperature of the entering air. It does not follow from the foregoing reasoning that the whole air stream is brought to complete saturation, but merely that its state point should move along a line of constant thermodynamic wet-bulb temperature as explained in Chapter 3. The extent to which the final temperature ap proaches the thermodynamic wet-bulb temperature of the entering air, or the extent to which complete saturation is approached, is conveniently expressed by a ratio known as humidifying effectiveness or saturating effec tiveness, and is defined as t\ -- t% h = --; X 100 (1) where h = humidifying effectiveness, percent, h = dry-bulb temperature of the entering air, Fahrenheit, q = dry-bulb temperature of the leaving air, Fahrenheit. I = thermodynamic wet-bulb temperature of the entering air, Fahrenheit. The following may be taken as representative humidifying or saturating enectiveness of a spray-type air washer for the conditions stated: 1 bank--downstream.......................................................... ;.. 60-70 percent I bank upstream......... ..................................................... 65-75 percent , banks--downstream............................................................... 85-90 percent f banks--1 upstream and 1 downstream............................. 90-95 percent & banks--upstream................... ,.:.......................................... 90-95 percent unnne, or saturating effectiveness of a washer is dependent cond't' e?fe?tial items of design mentioned under Air Washers. Other v1:n.u,,tl?ns 9mg the same, low velocity of air flow is more conducive to g er humidification effectiveness. bulht^ Preheating of the air increases both the dry- and. wet- humidqmper^tures' iwers the relative humidity, but does not alter the mty ratio (pound water vapor per pound dry air). At a higher wet-