HIGH TEMPERATURE HIGH PRESSURE SPRAY TEST HOT MANIFOLD TEST
LOW PRESSURE SPRAY TEST / WICK FLAMMABILITY TEST
MOLTEN METAL TEST (MONSANTO)
HOT CHANNEL IGNITION TEST
AUTOIGNITION TEMPERATURE (AIT)
FLASH AND FIRE POINTS 0*31601
TOWOLDMONOQ32006
Know Your__ Hydraulic)
Fire Tests
y?
klO
V/
Defining fire resistance in precise terms and numbers is extremely difficult and is best done in terms of expected fire hazards. Assessment of hazards should include consideration of all three components re quired for combustion--fuel, oxidizer, and source of ignition--as well as ways in which the three can combine into a fire. Simulative tests are considered most meaningful in assessing fire resistance. Since exposure conditions and sources of ignition vary widely, multiple tests are usually used in fire re sistance evaluation. Test conditions should reflect two basic parameters of fire resistance--the ability to resist ignition and to prevent propagation of flame away from the source of ignition.
An ounce of prevention can be worth the cost of a plant or even the life of a worker. Hazardous plant operations can be isolated--fire walls can be built;
sprinkler systems can be instalW.
But the simplest and surest way lo protect against firesis-t^stop tneTp befej^l)j>e^start
--with fire-resistant Pydraijr f|uids(rydrauP\yill not support combus?
When emergencies occ^/r^Pydrauj^j^inimizes the danger of local fires mat can injure workmen, spread to other locations, flash back to the Jtse-crtr ^ 4jg6o- break, or destroy'equipment. By their very chemical naturefcPydraul fluids are fire-resistant-- from start-up through every hour of operation.
Know yourhazards . . . know the tests and performance levels which are essential for assessing the fire resistance of any hydraulic fluid. The most widely accepted tests for/measuring fire resistance are presented on the following pages.
he/>ftruMsUi
Oi,31b02
TOWOLDMON0032007
HIGH TEMPERATURE HIGH PRESSURE SPRAY TEST
Procedure: AMS 3150C. The fluid, at 1000 psi, is sprayed through a 0.0145 in. diameter orifice pass ing through the flame of an oxyacetylene torch with a No. 1 Purox tip held perpendicular to the fluid stream. Attempts are made to ignite the fluid Btream at varying distances from the orifice.
Performance: This test simulates the hazard of a
^^^jyayTrO^
riituUc fluid leak coming in contact
with a high temperature flame ignition source. Per
formance is evaluated based on the ease of ignition,
and the distance the flame is carried from the source
of ignition, if ignition occurs.
0431603
TOWOLDMON0032008
HOT MANIFOLD TEST
Procedure: AMS 3150C. Ten milliliters of fluid are dripped in 40 seconds onto a stainless steel simu lated hot manifold held at 1300F. (704C.). Flash ing or burning on contact with the (tube, and carrying of flame to fluid collected in th^ bottom of the shield/tube holder are observed.
Performance: This test simulates a hyaremhc fluid leak coming into contact with a hot surface. The hydraulic fluid should show only intermittent flash ing or burning when dripped on the 1300F. (704 C.) manifold and should not carry flame to the bottom of the shield.
LOW PRESSURE SPRAY TEST
Procedure: AMS 3150C. The fluid is sprayed from a Binks Thor No. 7 paint spray gun (0.070 inch diameter orifice, 40 psi air) in bursts over the source of ignition, burning oil-soaked waste. Any increase or decrease in the flame caused by the fluid mist is observed.
Performance: This test is not commonly used, but is designed to simulate a line break spraying onto an open source of ignition. Criteria of performance is to observe for flame increase, no change, or de crease in intensity.
O't3lb0'1
TOWOLDMON0032009
i
WIC FLAMMABILITY test
\/ Procedures U.S. Bureau of Mines Schedule 30. A pipe cleaner is soaked with fluid and cycled in the horizontal plane into the hottest part of a nonluminous flame of a laboratory burner. The number of cycles required to give a /elf-sustaining flame is
determined. \
Performance: ThisXtest simulates fluid soaked in
absorbent flammable materials and exposed to open
flames. This test is applicable to water-containing
fluids, but can also be used to demonstrate the
stability of non-evaporaling synthetic and synthetic
base fluids.
\
MOLTEN METAL TEST (MONSANTO)
Procedure: Fluid is sprayed, poured or dripped on to molten, metal surfaces in the 800F. (zinc) to 1200F. (aiuminum) range. Observations are made of burning rates and tendencies to propagate flame to fluid-wet areas adjacent to molten metal sur faces. This is done both with and without an ex ternal source of ignition such as a spark or flame.
Performance: This test measures ease of ignition on a molten metal surface and provides an indication of flame intensity if flashing or burning occurs.
0*3160^
TOWOLDMONOQ32010
HOT CHANNEL IGNITION TEST
Procedure: factory Mutual Engineering Associa tion. Fluid iVsprayed at 1000 psi and 140F. from a 1.5 gph, 80\ angle oil burner, nozzle on to the 1300F. surface! of a channel iron. The channel is 7 inches wide by 26 inches lpng steel and is sup ported at a 30 a^igle.
Performance: ThisXtest simulates ignition by hot metal surfaces and \equi/es that no ignition occurs when fluid is sprayed oj! the 1300F. surface.
AUTOIGNITION TEMPERATURE (AIT)
Procedure: ASTM D 2155-66. A fluid sample is in jected via hypodermic syringe into a heated glass flask. Autoignition is determined by appearance of visible flame.
Performance: This test measures autogenous igni tion temperature in glass in air at one atmosphere pressure. Test conditions are critical and applica tion of data to metal systems of irregular design is difficult.
TOWOLDMONOQ32011
FLASH AND FIRE POINTS Procedure: ASTM D 92-66. The fluid is heated in an open test cup at a constant rate. A small test flame is passed over the surface at specified tem perature intervals. The lowest temperature at which the vapors above the surface ignite is the flash point. The fire point is the temperature at which the fluid ignites and burns for at least five seconds. Performance: This test measures the ignitability of heated fluid. Flash and fire test results are some times misleading since they are so directly related to the chemical nature of the product being tested.
<>3160 7
TOWOLDMONOQ32012
*!
The Tests
Described Here...
show some of the rigopusifiethods of determining fire resistance. So^,e(Pydrajihnids show intermix
ZtfivnuJ df
tent flashing or bulling under severe ^exposure, bu
they will not support combustion /(way from a: ignition source; Pydraui is tne oijhy fire-resistam AvuA
hydraulic fluid listed /by ^Underwriters' Labors-
tgrig6,-Inc. for hazardous hydraulic application
c ,ic
f` *^ *id* /// , .
1/snAfui^ti/J 'J-Uc^L.
// Pydraur fluids are chemically synthesized from .. yo 'Snatefials which resist burningj^Wa?CT^iasea:::^y^M:p^)/^
drauliG-fluids-depend-on the water for Are -resistance,
r,
' -&Ue-V/) 4444 Jd
,
1/--4-C4*Q/J
byitheJubricant-Gomponentsare-flammable: Glycdi^// f \
-(inwater-glycol fluids) `andiight petroleum'Tjilg'lin A/j 'T)^ ' ftO /) -
water-oil .emulsions) will bothbuwvCompared-with
i^^-p_UCi-OXA^
j-^^at^-based-fluids4br-Jb^j^jsUnx^-Eyjdr-ab ft/v*.
Yap4i4/M<u< zdj) uplift
fr
^uids ^Idom-appear-inore-flre-resistanti-butr-teet-9-- ^
'
of-ueed water-based -fluids -do -not-slrow-the-same
-degree -of flfel'^isTahce--flammability-increases-as
iho-water snufferevaporates'from-tl:ie^ysterrr.
Residual, or lasting, fire resistance through this simple demonstration:
3. Dip blotter paper squares in Pydreral, water-
plvool-flukL-water-oi) jemulsion. -and -mtoirr water:
2. Drain off excess fluid and prop on glass dish fi>r-an -bour-or-twor-
3. I
with ]pj>r book match.
4. 'Eydraul d'oesbot-evaporaterdoesnot-ehange. `if does not burn.
bi-dPiece-dipped -in water bums-normallyr
fi.--WateM3Hyeol--and --water-oil -papers burn'
brighter, hotter,-due tothe'flammable giycol
and oil bases.of theiwo-flaid's.
s 0 /b/b
>i<AVv .
bis demonstration points out the lasting fire re sistance of Pydraubfluids that water-and oil types do not have. In any Hydraulic operation, a break or a leak can spew fluid over equipment, floors, walls, and ceilingsproducingan "innocent" puddle. I%drS31'' fluids will remain fire-resistant under these and all conditions.
0431600
TOWOLDMONOQ32013
Pydraul Fluids Offer
Fire Resistance and Top Performance
Besides fire resistance, Pydraul fluids offer you performance characteristics that will cut your maintenance time and costs drastically. Pydraul lubricates as well as premium grade antiwear oils. And they prevent rust and corrosion caused by water-base fluids. Machines operating on Pydraul simply require less maintenance; pumps last longer.
If you need the safety of a fire-resistant fluid and want the economies of less maintenance, you need Pydraul. Pydraul is now being used in these applications, but the danger of hydraulic fires exists in many other applications if ignition sources are near.
------------------------------------------------------------------------------
.
. i ;
Automatic Welding BOF
Coil Bander Coke Ovens Core Molding Machines Damper Controls Die Casting Machines Draw Bench Electric Arc Furnaces Elevators and Hoists Extrusion Presses Forging Presses Furnace Door Openers Furnace Loader Furnace Tilters Heat Treat Furnaces Hydraulic Jigs Hydraulic Presses
'
Hydraulic Shears Induction Furnaces
Ingot Loaders Injection Molding Machines
Mobile Equipment Permanent Mold Casters
Plating Machines Quenching Furnaces
Regulators Remelt Furnaces
Scarfers Scrap Metal Balers
Stampers Tilting Crucible
Trim Presses Turbine Bearing Lubrication
Turbine Controls Vacuum Degassing
0431609
TOWOLDMONOQ32014
/'hfV-vi4
ciAjf
1X^4 ^ Biull
1-oA h"U^ -
16 mm full-color irjovte available--15 minuted
"BEFORE HYDRAULIC |IRES START"
Now you can see for yourself-- and demonstrate to others
Tests-showilng fireuesuHance of
gydraul fluids
""
^ypIcaVPydraljHtistallations^
An incident injvhich-Eydraul^' /preventea-disaster ^
receive ac^y for^oWirigTvKite:
Monsanto
Monsanto Company / Functional Fluids / 800 North Lindbergh Blvd. / St. Louis, Missouri 63166
0431610
TOWOLDMONOQ32015
DISTRICT SALES OFFICES ALL DIVISIONS
Additional District Offices
are msin,ain,'d *'
ATLANTA, GEORGIA 30326
Lenox Towers East 3400 Peachtree Rd, N. E.-Suite 1711 Tel. (404) 577-2260
BOSTON, MASSACHUSETTS 02149
Everett Station Tel. (617)387-5010
CHICAGO, ILLINOIS
3158 Des Plaines Ave. Des Plaines, Illinois 60018 Tel. (312)296-6688
Agricultural Division
LULING, LOUISIANA 70070 P. 0. Box 174 Tel. (504) 784-6263
MEMPHIS, TENNESSEE 38113 1023 Riverside Drive P. 0. Box 13248 Tel. (901)947-3151
Textiles Division
CINCINNATI, OHIO 45206
1501 Madison Road
Tel. (513)751-6707
CLEVELAND, OHIO 44122
3645 Warrensville Center Rd.
Tel. (216)991-5400
DETROIT, MICHIGAN 48235
500 Northland Towers East Tel. (313) 357-0910
HONOLULU, HAWAII 96812
205 Pacific International Bldg. 677 Ala Moana Blvd., P. 0. Box 3824
Tel. (808) 512-744
HOUSTON, TEXAS 77002
1300 Main Street
Tel. (713) 223-4011
LOS ANGELES, CALIFORNIA 90022
6670 E. Flotilla St.
Tel. (213)723-2492
MINNEAPOLIS, MINNESOTA 55402
912 Northstar Center 110 S. Seventh St.
Tel. (612) 339-4651
NEW YORK, NEW YORK 10017
277 Park Avenue
Tel. (212)922-4111
PITTSBURGH, PENNSYLVANIA 15222
No. 4 Gateway Center Bldg. Room 534 Tel. (412)261-2156
ST. LOUIS, MISSOURI 63166
800 N. Lindbergh Blvd.
Tel. (314) 694-1000
SAN FRANCISCO BAY AREA
2710 Lafayette, Santa Clara, Calif. 95052
Tel. (408) 243-0414
AKRON, OHIO, 44313 3030 West Market St. Tel. (216) 836-7941
ATLANTA, GEORGIA 30303 Atlanta Merchandise Mart 240 Peachtree St., N. W. Tel. (404) 577-2260
CHARLOTTE. NORTH CAROLINA 28202 Wachovia Bank Buifding 129 West Trade St. Tel. (704)376-9871
ENGLEWOOD CLIFFS. N. J. 07631 661 Palisades Ave. Tel. (201)568-2151
NEW YORK, NEW YORK 350 Fifth Ave. Tel. (201) 556-5100
Hydrocarbons & Polymers Division-Lion Oil
EL DORADO, ARKANSAS 71730 Lion Oil Building Tel. (501) 863-3111
JACKSON, MISSISSIPPI 39209 P. 0. Box 10937 Westland Station Tel. (601)352-3648
LITTLE ROCK, ARKANSAS 72203 1515 West Seventh St. Tel. (501)376-2437
MEMPHIS, TENNESSEE 38113 1023 Riverside Drive P. 0. Box 13248 Tel. (901)947-3151
SEATTLE, WASHINGTON 98104
911 Western Avenue Tel. (206) 622-4203
SPRINGFIELD, MASSACHUSETTS 01101
730 Worcester Ave. Tel. (413) 788-6911
WILMINGTON, DELAWARE 19803
2005 Concord Pike, Fairfax Tel. (302)658-6531
Organic Chemicals Division (Rubber Industry)
AKRON. OHIO 44311 920 Brown Street P. 0. Box 2307 Tel. (216)434-1921
Monsanto
The information contained In this bulletin is, to our best knowledge,
true and accurate, but all recommendations or suggestions are made without guarantee, since the conditions of use are beyond our control.
The Monsanto Company disclaims any liability incurred in connection with the use of these data or suggestions. Furthermore nothing con
tained herein shall be construed as a recommendation to use any prod uct in conflict with existing patents covering any material or its use.
Monsanto Company / Functional Fluids / 800 North Lindbergh Blvd, / St, Louis, Missouri 63166
1068-IGI-LRA LITHO IN U.S.A.
04316X1
TOWOLDMONOQ32016