716 CHAPTER 45 1965 Guide And Data Book As shown, the two elements are rigidly connected by means FLOAT SWITCHES of a rod so that motion of one causes motion of the other. On the connecting rod is a power tafrenff that operates single-pole The float switch is a device in which a float, through vari double-throw contacts (as shown) or valves. A compression . ation in the level of a liquid, operates one or more sets of elec- spring permits setting of the differential pressure at which the device operates. The sum of the forces developed by the k>w- ' trical contacts. It is connected by equalizing lins to the vessel in which the liquid level is to be maintained or indicated. presure bellows the scale spring equals the force de Operation and Selection veloped by the high-pressure bellows at the control pointy . In discussing thin type of controller, two terms must be de - Some float switches (see Tig. 2) operate from the move fined and thoroughly understood. Instrumental differential is ment of a magnetic armature which is located in the field of a the difference in pressure, between the low and the high presv~'- permanent magnet.-- Others -(see Tig. 3) employ a variable sure elements for which theinstrument is adjusted. In the case- electiic signal 'generated ia a pickup coil located on the float of a temperature element this difference is expressed in chamber to operate a power relay. Still others employ true degrees. .Operating differential is, the difference in pressure or solid state circuits in. which a variable signal is generated by temperature required to open or.close the switch contacts.',It', ' ' liquid contairt .with; a probe which, replaces the float. .The is actUilBy the change ih instrument differential from' cutAin tO latter methods are'adapted to remote controlledapplications cut-out for( any,'setting. Operating differential can be'varied ' 'and are preferred' fori'ultra-low temperature applications. by means of a`second spring that acts in thesame direction as V.-' 'Switches having'mercury-tube contacts are usually not recom- the first, and takes effect only at the cut-in or cut-out pdiht^ _ ` mended for installation in an ambient temperature lower than without affecting the other spring. A second methbd'criuld be -: --'25 F since mercury will Creese solid at temperatures of to adjust the distance between collars Z-Z on the connecting approximately --38 F. rodrThe greater the distance between them, the greater the operating differential. Application Where.a constant instrument differential is required on a The float switch can be.used to maintain- or, indicate*the temperature; sensitive differential controller;.throughout a level of,a liquid,,operate an alarm, control the operation of a large temperature range, it.is usually necessary, to use a dif pump, or .to perform many other functions. . ferent fill in one element.than in the other,-if,they are of the A; float switch, solenoid liquid valve, and .hand expansion vapor charged type. The alternate is to use liquid filled power valve combination can be used to control the refrigerant level elements. .- on the high or low pressure ride of the refrigeration system in A second-type of-differential-temperature1 control employs the same manner, as high side or low ride float valves.are two capsules and capillaries connected to .one bellows and a used. Thei hand expansion valve, located in the refrigerant liquid fill This is known as a eonstanl-coliinie type fill, once liquid'line.immediately downstream of-the solenoid valve, is the operating point corresponds toa.constant vphime^of the initially adjusted .to provide a refrigerant flow rate at maxi two capqilea, Rspillftries, and bellows.. It should be noted that mum load, so as .to keep the solenoid liquid valve in the open if the two bulbs,have equal volume, a rise in the tempeiatiire position 80 to 90 percent of the time; it need not be adjusted of.one bulb requires an equivalent fall in the temperature of thereafter. From the outlet side of the hand expansion valve the other to maintain the operating point. . . ` . the refrigerant passes through a line and enters the evaporator or surge drum, depending on-the unit design. , . Refrigerant Control Devices' 717 When the float switches applied for low ride level control, proper precautions must be taken to provide a quiet, liquid level'that properly falls in response to.an increase in evapo rator,load, and rises with a decrease in evaporator load. -The same recommendations for insulation of the body and liquid leg of the low ride float valve apply to the float-switch when it is used for refrigerant level control oh the low pressure ride of the refrigeration system. To avoid floodback in this appli cation, controls should be wired to prevent the opening of the pnlonnid liquid valve when the solenoid suction valve closes or when the compressor stops. ; >'.- ;. PART II: CONTROL VALVES . ' "Valves are.used to start, stop, direct, modulate the flow of refrigerant to satisfy the'system requirements in accordance with" load requirements. To assure satisfactory performance, vaives should be adequately protected from foreign material, excesrive moisture, and corrosion in refrigeration systemfl, by the installation of properly'sized strainera and- driers.. Space does not permit illustration of all of the valve designs and 'constructions which are eurrently available. It should be noted , that the diaphragm and bellows can; be used inter changeably in various types of refrigerant,flow `control valves. THERMOSTATIC EXPANSION VALVES The thermostatic erp&nnnTi valve controls the flow rate of liquid refrigerant entering the evaporator,inresponse to the superheat-of the refrigerant gas leaving the evaporator. Jts baric function is to keep practically the entire 'evaporator active, without permitting unevaporated refrigerant'liquid to be returned through' the suction line;to the compressor. The thermostatic expansion valve accomplishes.this by con trolling the mass flow rate of refrigerant entering the evapo rator so that it equals the rate at which* the refrigerant- c*n he completely vaporized in the evaporator by the absorption - of heat. Since the thermostatic expansion valve is operated by the superheated refrigerant gas leaving the evaporator and is responsive to changes in superheat of this gim, a portion of the evaporator must be devoted to superheating the refrigerant gas. ' . . `' : *. < Unlike the constant pressure type,-use of the thermostatic expansion valve is not limited to constant load applications. They are used successfully for controlling the refrigerant flow in air-conditioning, commercial, low temperature, and ultra- low temperature refrigeration systems. They are also applied to control all types of direct expansion evaporators. - ' .Operation .. A schematic - cross-section of the thermostatic arpa-nainn valve, with the principal components identified, is shown in Tig. 4., The three forces shown which govern thermostatic ex pansion valve operation are: -Pv * the vapor pressure of the thermostatic element (a func tion of thebulb temperature) which is applied to the top * of the diaphragm and acta to open the valve.' .. Pa " .the evaporator pressure, which is applied underneath the .... diaphragm through the equalizer passage, and acta in a ... cloang direction. . Pi the* pressure equivalent of' the superheat spring force; which is applied underneath the diaphragm, andis a closing force. At any constant operating condition, these forces are and Pi = Pa + Pi. Fig. 5. shows an evaporator nring Refrigerant -12;and operating at a saturation temperature, of 40 F (37 psig).; liquid refrigerant enters the expansion valve, is reduced- in pressure and temperature at the valve port,-and enters the evaporator, at point A as a mixture of saturated liquid-and vapor. As flow continues through -the evaporator, more and more of the boiling refrigerant is evaporated. The refrigerant temperature will remain at 40 F until the liquid portion is completely evaporated by the absorption of heat at point B. From this point, additional heat absorption the temperature and superheats the refrigerant gas, while the pressure remains constant at 37 psig, until at point C (the outlet of the evaporator) the refrigerant gas temperature is 50 F. At this point the superheat is 10 F deg (50 -- 40). An increase in the heat load on the evaporator increases the temperature of the refrigerant gas leaving the evaporator. The bulb of the thermostatic expansion valve senses thin increase; the thermostatic charge pressure (Pi) increases and causes Fig. 2 .... Magnetic Hoot Switch Pt -THERMOSTATIC ELEMENT'S VAPOR, PRESSURE '. ' %-EVAPORATOR PRESSURE Pt -PRESSURE ^EQUIVALENT OP THE SUPERHEAT SPRING FORCE Rg. 4 .... Thermostatic Expansion Volvo* Fig. 5 .... Thermostatic Expansion Valve Controlling Flow of Liquid Refrigerant i 2 Entering Evaporator