November 1, 1991 Dow U.S.A The Dow Chemical Comoany PO Box 400 Plaouemine, Louisiana 70765-0400 Shirley Shaw 5301 cc: Carl Mercer, 5301 Art Royals, 3502W REACTIVE CHEMICALS REVIEW - OCTOBER 28, 1991 Project: Glycol 2 EO Scrubber Project rep: Shirley Shaw The scope of this project includes installing a scrubber system to remove the vents from the EO storage tanks during de-pressurization which will occur during offloading of tank cars during shutdowns. The scrubber system will consists of a packed tower, reaction tanks, pumping and a cooling system. The scrubbing solution will be 5% sulfuric acid/30% glycol/water. Concerns: The main reactive chemical concern is the catastrophe which would probably result if acid scrubbing solution would back-up into the EO storage tanks. Since this project is in the initial engineering stage perhaps a HA20P study of the line between the DH tank and T-202 would be appropriate. The potential for this scenario to occur should be completely eliminated. Another Reactive Chemicals review should be conducted towards the end of Phase 3 Engineering. Gerald Wagener, Chairman Reactive Chemicals Committee DO A 135799 gonftdfnttal