Document 9O2VLB4vyvRzrZwvjZVNR3oR
210
Chapter 10
1945 Cuide
j-------1-----------1-------- 1----------1--------1----------1------- 1---------- 1------- 1---------- 1-------- 1----------1--------1---------- i------- 1---------- 1-------r---------- 1--------1--i--
O2
4
6 8 10 12 14 16 18 20.
GROSS OUTPUT - HUNDRED FEET STEAM RADIATION
t t i | | T-r t ':r i--iiii--i--i--i--i--i--r--i--i--i--i "i t i i i 1 i * * 1
0;
5
10 15 20 25 30
GROSS OUTPUT-HUNDRED FEET WATER RADIATION
. Fig. 19. Oil Fuel Burning Rate Chart3
This chart is based upon No. 3 oil having a heat content of 143.400 Btu per gallon. If other grades of oil are used multiply the value obtained from this chart by the following factors: No. 1 oil (139,000 Btu per gallon) 1.032; No. 2 oil (141,000 Btu per gallon) 1.017; No. 4 oil (144.500 Btu per gallon) 0.992; No. 5 oil (146,000 Btu per gallon) 0.982; and No. 6 oil (150,000 Btu per gallon) 0.956.
Au tomatic Fuel Burning Equipment
211
REFERENCES
Performance Expectancy of Domestic Underfeed Stokers for Anthracite, by Allen J. Johnson (Transactions, A.I.M.E., Coal Division, Vol.- 119, 1936).
The Relation of the Size of Bituminous Coals to Their Performance on Small Under
feed Stokers--Burning Tests on Four Typical Coals, by R. A. Sherman, E. R. Kaiser and
H. R. Limbacher, Technical Report No. 1, Bituminous Coal Research, Inc. (July, 1937)
Part II.
.. '
Oil Fuels and Burners, by James A. Moyer, McGraw-Hill. Handbook of Oil Burning, by Harry F. Tapp.
'"
A Study of the Oil Burner as Applied to Domestic Heating, by Arthur H. Senner (Technical Bulletin 109, V. S. Department of Agriculture).
Progress in Domestic Oil Heating, by Rene J. Bender (Mechanical Engineering,
October, 1942).
.
A.S.H.V.E. Research Report No. 907--Study of Performance Characteristics of
Oil Burners and Low Pressure Heating Boilers, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 37, 1931, p. 517).
' A.S.H.V.E. Research Report No. 925--A Study of Intermittent Operation of Oil Burners, by L. E. Seeley and J. H. Powers (AlS.H.V.E. Transactions, Vol. 38, 1932. p. 317).
Air Supply and Its Effect on Performance of Oil Burners and Heating Boilers, by L. E. Seeley, J. H. Powers and E. J. Tavanlar (A.S.H.V.E. Transactions, Vol. 39,1933, p. 75).
Study of Fuel Burning Rates .and Power Requirements of Oil Burners in Relation to
Excess Air, by L. E. Seeley and E. J. Tavanlar (A.S.H.V.E, Transactions, Vol. 40
1934, p. 319).
.
Oil Burning in Residences, by D. W. Nelson (A.S.H.V.E. Transactions, Vol. 41 1935, p.355).
A Study of Oil-Fired Heating Boilers, by R. C. Cross and W. R. Lyman (Heating and Ventilating, October, 1931);
Combustion, American Gas Association. Comfort Heating, American Gas Association.
,
Approval Requirements of. Central House Heating Gas Appliances, American standards Association.
A Method for Determining Fuel Burning Rates in Heating Boilers Fired by Auto matic Devices, by R. C. Cross (Heating and Ventilating, January,. 1932).
.Heat Losses and Efficiencies of Fuels in Residential Heating, by R. A. Sherman and K. C. Cross (A.S.H.V.E. Transactions, Vol. 43, 1937, p. 185).
4 6 6 .10 12 >4 GROSS OUTPUT - HUNDRED FEET STEAM RADIATION
10 15 20 25 GROSS OUTPUT * HUNDRED FEET WATER RADIATION
Fig. 20. Gas Fuel Burning Rate Chart