YOUR "ASKAREL" TRANSFORMER SHOULD BE
TOWOLDMON0030411 WATER_PCB-00014880
FAR A8 EQUIPMENT CAN BE I)
iest friend!
Since "askarel'' type transformers were first made in 1930, few pieces of electrical equipment have equalled these "juice controllers" in trouble-free service. The name "askarel" applies to the liquid insulation that fills askarel type transformers. And "askarel" is a general name for a unique kind of chemical classified as a halogenated hydrocarbon. But., don't let this chemical jargon bother you one bit. After you read this little pamphlet, you'll be un EXPERT on operating askarel transformers; you'll know all about this wonder ful liquid askarel insulation because it's all very simple.
Since many engineers and maintenance operators work with BOTH askarel and transformer "oils," you will want, to remember that askarel is different from mineral oil . . . and you'll want to know the simple ways to ' check up" on the health of your askarel transformer.
That's the reason for this pamphlet. First, to tell you that your askarel transformer, in addition to being F1RESAFE, can be the most trouble-free piece of equipment you operate. Second, to give you the few simple facts that will make you an expert on the "whys" and "wherefores" of the easy maintenance. Knowing the facts given on the following pages, you will keep your askarel (and transformer) operating at trouble-free, top performance, year, after year, after year.*
*We own one thmt has boon operating as faithfully as a haart beat for 28 years I
Monsanto a/so supplies:
Pydraul AC All synthetic fire-resistant compressor lubricant.
Pydraul
All synthetic fire-res'Stant hydraulic fluids.
Thermal Fluid Fire resistant, non-vaporising heat transfer fluid.
Coolanol
Dielectric coolants for tugn power electronic circuits.
Fluid OS-59 Dielectric for high frequency power transformers.
Askarel transformer fluids can be ordered directly from any one nf these Monsanto sales service centers A" I;j r t a Hoston
Syracuse Wilrini'glon
o
LET'S
OHS -- that can burn There uri> 11uit* a number of these. They are sold by oil companies; anil these mineral nils are used m transformers where, if they catch lire, no ureal harm [besides t hi* transformer tselfi conies from the burning oil. If water gets into an oil-lilled transforrv.er, it. lends to settle through the oil lo the bottom. There are certain wavs to cheek on the health of mineral oil insulation, loo, but the "('heekpmtils" arc somewhat different than for askarel. ASKARELS -- that cannot burn Although there are TWO fypes of asknrcl fluids 'supplied under a number of brand namesj, actually they all have just one and the Hitme basic ingredient: Monsanto's Aroelor" 12(50. df you want to know, Aroelor libit) is hexaehloruliiphen.vl!. And THIS is one of the world's best liquid insulations!
don't worry about "different kinds"
So, what are the two types? What's the difference? Simply tins: they have different pour [joints and the liny amount of "scavenger" ohemieal added to each is different. The I'yranol 1 l To [General Electric! type has ihe lower pour point; it will still pour at -IT0 below 1F.1 zero. Tin* Inerteen ITO i Westiughmise.' type will pour down to 26 below F., zero. These two types each contain a liny amount of a different additive; both additives are good and do their joo. However, the additive in I'yranol tvpe askarel can crystallize out a b.t at M" above T.) zero. It does no harm; the crystals disappear after a while when the transformer warms up.
tuber brand names, like t Tilurmaul . Allis Chalmers ; Xudaiuo! 'Wagner Electro ; Asbestol . Anu-rtran Corp. ; Saf-T-kuhl Kubluiari Electric' are either one type or the ether. Some manu facturers simply call their lluid by the common descriptive nameuskanl. I!ut, transformer manufacturers who supply askarel thuds have sound reasons lor favoring their own ivpe. So, it'- best in stay with your particular brand.
However, since basically askarel is askarel, there will be rto difference in the operation of your transformer if IN EMERGENCY you would interchange or even mix the two types!
Hut askarel is NOT oil c.unni. should mu. must not be mixed with ordinary transformer oil. For one reason: the m.-nle core materials used with mineral oil tilled units get gooey with askarel. For another reason out T, of Mi neral oil nixed into askarel 'clobbers'' its lire resistance. For another reason never mind1 Don't ni'.r or wh'ichait-jf nsi-inv/ anil mi.
"Askari-l" liquid insulation is a very eareiully-manuiartured, highly pure, chemically made thud. It noes not vary in compos.turn like the range of oils. AND . . . assurel is Imiru'r titan water. If water gets into askarel insulation, only a smidgeon ' 12A ppm dissolv es the rest;/oofs on fop.
Asktirt l is imr o/ the nmni Jirc-ri'mxtunt, i'Iii in irn'f)/-i nrrt, hi m-sMb/e /u/uills n-cr ilnchipul' You can be sure of this: askarel does not deteriorate when exposed to air, heat, hot metal; it ooes not break down over long use to form conducting or corrosive chemicals, it docs not sludge or oxidize. Askarel will remain pcrf-rtly stable year after year after year unless broken down by exposure to severe arcing the kind that could set an oil transformer atir--. The only real 'enemy1' of askarel is: contamination by water.
03h7900
TOWOLDMON0030413 WATER_PCB-00014882
NOW LET'S TALK
year to year operation!
One of the most brain-y electrical engineers in the business once said: "The best 'maintenance' for askarel transformers is KEEP 'EM DRY, and leave them alone!"
This business of "keep 'em dry," however, whether your trans former is EITHER an oil-type or an askarel type, is the watchword! Il takes some care. In fact, anything MECHANICALLY you can do to stop moist air breathing and condensation will be the best health insurance for your liquid tilled transformer. Here are some of tin* questions that come up when you want to "keep 'em dry."
Is your transformer a welded shell or a gasket top? (even the tightest gaskets can "breathe!")
Does your transformer run. stop: run, stop: run. stop? (This hot-to-cold temperature cycling makes the breathing faster and harder!)
Is air around it mostly cold and dry or hot and moist? (Wouldn't it be great for automobiles and transformers if there wasn't any such thing as condensation!)
When you have "breathing" and high humidity you can cut back on check-ups if you lit the transformer with a drying device tall transformer makers oiler these) or you can bleed dry nitrogen into the shell. Any mechanical steps you take to stop inside con densation will he double insurance on trouble-free operation.
Of course, if you are ordering a brand new transformer either oil or nakimd type you can "design out" most of the moistureentry points. Musically, you call for all-welded construction, in cluding fins, pipes, and instrument connections AND a recessed gasket for the hand holes.
(If you or your electrical equipment supplier would like more complete details on tips to keep innards dry, we can send you a copy of: "Design Details For Moisture Protection of Liquid In sulation Transformers.")
So you'll be happy to learn that preventing moisture contamina tion is the only major health insurance you need provide for your askarel insulation.
CHECKING THE CHECKPOINTS
Now you are well on your way to being an "expert." Since you know that keeping tabs on MOISTURE is the major checkpoint on your askarel transformer, let's ask:
How do you keep tabs on moisture?
You do this by a periodic test of the askarel's dielectric strength.
Do not bother to check -- or If you do -- do not be misled or dis turbed by relatively high power factor.,. or even drop in volume resistivity.
(If you want to know why. you can read the fine print on the following page.)
The DIELECTRIC STRENGTH of the askarel is your major clue to the ``health'' (i.e. dryness) of your askarel transformer. Besides taking a good look at a sample of your askarel -- dielectric strength iB the only "test" you need actually run!
Here's why: the dielectric strength of askarel is sensitive to moisture: nof senstfire to other ordinary contaminants (like metal dust, salts, dirt, etc.). The dielectric strength is also hurt by severe arcing, but you'll know that aremg is the culprit if the askarel has gotten noticeably black or has particles of sooty carbon floating in it. Unless you've had severe arcing (lightning, accidental overload, back surge, etc.), the dielectric strength is your "moisture indicator."
New askarel has a minimum dielectric strength of 35 KV at 25C.; a maximum moisture content of 30 ppm. If you check the dielectric strength periodically, find that it is rapidly decreasing this is your "clue" to moisture pick-up, arcing, or both. When the moisture content rises to 100-120 ppm (or over) -- the dielectric strength will drop to 20 KV or less. That's your clue!
INSPECT FOR WATER CONDENSATION IN THE SHELL, AND "REFINE" THE ASKAREL.
As the operator, you will have to judge how often you want to check up on your askarel insulation. Steadily running, well-sealed askarel transformers have run as long as 25 years on the initial charge of askarel -- and the dielectric strength still checked out at above 30 KV. HOWEVER, if the dielectric strength drifts down ward to 25-20 KV at 25"C, -- then it is time to "clean-up" the liquid insulation and to get rid of any water accumulation in the shell, too.
This askarel clean up is relatively simple; the askarel need NOT be discarded. BUT MOST IMPORTANT ... if the dielectric strength drops rapidly over a short period of time, this shows rapid pick-up of water (or arcing).
When you take your sample for check-up be sure to take it carefully (so it represents the surface) and handle the sample properly (so it doesn't pick up moisture in the sampling).
Olil'111
J
How to check test vour a %/
' ' -'(tv *' >
' "'*1 f~
You'll be able to "take the pulse" of your askarel insulation with the following five simple rapid tests, iThree are simply "inspcci urn
by-eye!" i You can do these check-ups yourself or have the tests run by a local transformer service shop.
1
COLOR 'by inspectioni
New assarel is a clear, faint-
yellow liquid. After long-term use, the color will gradually
intensify to brown. Any color change, suc h as taking on a
green, red or blue cast, indicates extraction. If you lind
a distinct changv ni rolur, the complete range of electrical
characteristics should be checked to learn if the exiracied
color is tin* tell-tale for contamination.
CLARITY i by inspection > New nskan-l is clear and should remain clear in service. Development of turbidity or cloudi
2 ness indicates contamination from water, insulation par ticles, metallic dust or dirt. Cloudiness or turbidity calls for a complete analysis. Tin* exception to this would be cloudiness in a cold sample of I'YHAS'Ol. I ',7". This tvpe askarel contains a scavenger additive wnich will '`come out" of solution when .'old .around ITF. and cause white turbidity and nerliaps show salt-like deposits on the trans former shell. If this is noticed, heat the asxarel sample to 150-200F. for several hours am; agitate. Cpon heating, the I'yranol's additive will redissolve, as it will in a warm transformer.
BLACK COLOR AND SMALL CARBON PARTICLES by in spection ) If the color of t lie sample is black, and (`specially
3 if suspended carbon particles can be seen, this shews that the askarel has arced and should be discarded. You can also deled exposure to strong arcing rlinniralhi, with indicator paper. Simply dip a piece of moist blue litmus paper into the askarel. If the blue litmus turns red, then* is excess acidity from arcing beyond the limit absorbed by the "scavenger" additive.
OJ5 790i
TOWOLDMON0030415 WATER_PCB-00014884
DIELECTRIC STRENGTH ihy ASTM 1)901. P8T7. The
(licli'ctric strungl h is i In- most important; and il is a simple
4 test to make. Tin- dielectric strength of new askarel is
;r> K \' at 2a minirmitn. 'Hus \ nine should not be allowed
to tall below
KY. Contaminants iwhieh may have
pronounced elTeet <>n the power factor and volume resisU'ily; nniiiilln i/n a,it linen- ask,net's ihelertrtr strength.
Heduced dieleetne strength almost always shows exposure
to strong arcing nr moisture coiu.uuinauon.
5
MOISTURE
The moisture content of new askarel is
:ii> parts per millioi: maximum. The moisture siitnrntnin level
is about 1 Jh ppm at ordinary temperatures. When the
moisture eotitent approaches Ida ppm isaturatinn level;,
the dieleetne strength goes down. The moisture content
oi aslurel should not he allowed to rise over 70 ppm; it
NOTE: ll viur surnple shows du-k-a KA' dielectr c strength. >ou n.'oi; not cheek tor moisture. However, if you do cheek moisture, use the Karl Fisher Method. \S I'M I >-l
IF ANY OF THESE FIVE CHECK-UPS APPEAR ABNORMAL, CON TACT YOUR TRANSFORMER MANUFACTURER FOR COMPLETE ANALYSIS. I'he.se simple 1 ests will show you tile condition of ymil askarel msnlatvm, but only nnhrerll;/ iVn eondbion of your transformer. They ran be rolled U|>nn when the sample is carefully taken .so as not to 'miss" water globules Moating on : lie sarlaee nr adhering i o I he shell in I ae air space ever t lie insiilation -. So, if y:>u have talien meidiameal preeaut ,ot.s against moisture entiy into your askarel 1 ransloiiners and can "Keep 'em dry!" these tests will be your assurance that, between cheeks, you can "Forget 'em."
he AST
GROOMING ASKAREL FOR RE-USE
If strong arcing has blackened askarel, throw it away; it costs less to replace arced insulation than to reclaim it. If there's been no arcing, but a low dielectric test shows moisture contamination, you'll find it is quite easy to refine the askarel back to good operating dielectric strength. Simply run the insulation through a dry. ab sorbent filter.
Most operators prefer a portable refining apparatus, such as a plate press, fitted with a dolly, (available from Sparkler, Mundelein. III.:; or the earthen cartridge filter type, available from Industrial Filter (lorp., Lebanon, Ind.i. Filter paper liners for the plate press are available from Carl Schleicher & Schucll Co., Keane, N'.H.
Any flexible hoses and gaskets on the refining equipment should be lined with or made of materials that will not be softened by contact with askarel fluid. (Silicone or Teflon materials are suitable).
If you use a filter press, before refining it is advisable to oven dry the filter paper at. 100C. for a half hour to remove all moisture. If the askarel to be refined contains excessive moisture, circulate it hot (55-60T.) through the filter fitted with the paper liners only first. Then, refit press with dry paper and load it with the absorbent earth.
The earth refining process is simple:
1. SPREAD DRY EARTH EVENLY OVER THE FILTER SURFACE.
Fine-mesh Attapulgus clay or Fullers earth, dried and activated by heating for 12 hours at 25CTC. immediately prior to use. is highly efficient. The amount of earth used should be 0.1 to 0.2 per cent by weight of the askarel (askarel weighs about 13 pounds per gallon).
To deposit the earth evenly, stir one-third of the earth with a small portion of askarel m a clean container. Pump the mixture through
2. PUMP THE HEA TED ASKAREL FROM TRANSFORMER THROUGH FIL TER.
Circulate askarel taken from near the top of the transformer, pass it hot (55-60' C.) through the filter and feed back through the bottom transformer outlet.
3. CONTINUE CIRCULATING THROUGH THE FILTER UNTIL ASKAREL IS CLEAR.
When the askarel is clear use the simple tests described earlier to check for restored dielectric strength.
4. CHECK THE TRANSFORMER AFTER REFINING.
After refining the askarel, the overall power factor and insulation resistance should closely approximate the values it would show with new askarel fluid.
If the overall power factor is more than 30-35 per cent (at 20C. and 60 cycles) it is considered FOOR and it is advisable to run a complete analysis of the entire insulation system.
TOWOLDMON0030416 WATER_PCB-00014885
POWER FACTOR & VOLUME RESISTIVITY
High power factor Htii low volume resistivity in transformer mineral uils are commonly regarded as "danger signals" that the oil has deteriorated arm broken down chemically.
This is NOT true of askurel liiiuid insulation.
New, unused nskurol shows these electrical values:
Power Factor:
0.0,r>-0.2';
m (it) cycles 20"G.
iiihou! 1-2.(P'; i" (it) cycles lOOT.i
Volume KcHiHlivity: 1(10-1 OHO x ID11 olim-cm .r lOlPC., nOOV., DC., ti.l" gap)
Psed askarel from SATISFACTORILY OPERATING TRANS FORMERS noruiully 'and frequently shows
Power Factor:
2(1 to SO'; (<HiO cycles. 10<1C.
Volume Resistivity: about 25 x Id11 olim-cm i 100C., 500 V., DO., 0.1" gap'
This relatively limit power factor and relatively low volume re activity of used askarel ARK 70 HE EXPECTED. Even ai these level*, the nskanTs dielectric strength is STILL in the 00-05 KV range.
The reason is simple: askarel, unlike "oil," is a relatively polar liquid. The volume resistivity is sensitive to traces of conductive
contuiimiarita. However, even in the presence of large amounts <>f contaminants, the volume icsistivily does not seem to fall below ]0 \ 10 : ohm -cm i. Vet the dielectric strength reimdns high, holllusc intrinsically askarel remains a non-conductor.
To ipiote from Insulation Magimne, Decemher 111(11
DIELECTRIC LOSS YARDSTICKS
by .1 11111 (' Hulls, Manager Insiilainm [)evele|iniei.t Si'i'tion, and Graham Lee Moses, Manager Services Kl.gr/teenirg, U'esduglKKisc Klertrrr Corfu, Fast l'ittsluirgli, l',.
"Dielectric loss is a good comparative ova.nation for seme charuclcristics of insulation. It may he used for comparing similar samples of the same materials. Il may not be used as ail ovrall evaluation for com paring different materials." <i.e "oils1' and aska-elsi
Power factor is nol an important criteria of askarel insulation efliciency IN A PROPERLY < '(INSTRUCTED TRANSFORM HR.
However if improper construction materials or unpredictable foreign conl.immunt.H enter the system nigh power factor mi the absence of moisture in the shell i ran indicate improper const ruction.
NOW . . . since you know that the DIELECTRIC STRENGTH
is the most important checkpoint, and that iexcept for arcing'
MOISTURE is the villain that saps dielectric strength
you
want to make sure that your SAMPLE truly represents vmir
askarel insulation.
TAKE YOUR SAMPLE AS CLOSE TO THE TOP OF THE LIQUID SURFACE AS POSSIBLE!
(Many large askarel transformers nave a huilt-ui sampling tube near the surface for convenient sam pling. If additional sampling tube connections are contrived on to valves for easier sampling, make the tubes of clean glass, stainless steei, aluminum or t m for rigid types; and s.licone ur Teflon tubing for flexible
types.1
Wafer //oiifs on askarel. if iherc is any water in vnur transformer, it may collect m little puddles ON TOP of the askarel. \ \ 1 L therefore, more water will probably he dissolved m the a-karcl near the lop, where it. contacts any collected condensation.
If you find low dielectric strength and high moisture m the ,i.-.kore , you will probably want to thoroughly dry out the viell ,md take some inetduimcid steps to keep it dry.
When you take your askarel sample for testing, take tpe Nnnc precautions (but no more' that you take when sampling mineral oil.
1 Select a dry day. Do not sample insulation on a warm, moist day when humidity exceeds 75%, and
2 Make sure that the aska'el is at least as warm as trie sur rounding air. (Cold liquids can condense moisture Irom humid air )
3 NEW containers lor fluid sample Your sample container should be a new and previously unused small mouth pint glass buttle fitted with a tiahelne screw cap fitted with an aluminum or tin bottle cap Imer Make sure that the new bottle does not stand around open to collect dust or moisture. Rinse the sample bottle and cap lining twe or three times with askarel from the transformer then fill it. When sample will be tested promptly, a clear glass bottle can be used. If sample is to be stored indefin itely, use an amber glass Dottle or wrap clear glass with aluminum foil.
Whenever a sample is to De shippec to Hie transformer manufacturer (or to Monsanto) for complete analysis, the container must be a 5 pint amber glass bottle, lor yo.jr convenience, various transformer manufacturers arid Monsanto will send you the sample bottle filled with new askarel. You simply empty out the new askarel and re fill bottle with your sample.
rel
Hut you might want these storage and handling "tips" to make you a complete transformer askarel expert.
STORE NEW ASKAREL IN A CLEAN DRY PLACE
Keep the 5, HO, or 55 gallon drums dry; turn them over on their sides to keep water off the drum head, ill can he sucked in by the drum "breathing.";
CLEAN UP SPILLAGE
Askarel can, if left standing, attack paint, rubber, or plasties. Absorb it from floors with sawdust, sweep, and then wipe dry. Use a rag wet with mineral spirits if you want :o make sure it's all cleaned away.
TAKE ORDINARY PERSONAL CARE
Transformer askarel has been made, handled and used lor over di) years without causing toxic or other ill effects. Askarel can be handled m the same manner as insulating mineral ml. As with mineral oil, there may be some people allergic to askarel, so pro longed skin contact should he avoided where possible.
When accidentally spilled or splashed on the skin, askarel does not present an acute hazard nor will it cause serious skin irritation. Simply wash it off with soap and water. If work clothes become impregnated with askarel, they should he rerruned and washed.
Eye contact may cause temporarily painful irritation but \() PERMANENT DAMAGE to the tissues or sight. Flush the eye with large amounts of water. A drop of castor oil may he put in the eye. As with all eye first-aid, refer to a physician who will treat the eye with an ointment.
Ordinary, infrequent exposure to askarel vapors will not cause any ill effects. However, prolonged exposure to strong vapors should he avoided. If hot thud is to be handled in a closed or confined area, provide ordinary exhaust ventilation. Harmful concentrations of askarel vapors are easily detectable by the smarting of the nose or eyes.
Should hot askarel (above 100C.) have to be handled in the open in a confined, unventilated area it is advisable to wear organic canister-type masks as supplied by Mine Safety Co., Pittsburgh. Pa.