Document B85GbYvN893RDXMNgeyXyEwMk
FIRE EXTINGUISHMENT AND CONTROL
Class D fire, as well as the correct way to extinguish Class D fires These units are not classified by a numerical system and
axe intended for a special hazard protection only
The following recommendations are given in NFPA Standard No 10 as a guide in marking extinguishers, and/or extinguisher locations, to indicate the suitability of the extinguisher for a particular class of fire Extinguishers suitable for more than one class of fire may be identified by multiple symbols as described previously
Markings should be applied by decalcomanias, painting, or similar methods having at least equivalent legibility and durability
Where markings are applied to the extin guisher, they should be located on the front of the shell above or below the extinguisher name plate Markings should be of a size and form to give easy legibility at a dis tance of 3 ft
Where markings are applied to wall pan els, etc, in the vicinity of extinguishers, they should be of a size and form to give easy legibility at a distance of 25 ft
OROINART
A
COMBUSTIBLES
1. Extinguishers suitable for Class A fires should be identified by a triangle con taining the letter "A" If colored, the triangle shall be colored green
FLAMMABLE LIQUIDS
2 Extinguishers suitable for Class B fires should be identified by a square con taining the, letter "B " If colored, the square shall be colored red
COMBUSTIBLE METALS
4 Extinguishers suitable for fires revolving metals
should be identified by a
five-pointed star containing the letter "D" If colored, the star shall be colored yellow
Extinguishers listed by Underwriters' Lab oratories, Inc, are rated after physical test ing These ratings, which are indicated by a numeral and a letter, define the extin guishing potential of an extinguisher be cause they specify the type and size or num ber that should be installed in a specific area
The numeral signifies the number of units of extinguishing potential and the letter(s), the dass(es) of fire on which the particu lar extinguisher is most effective for ex tinguishment For example, a 4-A 16-B C rating signifies that the extinguisher is rated for 4 units of Class A fire-fighting potential, 16 units of Class B fire-fighting potential, and is safe to use on Class C fires in or near electrical equipment
Extinguishers labeled with pre-1958 clas sifications can be reclassified by using con version tables published by the National Fire Protection Association (NFPA) in Std No 10, Portable Fire Extinguishers
Location of units The extinguisher must be located close to the likely hazards, but not so close that it would be damaged or cut off by the fire It should be located along the normal path of egress from the budding Where highly combustible mate rial is stored in small rooms or enclosed space, the extinguisher should be located outside the door, never inside where it might become inaccessible
eELECTRICAL EQUIPMENT
3 Extinguishers suitable for Class C fires should be identified by a circle con taining the letter "C " If
colored, the circle shall be colored blue
"Note Recommended colors as de scribed in the Federal Color Standard Num ber 595 are
Green -- No 14260 Red - No 11105 Blue - No 15102 Yellow - No 13655
!
34-17