Document 99qgE3kdkL3o2nmKe6wQKDyBD
TRANSMITTED VIA EMAIL
February 14, 2024
Mr. Rodney Talcott WWTP Superintendent City of Espanola Wastewater Treatment Plant 405 N. Paseo de Onate Espanola, New Mexico 87532 ratalcott@espanolanm.gov
Re: Administrative Order; Docket Number: CWA-06-2024-1742 NPDES Permit Number: NM0029351
Dear Mr. Talcott:
Enclosed is an Administrative Order (AO) issued to the City of Espanola Wastewater Treatment Plant (WWTP) for violations of the Clean Water Act (CWA) (33 U.S.C. 1251 et seq.). The violations were identified during a review of the permit file and inspection report for the WWTP. The violations alleged are for effluent limitation exceedances, failure to ensure the proper operation and maintenance of the facilities, improper record keeping, laboratory insufficiencies, and other violations as indicated in the AO.
This AO does not assess a monetary penalty; however, it does require compliance with applicable federal regulations. The first compliance deadline is within thirty days of receipt of the AO. The Environmental Protection Agency Region 6 is committed to ensuring compliance with the requirements of the National Pollutant Discharge Elimination System (NPDES) program and my staff will assist you in any way possible. Please reference AO Docket Number CWA-06-2024-1742 and NPDES Permit Number NM0029351 on your response.
If you have any questions, please contact Ms. Rachel Matthews, of my staff, at (214) 665-8589 or at matthews.rachel@epa.gov.
Sincerely,
Cheryl T. Seager, Director Enforcement and Compliance Assurance Division
Enclosure
e.c. Ms. Shelly Lemon NMED Water Bureau Chief shelly.lemon@env.nm.gov
Ms. Susan LucasKamat NMED Surface Water Quality Bureau susan.lucasKamat@env.nm.gov
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY Region 6
FINDINGS OF VIOLATION AND COMPLIANCE ORDER Docket Number: CWA-06-2024-1742; Permit Number: NM0029351
STATUTORY AUTHORITY
The following findings are made, and Order issued, under the authority vested in the Administrator of the United States Environmental Protection Agency (EPA), by Section 309(a) of the Clean Water Act (herein "the Act"), 33 U.S.C. 1319(a). The Administrator of EPA has delegated the authority to issue this Order to the Regional Administrator of EPA Region 6, who has further delegated this authority to the Director of the Enforcement and Compliance Division.
FINDINGS
1. The City of Espanola Wastewater Treatment Plant (Respondent) is a "person," as that term is defined at Section 502(5) of the Act, 33 U.S.C. 1362(5), and 40 C.F.R. 122.2.
2. At all times relevant to this Order (all relevant times), the Respondent was authorized to discharge from a wastewater treatment plant located at 308 Lower San Pedro Road, Espanola, in Rio Arriba County, New Mexico (facility), and was, therefore, an "owner or operator" within the meaning of 40 C.F.R. 122.2.
3. At all relevant times, the facility acted as a "point source" of a "discharge" of "pollutants" with its wastewater discharging to the receiving waters named the Rio Grande, within the exterior boundaries of the Pueblo of Santa Clara and downstream from that portion of the river also designated as Segment No. 20.6.4.114 of the Rio Grande, which is considered a "water of the United States" within the meaning of Section 502 of the Act, 33 U.S.C. 1362, and 40 C.F.R. 122.2.
4. Because Respondent owned or operated a facility that is a point source of discharges of pollutants to waters of the U.S., Respondent and the facility were subject to the Act and the National Pollutant Discharge Elimination System (NPDES) program.
5. Under Section 301 of the Act, 33 U.S.C. 1311, it is unlawful for any person to discharge any pollutant from a point source to waters of the United States, except with the authorization of, and in compliance with, an NPDES permit issued pursuant to Section 402 of the Act, 33 U.S.C. 1342.
6. Section 402(a) of the Act, 33 U.S.C. 1342(a), provides that the Administrator of EPA may issue permits under the NPDES program for the discharge of pollutants from point sources to waters of the United States. Any such discharge is subject to the specific terms and conditions prescribed in the applicable permit.
7. Respondent applied for and was issued NPDES Permit No. NM0029351 (permit) under Section 402 of the Act, 33 U.S.C. 1342. The previous permit became effective on November 1, 2017, expired on October 1, 2022, but was administratively continued until the current permit became effective on March 1, 2023. At all relevant times, Respondent was authorized to discharge pollutants from the facility to waters of the United States only in compliance with the specific terms and conditions of the permit.
8. Part I.A. of the permit places certain limitations on the quality and quantity of effluent discharged by Respondent. The relevant discharge limitations are specified in Attachment A, which is incorporated herein by reference.
9. The permit also includes "Monitoring and Reporting Requirements" that require Respondent to sample and test its effluent and monitor compliance with permit conditions according to specific procedures, in order to determine the facility's compliance or noncompliance with the permit and applicable regulations.
10. The permit requires Respondent to file certified Discharge Monitoring Reports (DMRs) of the results of monitoring. DMRs filed by Respondent show discharges of pollutants that exceed the effluent limitations as specified in Attachment B, which is incorporated herein by reference.
11. Each instance in which Respondent discharged pollutants to waters of the United States in amounts exceeding the effluent limitations contained in the permit was a violation of the permit.
12. Pursuant to Part III.A of the permit, Respondent is required to furnish, within a reasonable time, any information to determine compliance with the permit.
CWA-06-2024-1742 Page | 2
13. Pursuant to Part III.B of the permit, Respondent is prohibited from allowing a bypass except under specific circumstances.
14. Pursuant to Part III.B of the permit, Respondent is required to at all times properly operate and maintain all facilities and systems of treatment and control (and related appurtenances) which are installed or used by permittee as efficiently as possible and in a manner which will minimize upsets and discharges of excessive pollutants and will achieve compliance with the conditions of this permit. Proper operation and maintenance also includes adequate laboratory controls and appropriate quality assurance procedures.
15. Pursuant to Part III.C of the permit, Respondent is required to conduct monitoring according to test procedures approved under 40 CFR Part 136, unless other test procedures have been specified or approved.
16. Pursuant to Part III.C of the permit, Respondent is required to calibrate and perform maintenance procedures on all monitoring and analytical instruments at intervals frequent enough to ensure accuracy of measurements and shall maintain appropriate records of such activities.
17. Pursuant to Part III.C of the permit, Respondent is required to have an adequate analytical quality control program, including the analyses of sufficient standards, spikes, and duplicate samples to ensure the accuracy of all required analytical results and shall be maintained by the permittee or designated commercial laboratory.
18. Pursuant to Part III.C of the permit, Respondent is required to have appropriate flow measurement devices and methods to ensure the accuracy and reliability of measurements of the volume of monitored discharges.
19. Pursuant to Part III.C of the permit, Respondent is required to retain records of all monitoring information, including all calibration and maintenance records and all original strip chart recordings for continuous monitoring instrumentation, copies of all reports required by this permit, and records of all data used to complete the application for this permit, for a period of at elast three (3) years from the date of the sample, measurement, report, or application.
20. On July 13, 2023 and August 16, 2023, a combined inspection of the facility's wastewater treatment plant and laboratory were conducted by EPA inspectors, as specified in Attachment C, which is incorporated herein by reference.
21. As a result of the inspection, it was found that Part III A, B, and C of the permit were violated in that:
a. Respondent failed to conduct sampling as required, b. Respondent failed to calibrate laboratory devices, c. Respondent failed to maintain adequate monitoring
records and other records, d. Respondent failed to provide requested records, e. Respondent failed to properly operate and maintain
the wastewater treatment plant (and related appurtenances), f. Respondent failed to provide adequate operating staff duly qualified to carry out operation, maintenance, and testing functions, g. Respondent allowed prohibited bypasses, h. Respondent failed to conduct monitoring according to approved test procedures, i. Respondent failed to maintain an adequate analytical quality control program, j. Respondent failed to maintain the Parshall Flume and the secondary ultrasonic flow meter,
22. Each violation of the conditions of this permit or regulations described above is a violation of Section 301 of the Act, 33 U.S.C. 1311.
SECTION 309(a)(3) COMPLIANCE ORDER
Based on the foregoing Findings and pursuant to the authority of Section 309(a)(3) of the Act, EPA hereby orders the Respondent to take the following actions:
A. Immediately take all measures as necessary to comply with permit conditions.
B. Within thirty (30) days of the effective date of this Order, Respondent shall either:
i. Provide written certification to EPA Region 6 that the violations cited herein have been corrected, how they were corrected, and that the facility is in compliance with the requirements of the permit, or
ii. Provide a list of all noncompliance related deficiencies to EPA Region 6, and a schedule to correct each deficiency, for review and approval.
CWA-06-2024-1742 Page | 3
C. Any approved compliance schedule submitted under B above will be incorporated and re-issued in a future administrative order.
D. If Respondent would like to arrange a meeting with EPA to discuss the allegations in Section 309 (a)(3) Compliance Order, Respondent should contact EPA within thirty (30) days of the effective date of this Order. The meeting will be held at the Region 6 offices, 1201 Elm St., Dallas, Texas, or through a virtual platform, as appropriate, and the Respondent can provide any information it believes is relevant to this Order. Respondent shall submit to EPA all information or materials it considers relevant to EPA at least ten (10) days prior to the meeting.
E. To arrange a meeting, or to ask questions or comment on this matter, please contact Rachel Matthews, of my staff, at (214) 665-8589.
F. All information, and/or correspondence, shall be electronically submitted to:
Ms. Nancy Williams williams.nancy@epa.gov
and
Ms. Rachel Matthews matthew.Rachel@epa.gov
GENERAL PROVISIONS
Respondent may seek federal judicial review of this Order pursuant to Chapter 7 of the Administrative Procedure Act, 5 U.S.C. 701-706.
Issuance of this Section 309(a)(3) Compliance Order shall not be deemed an election by EPA to waive any administrative, judicial, civil or criminal action to seek penalties, fines or other relief under the Act for the violations cited herein, or other violations that become known to EPA. EPA reserves the right to seek any remedy available under the law that it deems appropriate.
Failure to comply with this Section 309(a)(3) Compliance Order or the Act may result in further administrative action, or a civil judicial action initiated by the United States Department of Justice.
This Order does not constitute a waiver or modification of the terms or conditions of Respondent's NPDES permit, which remain in full force and effect. Compliance with the terms and conditions of this Order does not relieve Respondent of its obligation to comply with any applicable federal, state, or local law or regulation.
The effective date of this Order is the date it is received by the Respondent.
Date
Cheryl T. Seager, Director Enforcement and Compliance Assurance Division
Attachment A Administrative Order, Docket Number: CWA-06-2024-1742
NPDES PERMIT No. NM0029351
Page 1 of PART I
PART I - REQUIREMENTS FOR NPDES PERMITS
SECTION A. LIMITATIONS AND MONITORING REQUIREMENTS
1. FINAL Effluent Limits - 2.0 MGD Design Flow
During the period beginning the effective date of the permit and lasting through the expiration date of the permit (unless otherwise noted), the permittee is authorized to discharge treated municipal wastewater from Outfall 001to the Rio Grande within the exterior boundaries of the Pueblo of Santa Clara reservation. Such discharges shall be limited and monitored by the permittee as specified below:
POLLUTANT pH
MINIMUM 6.6 Standard Units
MAXIMUM 8.8 Standard Units
MEASUREMENT FREQUENCY Daily
SAMPLE TYPE Grab
POLLUTANT
30-DAY AVG
Flow
Carbonaceous Biochemical Oxygen Demand, 5-day (CBOD5)
CBOD5 Percent Removal (minimum) Total Suspended Solids (TSS)
TSS Percent Removal, (minimum) E. Coli Bacteria
Total Residual Chlorine
Total Ammonia
Dissolved Oxygen (minimum)
Report MGD
417 lbs/day 85% (*2) 500 lbs/day 85% (*2)
N/A
N/A
36.7 lbs/day
N/A
DAILY MAX
Report MGD N/A
--N/A
--N/A
N/A
N/A
N/A
7-DAY AVG
Report MGD 667 lbs/day
--751 lbs/day
--N/A
N/A
N/A
N/A
30-DAY AVG (*1) ***
25 mg/l
--30 mg/l
--126 (*3) cfu/100 ml
N/A
2.2 mg/l
2.0 mg/l minimum
DAILY MAX (*1) ***
N/A
--N/A
--235 (*3) cfu/100 ml 3 ug/l (*4)
N/A
N/A
7-DAY AVG (*1) ***
MEASUREMENT SAMPLE TYPE FREQUENCY
Continuous Totalizing Meter
40 mg/l
--45 mg/l
--N/A
Once/Week
Once/Month Once/Week
Once/Month Once/Week
6-Hour Composite Calculation (*2)
6-Hour Composite Calculation (*2)
Grab
N/A
Daily
Instantaneous
Grab (*4)
N/A
Once/Week
6-Hour
Composite
N/A
Once/Week
Grab
NPDES PERMIT No. NM0029351
WHOLE EFFLUENT TOXICITY TESTING (48-Hr Static Renewal) (*5) Daphnia pulex Pimephales promelas
NOEC
Report Report
MEASUREMENT FREQUENCY (*7)
Once/3 months Once/3 months
Page 2 of PART I
SAMPLE TYPE
24-Hr Composite 24-Hr Composite
EFFLUENT CHARACTERISTICS Expanded Effluent Testing (*6)
DISCHARGE LIMITATIONS Report
MEASUREMENT FREQUENCY At least 3 samples within 4.5 years prior to the date
of the permit application (*6)
SAMPLE TYPE 24-Hr Composite
Footnotes:
*1
See Appendix A of Part II of the permit for minimum quantification limits.
*2
Percent removal is calculated using the following equation: (average monthly influent concentration - average monthly effluent concentration) average
influent concentration.
*3
Colony forming units (cfu) per 100 ml.
*4
Regulations at 40 CFR Part 136 define "instantaneous grab" as analyzed within 15 minutes of collection. The effluent limitation for TRC is the instantaneous
maximum and cannot be averaged for reporting purposes. Sampling and reporting is required when chlorine is used for either bacteria control and/or when
chlorine is used to treat filamentous algae and/or used to disinfect process treatment equipment at the facility.
*5
Monitoring and reporting requirements begin on the effective date of this permit. See PART II, Whole Effluent Toxicity testing requirements for additional
WET monitoring and reporting conditions.
*6
See NPDES Permit Application Form 2A; Tables A, B, and C for the list of pollutants to include in this testing. Samples are to be taken on the same day as the
WET test event.
*7
A monitoring frequency reduction option is available, see Part II, Whole Effluent Toxicity testing requirements.
Attachment B Administrative Order, Docket Number: CWA-06-2024-1742
City of Espanola WWTP - NPDES Permit # NM0029351
Monitoring Period Parameter End Date
DMR Value
11/30/2023 9/30/2022 9/30/2022
9/30/2022
9/30/2022 9/30/2022 9/30/2022
E. coli Solids, total suspended E. coli Solids, suspended percent removal Solids, total suspended Solids, total suspended Solids, total suspended
272 612.54
816
-4.66
321 2666.43
74.66
Effluent Violations
Sample Type
Limit
Grab
235
6 Hour Composite
500
Grab
235
Calculated
85
6 Hour Composite
45
6 Hour Composite
751
6 Hour Composite
30
Statistical Base Short Description
DAILY MX 30DA AVG DAILY MX
MO AV MN
Limit Unit
Colony Forming Units per 100ml Pounds per Day Colony Forming Units per 100ml
Percent
% Exceedance
16 23 247
598
7 DA AVG 7 DA AVG 30DA AVG
Milligrams per Liter
613
Pounds per Day
255
Milligrams per Liter
149
Attachment C Administrative Order, Docket Number: CWA-06-2024-1742
Region 6 - Enforcement & Compliance Assurance Division
INSPECTION REPORT
Inspection Date(s): Media Program: Regulatory Program(s)
07/13/2023 and 08/16/2023 Water CWA - NPDES
Company Name: Facility Name: Facility Physical Location:
(city, state, zip code) Mailing address:
(city, state, zip code) County/Parish: Facility Phone Number Facility Contact:
Espanola, City of
Espanola Wastewater Treatment Plant
308 Lower San Pedro Road
Espanola, New Mexico 87532
405 N. Paseo de Onate
Espanola, New Mexico 87532
Rio Arriba
505-747-6186
Rodney Talcott
WWTP Superintendent
ratalcott@espanolanm.gov
FRS Number: Identification/Permit Number: Media Identifier Number: NAICS: SIC:
110039938583 NM0029351
221320 4952
Personnel participating in inspection:
Name
Affiliation/mailcode
Amy Andrews, P.E.
USEPA/6EN-WM
Magda Vargas
USEPA/6EN-WS
Jason Martinez
NMED/SWQB
Rodney Talcot
City of Espanola
Maria Mares
City of Espanola
Title Environmental Engineer Laboratory Inspector Environmental Specialist WWTP Superintendent Operator
EPA Lead Inspector
Signature/Date
Amy Andrews
Date
Supervisor
Signature/Date
Roberto Bernier
Date
6ENFORM-020-R8.2 (02/12/2020)
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Section I - INTRODUCTION
PURPOSE OF THE INSPECTION
Environmental Protection Agency (EPA) Region 6 inspector, Amy Andrews, and New Mexico Environment Department (NMED) inspector, Jason Martinez, arrived at the City of Espaola Wastewater Treatment Plant (WWTP) at 10:00 AM on July 13, 2023, for an unannounced inspection. We met with Rodney Talcott, the WWTP Superintendent for the Opening Conference. I presented my credentials to Mr. Talcott and informed him that this was an EPA inspection to determine compliance with the facility's National Pollutant Discharge Elimination System (NPDES) permit and the Clean Water Act (CWA). The inspection was conducted under the authority of the NPDES permit program, in accordance with the Federal CWA. The inspection was continued remotely using Microsoft Teams on August 16, 2023, for an in-depth laboratory review with EPA Region 6 inspectors, Magda Vargas, and Amy Andrews. This report is based on information supplied by City of Espaola representatives (the permittee), observations made by the EPA inspectors, and records and reports maintained by the permittee and the EPA.
FACILITY DESCRIPTION
The Espaola WWTP is classified as a major industrial discharger under the CWA, Section 402, of the NPDES permit program and is authorized to discharge up to 2.0 million gallons per day (MGD) based on design flow, with an actual average discharge around 0.9 MGD. The population served is approximately 10,500 residents according to 2020 United States Census. Discharge is to receiving waters of the Rio Grande River, which is within the boundaries of the Pueblo of Santa Fe reservation in waterbody segment 20.6.4.114 (NMAC, State of New Mexico Standards for Interstate and Intrastate Surface Waters) of the Rio Grande Basin. This segment includes the designated uses of irrigation, livestock watering, wildlife habitat, marginal coldwater aquatic life, primary contact and warmwater aquatic life, and public water supply.
The Espanola WWTP is an extended-aeration serpentine, activated sludge plant. Influent wastewater is brought into the treatment plant from seven (7) lift stations via two separate influent pipes at the entrance works, passing through mechanical bar screens with a 3/8-inch opening and an aerated grit tank where the grit slurry is sent to a cyclone for grit removal. Wastewater from the aerated grit tank is sent via influent lift pumps to a splitter box which has the influent Parshall Flume flow meter with ultrasonic secondary flow meter. The splitter box previously would have sent the wastewater to one of two separate treatment basins and associated clarifiers. One set is the original aeration basin/clarifier designated as north/south and the second set is the newer systems designated east/west system. Facility personnel stated that the north/south (original) basins are no longer being used and are currently empty.
Treated effluent flow from both basin systems would combine and then be sent to the ultraviolet (UV) bacteria control building. The UV system is a Trojan UV3000PTP with four banks of 32 UV bulbs each. The flow is then metered through the effluent Parshall Flume with an ultrasonic secondary flow meter and discharged through Outfall 001 to the Rio Grande.
2
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
The clarifiers introduce the return activated sludge (RAS) to the front of each aeration basin where it combines with the flow from the primary clarifiers. Waste activated sludge (WAS) and scum are removed and sent to the thickening centrifuges. Sludge is extracted from and sent to thickening/ dewatering centrifuges and then to the digester. Combined digested sludge systems is sent to the drying beds. Facility personnel stated that they are interested in certifying their biosolids for Class A application and reuse, however they do not have the procedures and laboratory testing processes set up to do so. Biosolids were previously sent to the Cerro Colorado Landfill in Albuquerque, but now are being held indefinitely at the WWTP in anticipation of the Class A certification.
The facility's laboratory is not accredited under national or private programs. The laboratory performs sample analyses of the following parameters for compliance with their respective NPDES permit: Dissolved Oxygen (DO), E. coli, pH, 5-Day Carbonaceous Biochemical Oxygen Demand (5-Day CBOD), Chlorine Residual (Cl2), and Total Suspended Solids (TSS). The laboratory performs additional sample analyses once a month of the following parameter for the Pojoaque Terrace Wastewater Treatment Plant for compliance with NPDES permit number NM0028436: E. coli.
On the day of the in-person inspection, the facility had three certified operators licensed by the New Mexico Water Quality Control Commission (NMWQCC). The WWTP Superintendent holds a Wastewater Level 4 (WW4) certification and has responsibility for running the entire plant, as well as oversight of the laboratory. The second certified Operator has a Wastewater Level 3 (WW3) certification and does not perform any laboratory analysis. The third certified Operator has a Wastewater Level 1 (WW1) certification and is the primary laboratory technician. There were three (3) additional uncertified operators and three (3) summer interns who also perform operations tasks at the plant and assist with sample collection and laboratory analysis. All of the uncertified operators had initiated employment with the facility within the last year. The interns were scheduled to stop working at the plant in midAugust. In accordance with the Environmental Protection Wastewater and Water Supply Facilities Utility Operator Certification Regulations at 20.7.4.13 NMAC, the Espanola WWTP is required to have a WW4 on-duty for plant operations at all times. In order to perform wastewater analysis for regulatory compliance a Wastewater Laboratory Technician Level 1 (WWLT1) is required for analyses involving colorimetry and commercially prepared reagents, including but not limited to Dissolved Oxygen (DO) and pH by probe, and commercially available test kits. A Wastewater Laboratory Technician Level 2 (WWLT2) is required for analyses using specific ion electrodes, titration, gravimetry, microbiology, media and standards preparation, including Biochemical Oxygen Demand (BOD), fecal coliform, E.coli, residuals (TSS), and Total Residual Chlorine (TRC) by titration. An operator holding a WW1 certification is only certified to perform TRC by the N-diethyl-p-phenylene-diamine (DPD) method, pH, Temperature and DO by probe. An operator holding a WW2 certification is certified to perform any activity which requires a WWLT1 certification. An operator holding a WW3 certification is certified to perform any activity WWLT2 certification. An operator holding a WW4 certification is certified to perform any activity which requires a WWLT2 certification.
3
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Section II - OBSERVATIONS
PLANT OPERATIONS OBSERVATIONS
At the opening meeting introductions were made and the inspection objectives were discussed. I provided a document request list of documents and information to be reviewed as part of the inspection. Facility personnel provided a description of the operational processes of the facility and described operational challenges that had been encountered recently.
After the opening meeting, we toured the WWTP. Observations made during the tour included the following:
1. The grit removal system has been down for more than a year, allowing grit to pass into the treatment basin. During the inspection grit was floating in the anoxic zone of the treatment basins, see Appendix 1, Photo 1. The grit is likely causing significant equipment damage to aeration nozzles, pumps, piping, sludge thickening centrifuges, as well as to treatment basin and digester basin walls. The reduced oxygen circulation in the treatment basins also likely compromises the biological treatment efficiency, which reduces the efficiency of the entire plant treatment process.
2. The north/south (original) basins which are no longer being used are currently empty except that they were never cleaned out and are still exposed to rainwater. Facility personnel are not certain where the drains for this basin are located.
3. Denitrification is occurring in the clarifiers, causing floating solids that have the potential to go over the clarifier weirs. Grit is present with the floating solids, and clarifier weirs are not level, see Appendix 1, Photo 2.
4. The three plant centrifuges cost around $100,000 per year to run, and one of them is currently non-operational. Facility personnel would like to replace all centrifuges with a fan press at a onetime cost of $750,000 and would like to also remove the digester and associated blowers.
5. The water reuse system is currently running on a temporary effluent pump, which is very inefficient. Facility personnel are waiting on the permanent pumps which have been delayed due to supply chain issues. At some point during the in-person inspection, the reuse pump went down, which caused the sprayers on the clarifiers to shut off.
6. The effluent Parshall Flume had algae buildup on the bottom, see Appendix 1, Photo 3. All flow meters were last calibrated on March 25, 2022. Facility personnel stated that they verify the calibration of the flow meter daily, but they do not keep records of the verification. After the inspection, facility personnel stated verbally that the flow meters had been calibrated.
7. Due to the outfall being located within the boundaries of the Pueblo of Santa Fe reservation, the outfall was not visited during this inspection. Facility personnel stated that approximately two years ago, a large rainfall caused massive flooding at the river which clogged the end of the outfall pipe. This resulted in effluent backing up in the pipe and flooding the UV building. Facility personnel at the time punched a hole in the top of outfall pipe to allow the water to flow out to the river. The clogged outfall pipe has not been fixed. On the day of the in-person inspection, a sump pump was present in the UV building, plugged in, and plumbed such that pumped water
4
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
would go into the UV trough after the UV disinfection, see Appendix 1, Photo 4. Facility personnel stated that this sump pump had been installed during the flooding event.
LABORATORY OBSERVATIONS
During the review of laboratory documents and the Microsoft Teams Laboratory Review of the facility, the following observations were made.
1. Standard Operating Procedures (SOPs) were not properly maintained, as detailed below.
a. The 5-Day CBOD SOP ambiguously references the entire Standard Methods for the Examination of Water and Wastewater (SM) 5210 Biochemical Oxygen Demand (BOD) section and does not adequately reference the individual method used. The reference does not clearly state the part number and sub-part letter of the individual method used. The method used for analysis most closely resembles SM 5210 B. 5-Day BOD Test method, therefore this method will be used for comparison.
b. The E. coli SOP does not reference an approved EPA method. The method used for analysis most closely resembles SM 9223 Enzyme Substrate Coliform Test method and Colilert media (not Colilert-18), therefore this method will be used for comparison.
c. The pH SOP ambiguously references SM 4500 - H+ B. pH Value Electrometric Method. The reference does not clearly state the part number and sub-part letter of the individual method used, nor is it clearly defined that this reference is used for the pH analysis specifically.
d. The TSS SOP ambiguously references the entire SM 2540 Solids section and does not adequately reference the individual method used. The references do not clearly state the part number and sub-part letter of the individual method used, nor is it clearly defined whether the references are used for the TSS analysis specifically. The method used for analysis most closely resembles SM 2540 D. Total Suspended Solids Dried at 103-105C method, therefore this method will be used for comparison.
e. The DO SOP does not reference an approved EPA method. The method used for analysis most closely resembles SM 4500-O G. Membrane Filtration Method, therefore this method will be used for comparison.
i. The method as written does not cover the analysis of water samples using the inline probe as indicated on the DO bench sheets, and the method observed. Rather it appears to cover the calibration of and taking measurements for the analysis of 5Day CBOD samples.
f. There was no SOP provided for the analysis of Cl2. Based off the observed method the analysis most closely resembles the Orion Research Instruction Manual, Residual Chlorine Electrode Model 97-70. 1977 (Orion) method, therefore this method will be used for comparison. As the bench sheets do not directly indicate whether the instrument reads in mV or is equipped with a direct concentration readout, it is most likely that a direct concentration readout is used based on the "Effluent Conc." Column on the bench sheet. Based on the results observed on the bench sheets, it appears the sub method for 0.2 to 20 ppm is used.
5
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
i. The observed method greatly resembles the SM 4500-Cl I. Iodometric Electrode Technique method, which is not an EPA approved method. However, Orion reagents are being used, therefore, for the purposes of this inspection the Orion method will be used for comparison.
2. Several SOPs provided by the facility had inconsistencies with the methods observed, as detailed below.
a. The 5-Day CBOD SOP does not specify the collection time or day of samples in relation to the time and day of analysis, when the pH of the samples is adjusted, or sample storage requirements.
b. The E. coli SOP does not specify the Colilert media used in analysis.
c. The TSS SOP appears to detail the method twice, the first using 10mL of sample with the potential to not use a filter, and the second using either 50mL of influent or 1000mL of effluent. The second method using 50 or 1000mL was the only method observed. The SOP also does not mention rinsing the graduated cylinders used in sample measurement nor the filter with water three (3) times after the entire sample is poured over the filter, as observed. Additionally, the SOP does not detail filter preparation before sample preparation.
3. The SOPs provided by the facility and the methods observed for sample analysis had several inconsistencies with EPA approved methods, as detailed below.
a. The 5-Day CBOD observed method and SOP did not include or otherwise mention limiting factors for data qualification such as: sample temperature at time of preparation and analysis, time of analysis after sample preparation, and minimum DO residual and depletion factors.
i. Per SM 5210 B. 5-Day BOD Test method, sample temperature must be at 203C at the time of sample preparation and analysis, sample analysis must be within 30 minutes of sample preparation, and DO readings must have a minimum residual of 1.0mg/L and minimum depletion of 2.0mg/L otherwise the data is invalid.
b. The E. coli observed method and SOP did not include or otherwise mention the limited holding time of samples after the addition of the Colilert medium. Additionally, both the observed method and SOP instruct the analyst to shake the sample after addition of Colilert media for 1-2 minutes.
i. Per SM 9223 Enzyme Substrate Coliform Test method for Colilert, incubation must begin within 30 minutes of the addition of Colilert media. The sample must be shaken after the addition of Colilert media for seven (7) seconds or back and forth in a one-foot space 25 times.
c. The pH observed method and SOP did not include or otherwise mention the 15-minute holding time of samples. Additionally, temperature dependency of pH analysis and the need to adjust calibration and readings for temperature if the instrument does not automatically do so is not included or otherwise mentioned. The pH probe used in analysis does not contain a thermometer, and so a temperature probe must be used in conjunction to the pH probe during calibration and analysis to automatically adjust for temperature.
6
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
d. The TSS observed method and SOP instruct the analyst to weigh the filters after just one (1) hour of drying in an oven with a 15-minute cooling period in a desiccator for both filter preparation and sample preparation.
i. Per SM 2540 D. Total Suspended Solids Dried at 103-105C, filters must be dried in an oven for a minimum of one (1) hour, brought to room temperature, and weighed a minimum of two (2) times or until the difference between each weight is less than 0.5mg. This process must be done for both filter preparation and sample preparation.
e. The Cl2 observed method does not accurately follow the Orion method as detailed below.
i. The observed method does not include a daily slope check, which is separate from the direct calibration as detailed in the Orion method.
ii. The observed method uses different volumes of standard for the calibration curve/direct calibration as detailed in the Orion method.
1. Orion: 1mL each of Residual Chlorine Standard - Orion 977007, Acid Reagent - Orion 977011, and Iodide Reagent - Orion 977010 mixed in a 150mL beaker, let sit for two (2) minutes, and add 99mL water. After initial reading, add additional 10mL of Residual Chlorine Standard - Orion 977007.
2. Observed: three (3) solutions of 1mL each of Acid Reagent - Orion 977011 and Iodide Reagent - Orion 977010 mixed with 0.1mL, 1.0mL, and 10mL of Residual Chlorine Standard - Orion 977007, mixed in a 100mL volumetric flask, let sit for 2-3 minutes, and dilute to volume with water.
iii. The observed method uses a different technique for calibration than the direct calibration as detailed in the Orion method.
1. Orion: solution of 1mL each of Residual Chlorine Standard - Orion 977007, Acid Reagent - Orion 977011, and Iodide Reagent - Orion 977010 mixed in a 150mL beaker, let sit for two (2) minutes, and 99mL water is measured under the calibration setting of the instrument and the slope set to that which was determined in the daily slope check.
2. Observed: a three (3) point calibration using the solutions described in bullet ii.2. above. This calibration curve is invalidated due to the non-linear nature of the concentration after 0.2ppm.
iv. The observed method uses different volumes of standard for the calibration curve/direct calibration as detailed in the Orion method.
1. Orion: 1mL each of Residual Chlorine Standard - Orion 977007, Acid Reagent - Orion 977011, and Iodide Reagent - Orion 977010 mixed in a 150mL beaker, let sit for two (2) minutes, and add 99mL water. After initial reading, add additional 10mL of Residual Chlorine Standard - Orion 977007.
2. Observed: three (3) solutions of 1mL each of Acid Reagent - Orion 977011 and Iodide Reagent - Orion 977010 mixed with 0.1mL, 1.0mL, and 10mL of Residual Chlorine Standard - Orion 977007, mixed in a 100mL volumetric flask, let sit for 2-3 minutes, and dilute to volume with water.
7
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
v. The observed method uses different volumes of sample for the analysis as detailed in the Orion method.
1. Orion: 100mL of sample in a 150 mL beaker mixed with 1mL each of Acid Reagent - Orion 977011 and Iodide Reagent - Orion 977010, let to sit for two (2) minutes before analysis.
2. Observed: 1mL each of Acid Reagent - Orion 977011 and Iodide Reagent - Orion 977010 diluted to volume with sample in a 100mL volumetric flask, not allowed to sit for two (2) minutes before analysis.
4. Bench sheets were not properly maintained, as detailed below. See Appendix 2 for selected examples from the documents provided.
a. The Cl2 bench sheets do not reference an approved EPA method and no units are used.
b. The Espanola WWTP E. coli bench sheets cite SM 20th edition 9223 B, which is not an approved EPA method, the date of the end of incubation and subsequent analysis is not recorded, and the temperature of beginning and end of incubation is not recorded per SM 9223 Enzyme Substrate Coliform Test.
c. The 5-Day CBOD bench sheets cite SM 20th edition 5010, which is not an approved EPA method, and the following are autogenerated and not left to be manually entered to reflect actual data; the time for the grab samples at 10am, the effluent temperature as 20, the time read 3:15 with no indication of am or pm, and the volume of seed for all the samples. Additionally, the following are required per SM 5210 B. 5-Day BOD Test but are not present: sample storage temperature, date of pH adjustment, time of sample preparation, time of sample analysis or DO reading before incubation, time and temperature at both the beginning and end of incubation.
d. The Air Basin DO bench sheets do not reference an approved EPA method, there is no calibration information, there is no indication the method uses in-line analysis on the bench sheets and as such the collection and analysis time would be the same. Without indication of in-line analysis collection and analysis times must recorded separately per SM 4500-O G. Membrane Filtration Method. Additionally, the bench sheet design does not allow for analysts to sign off on the "AM" and "PM" sample collection/analysis time individually as there is only one (1) place for a signature for both times.
e. No physical bench sheets were provided for TSS, the following is based on Excel reproductions of the physical bench sheets. The Excel documents cite SM 20th edition 2540 B., which is not an approved EPA method. Based off observations made of the physical bench sheets which were provided for other analysis, it can be reasonably assumed the following are auto populated and not filled with the actual values: oven or drying temperature, time of sample collection, and drying time. The following are required per SM 2540 D. Total Suspended Solids Dried at 103-105C, assuming there are two (2) or more periods of incubation followed by two (2) or more weights, but are not present: time and temperature at both the beginning and end of incubation in the oven, time at both the beginning and end of incubation in the desiccator, and time of filtration. Additionally, no information was provided for the filter preparation.
8
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
5. Discrepancies in data recording were observed, as detailed below. See Appendix 2 for selected examples from the documents provided.
a. The Cl2 bench sheets were missing data entries for the below dates
i. 6/23/2023 - no data recorded for the date, time of sample grab and analysis, and standards.
ii. 6/26/2023- no data recorded for the date, time of sample grab and analysis.
iii. 6/26/2023, second entry - no data recorded for effluent concentration, blank factor, and analyst initials.
iv. 6/30/2023 - no data recorded for analyst initials.
v. No data is recorded for the date reagent and standard replaced for the months of June, May, April, March, and February of 2023.
vi. No bench sheets were provided for the months of November, December, June, July, August, September, and April of 2022.
vii. There are no data entries for the following dates
1. 1/01-22/2023 2. 1/01-05/2022 3. 1/07-31/2022 4. 2/02-28/2022 5. 3/01-02/2022 6. 3/04-07/2022
7. 3/9/2022 8. 3/11-31/2022 9. 5/01-03/2022 10. 5/05-31/2022 11. 10/01-23/2022 12. 10/25-31/2022
b. The Espanola WWTP E. coli bench sheets never list data for flow, are missing data for 5/25/2023, have no data entries for the month of April 2022, and show a transcription error in March of 2023 where the dates were written using February instead of March. Additionally, in 2022 there is supplementary data added and circled in the results column. These appear to be rounded values of the actual results, with the duplicate analysis results added together. There are no notes to indicate the significance of these rounded and circled numbers, and the practice is not continued into February of 2023 and on.
c. The 5-Day CBOD bench sheets are missing the date read data and corresponding analyst initials for samples collected 6/22/2023, 5/18/2023, 3/30/2023, 1/19/2023, 6/30/2022, and 5/12/2022. Additionally, there is no data recorded for 4/6/2023, 3/23-2/2/2023, 1/5/2023, 4/14/2022, and the month of December 2022.
d. The Air Basin DO bench sheets are missing data for first or second am/pm readings, effluent am/pm readings, digestion and effluent reading, analyst initials, and the date in instances that were too numerous to count. There are no bench sheets for a number of days that are too numerous to count.
e. The Pojoaque Terrace E. coli Chain of Custody (COC) documents are carbon copies. Bench sheets were not provided, and it is not clear that bench sheets for these analyses exist; the COC documents do not contain all required documentation for the analysis process. There are several instances of missing data entries on the COCs, however due to the nature of the carbon copies it is not clear if the information was simply not transferred to the copy or if the information was not recorded at all. These are not adequate records of analysis for the
9
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
laboratory to keep, as they are not legible. The COC documents do not adequately trace the custody of the samples at every step of the process from sample collection to transfer to the laboratory with names times and signatures of all persons handling the samples, nor do they notate that the proper custody seals were intact upon arrival at the laboratory. Additionally, there are several instances in which the sample collection time is recorded as occurring after the sample received time, as detailed below. It is unknown how or why this occurred; however, this is not an accurate representation of sample handling and COC.
i. 12/5/2022: Collection time 11:10, received time 9:40
ii. 10/4/2022: Collection time 11:00, received time 10:52
iii. 8/8/2022: Collection time 11:15, received time 9:41
iv. 7/6/2022: Collection time 11:00, received time 9:40
v. 5/9/2022: Collection time 11:10, received time 11:00
vi. 4/4/2022: Collection time 11:15, received time 10:30
vii. 3/8/2022: Collection time 11:20, received time 10:15
viii. 1/10/2022: Collection time 11:15, received time 9:24
6. Data abnormalities were observed, as detailed below. See Appendix 2 for selected examples from the documents provided.
a. For all bench sheets, times are recorded at exactly the ten- and five-minute marks and are consistently at the exact same time every day. It appears that an approximate time is recorded instead of the actual time, which is not an accurate representation of the data and analysis of the samples. Additionally, there is often no indication of whether the time is in the morning or afternoon.
b. The Cl2 bench sheets record the sample analysis as beginning exactly 15 minutes after sample collection. Again, it appears an approximate time is recorded instead of the actual time, which is not an accurate representation of the data and analysis of the samples. Additionally, before March of 2023, the blank measurements were consistently exactly 0.001, with an occasional 0.01 which is assumed to be a transcription error. After March of 2023 the blank readings are varied and no longer exactly the same. It is not known why or how the blank readings were so consistent, however it is not an accurate representation of the data and analysis of the samples. January, February, March, and May of 2022 have effluent and blank readings recorded as only "<1", which is not an accurate representation of the data and analysis of the samples.
c. The Espanola WWTP E. coli bench sheets record the sample incubation time as beginning exactly 15 minutes after sample collection and the incubation end time is recorded as exactly 24 hours and 15 minutes later. These appear to be approximate times, not the actual times, and therefore do not accurately represent the data and analysis of the samples.
d. The 5-Day CBOD bench sheets regularly record the pH of samples as exactly 7.0. Such a consistent measurement is not usual, and it is not an accurate representation of the data and analysis of the samples.
10
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
7. There were too numerous to count instances where the data is invalidated due to the nature of the respective method and/or the quality assurance and quality control data, as detailed below.
a. Cl2 data was invalidated when the blank samples were reading higher than the effluent samples, and when the blank and effluent measurements were less than 0.2ppm.
b. 5-Day CBOD data is invalidated when the final DO measurements are less than 1.0mg/L or have a depletion less than 2.0mg/L after five (5) days.
c. TSS measurements are invalidated when there is not a minimum of two (2) dry weights of filter and sample.
d. Pojoaque Terrace E. coli are invalidated when the holding times cannot be confirmed to be within the acceptable window.
8. The mass balance used in TSS analysis had an expired National Institute of Standards and Technology (NIST) certification at the time of the on-site inspection. See Appendix 1, Photo 5.
9. Many thermometers used to monitor the temperature-controlled instruments and analysis had an expired NIST certification at the time of the on-site inspection. See Appendix 1, Photo 6.
10. It was observed that the running temperature for temperature-controlled instrumentation and equipment used in the analysis of or storage of samples was checked once a day, and not the minimum of twice a day to ensure continuous and constant temperature.
11. There were seven (7) analysts' initials found on all the provided bench sheets which do not correspond with the three (3) NMWQCC certified employees: FL, JM, AD4, GZ, SZ, AF, CM. The initials for the certified employees are MM, RT, and SC.
a. The 5-Day CBOD Excel documents only display "MM" for analyst, despite the physical bench sheets regularly reflecting different analysts.
12. The following documents were requested at the time of inspection, and again during the Microsoft Teams Laboratory Review of the facility, for the dates January 2022 to June 2023 but were provided without sufficient time to be reviewed and included in this inspection report.
a. DMR submission receipts for 2022 and 2023
b. Records of monitoring for pH analysis from March 2022 to June 2023
c. Records of monitoring for WET testing analysis for June 20, 2023
d. Records of monitoring for Metals testing for 2022
13. The following documents were requested at the time of inspection, and again during the Microsoft Teams Laboratory Review of the facility, for the dates January 2022 to June 2023 but were not provided by the facility as of the writing of this inspection report.
a. Hand-written bench sheets, or records of monitoring, for TSS analysis
b. Hand-written bench sheets, or records of monitoring, for CBOD analysis for the month of February 2023 and the month of December for 2022
c. Records of monitoring for pH analysis for the months of January and February of 2022
d. Records of monitoring for Chlorine Residual analysis for the months of April, JuneSeptember, November, and December for 2022
11
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
e. Records of monitoring for DO analysis for the months of January, February, and June for 2022
f. Records of monitoring for WET testing analysis for 2022 and the first quarter of 2023 g. Records of monitoring for Metals analysis for 2023 h. Calibration reports for any instrumentation used in the analysis of regulated pollutants i. Temperature records for all equipment and instrumentation used in the analysis of
regulated pollutants j. NIST calibration certificates for laboratory instrumentation used in the analysis of regulated
pollutants, except for the in-flow DO meter k. Records of monitoring for Pojoaque Terrace E. coli sample analysis
Section III - AREAS OF CONCERN
Requirement 1 NPDES Permit NM0029351 Part I. A.1. Final Effluent Limits:
Concern 1 Facility personnel stated during the in-person portion of the inspection that they were not collecting pH on weekend days and were therefore only collecting pH on five (5) of the seven (7) required days. See Appendix 1, Photo 7.
Requirement 2 NPDES Permit NM0029351 Part III. A. 7. Duty to Provide Information. The permittee shall furnish to the Director, within a reasonable time, any information which the Director may request to determine whether cause exists for modifying, revoking and reissuing, or terminating this permit, or to determine compliance with this permit. The permittee shall also furnish to the Director, upon request, copies of records required to be kept by this permit. Concern 2 The facility did not provide the EPA with all the requested documents or provide explanation that one (1) or more of the documents did not exist, within two (2) months of the initial request date (see item 13 of the Laboratory Observations).
Requirement 3 NPDES Permit NM0029351, Part III: B.3.a. Proper Operation and Maintenance. The permittee shall at all times properly operate and maintain all facilities and systems of treatment and control (and related appurtenances) which are installed or used by permittee as efficiently as possible and in a manner which
12
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
will minimize upsets and discharges of excessive pollutants and will achieve compliance with the conditions of this permit. Concern 3 The grit removal system has been down for over a year, allowing significant damage to the entire plant. Even if the grit removal system were replaced today, this damage will continue to cost the City of Espanola money for years to come, in all the other downstream systems affected. The biological treatment processes are not operating properly, as evidenced by the effluent violations, and the denitrification taking place in the clarifiers. The clarifier weirs are not level, and the effluent flow meter has not been cleaned often enough to prevent algae buildup. The outfall pipe has not been repaired in a timely manner.
Requirement 4 NPDES Permit NM0029351 Part III.B.3.b. Proper Operation and Maintenance. The permittee shall provide an adequate operating staff which is duly qualified to carry out operation, maintenance and testing functions required to insure compliance with the conditions of this permit. Concern 4 City of Espanola representatives have said on multiple occasions that this WWTP requires 13 full time operators in order to be fully staffed, and that they cannot find qualified operators to hire. At the time of this inspection the facility employed three (3) licensed operators and six (6) unlicensed technicians who regularly perform laboratory analysis for regulated pollutants in addition to their plant operational duties. The main laboratory technician is not adequately licensed for the analysis performed in the laboratory. In accordance with NMAC 20.7.4, "operate" is defined as "performing any activity or function or making any process control or system integrity decision regarding water quality or water quantity that has the potential to affect the proper functioning of ... a public wastewater facility or to affect human health, public welfare or the environment." Facility personnel without any operator certification are not qualified to "operate" the facility nor perform any laboratory analysis including pH and dissolved oxygen without constant oversight from a certified operator. It is the responsibility of the municipality to offer operators a salary commensurate with the tasks of running the WWTP and the laboratory. Plant operations and laboratory analysis are not unskilled tasks, they require years of training and testing, and if operators are able to find unskilled work that pays higher than WWTP operations, they will not accept employment as an operator.
Requirement 5 NPDES Permit NM0029351 Part III.B.4.c.(1) Prohibition of Bypass. Bypass is prohibited, and the Director may take enforcement action against a permittee for bypass, unless: (a) Bypass was unavoidable to prevent loss of life, personal injury, or severe property damage; (b) There were no feasible alternatives to the bypass, such as the use of auxiliary treatment facilities, retention of untreated wastes, or maintenance during normal periods of equipment downtime. This condition is not satisfied if adequate back-up equipment should have been installed in the exercise of reasonable engineering judgment to prevent a bypass which occurred during normal periods of equipment downtime or preventive maintenance; and, (c) The permittee submitted notices as required by Part III.B.4.b.
13
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Concern 5 All water pumped from the floor of the UV building into the effluent flow trough after the UV disinfection is a bypass and is not allowed unless the above conditions have been met. The sump pump has been present and possibly bypassing for the last two years, since the UV building flooded.
Requirement 6 NPDES Permit NM0029351 Part III.C.2. Representative Sampling: Samples and measurements taken for the purpose of monitoring shall be representative of the monitored activity. Concern 6 Facility personnel stated that they clean the clarifiers every Wednesday and collect compliance samples on Thursday. This would cause the samples to be collected at the cleanest time period during the week and would not capture a representative sample of the effluent prior to the clarifiers being cleaned.
Requirement 7 NPDES Permit NM0029351 Part III.C.5.a. Monitoring Procedures. Monitoring must be conducted according to test procedures approved under 40 CFR Part 136, unless other test procedures have been specified in this permit or approved by the Regional Administrator. Concern 7 Facility personnel are not following the test procedures properly (see items 2 through 7 of the Laboratory Observations) from the methods approved under 40 CFR Part 136. Analytical results obtained from unapproved or improperly followed methods cannot be validated. Incomplete bench sheets prevent the methods from being verified that they were followed properly.
Requirement 8 NPDES Permit NM0029351 Part III.C.5.b. Monitoring Procedures. The permittee shall calibrate and perform maintenance procedures on all monitoring and analytical instruments at intervals frequent enough to insure accuracy of measurements and shall maintain appropriate records of such activities. Concern 8 Laboratory analytical instruments had not been calibrated within the last year as of the date of the inperson inspection (see items 8 and 9 of the Laboratory Observations).
Requirement 9 NPDES Permit NM0029351 Part III. C.6. Flow Measurements: Appropriate flow measurement devices and methods consistent with accepted scientific practices shall be selected and used to ensure the accuracy and reliability of measurements of the volume of monitored discharges. The devices shall be installed, calibrated, and maintained to insure that the accuracy of the measurements is consistent with the accepted capability of that type of device. Devices selected shall be capable of measuring flows with a maximum deviation of less than 10% from true discharge rates throughout the range of expected discharge volumes.
14
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Concern 9 At the time of the inspection the Parshall Flume had not been calibrated in over a year, and there was excess algae growing on the bottom of the Flume that could cause turbulence and/or inaccurate readings by the ultrasonic secondary flow meter.
Requirement 10 NPDES Permit NM0029351 Part III. C.4. Record Contents. Records of monitoring information shall include:
a. The date, exact place, and time of sampling or measurements; b. The individual(s) who performed the sampling or measurements; c. The date(s) and time(s) analyses were performed; d. The individual(s) who performed the analyses; e. The analytical techniques or methods used; and f. The results of such analyses. Concern 10 Several bench sheets were missing information as required per either the permit or the EPA methods cited or assumed used in the analysis of regulated pollutants.
Requirement 11 NPDES Permit NM0029351 Part III. C.5.a. Monitoring Procedures. Monitoring must be conducted according to test procedures approved under 40 CFR Part 136, unless other test procedures have been specified in this permit or approved by the Regional Administrator. Concern 11A Several SOPs and observed methods used for the analysis of regulated pollutants deviated from the EPA approved methods that were either cited or assumed used. The facility does not have approval for the use of alternate methods or deviations from methods listed in 40 CFR Part 136 from the Regional Administrator. Concern 11B The pH buffer bottles had a written `received-on' date, but not an `opened-on' date, see Appendix 1, Photo 8. The manufacturer of these buffers (Hach) states that the pH 4 and pH 7 buffers should be used within six months and the pH 10 buffer should be used within three months of opening. Several other laboratory reagents were also expired. It is impossible to confirm proper calibration of laboratory equipment, and therefore impossible to confirm proper analysis of a pollutant, if the buffers and reagents are expired.
Requirement 12 NPDES Permit NM0029351 Part III. C.5.b. Monitoring Procedures. The permittee shall calibrate and perform maintenance procedures on all monitoring and analytical instruments at intervals frequent enough to insure accuracy of measurements and shall maintain appropriate records of such activities.
15
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Concern 12 Several NIST certified calibrations for instrumentation used in the analysis of regulated pollutants were expired, and the facility failed to perform adequate temperature monitoring on temperature-controlled instrumentation and equipment used in the analysis of regulated pollutants.
Requirement 13 NPDES Permit NM0029351 Part III. D.5. Additional Monitoring by The Permittee. If the permittee monitors any pollutant more frequently than required by this permit, using test procedures approved under 40 CFR Part 136 or as specified in this permit, the results of this monitoring shall be included in the calculation and reporting of the data submitted in the Discharge Monitoring Report (DMR). Such increased monitoring frequency shall also be indicated on the DMR. Concern 13 Facility personnel stated that they collect plant process control grab samples on Monday, and compliance samples on Thursday, but never report on their DMRs any of the results from the samples collected on Monday. Any sampling that is conducted according to the requirements of the permit (i.e., grab samples) must be reported on the DMRs in addition to the compliance samples.
Section IV - CLOSING CONFERENCE
EPA Region 6 inspector, Amy Andrews conducted a closing conference at the Espaola WWTP at 3:05 PM on July 13, 2023, for the on-site portion of the inspection and inspectors were offsite at 3:25 PM. An additional closing conference was conducted by EPA Region 6 inspector, Magda Vargas via Microsoft Teams at 3:30 PM on August 16, 2023, and the meeting was ended at 4:09 PM. During the closing conferences, the Inspectors reviewed the Areas of Concern that were noted during each portion of the inspection. Additional AOCs have been noted in this report that were not covered in the closing conferences because they were determined afterward.
Section V - FOLLOW UP
The following information was requested by EPA on July 13, 2023: For the dates January 2022 to June 2023, provide the following documentation for the analysis of regulated pollutants per an NPDES permit; pH, CBOD5 5-day, BOD, TSS, E. coli, Total Residual Chlorine, Total Ammonia, Dissolved Oxygen, Whole Effluent Toxicity Testing, and any additional pollutants not listed. o Chain of Custody documents for all incoming samples to the laboratory o Bench sheets and all recorded data (records of monitoring) o All calibration reports for instrumentation used in analysis Meters, mass balances, etc o Temperature records for all equipment and instrumentation used in analysis Incubators, refrigerators used for storage, ovens, etc o Submitted and signed DMRs
16
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Provide all National Institute of Standards and Technology (NIST) calibration certificates for laboratory instrumentation used in the analysis of regulated pollutants Influent and effluent flow measurements from January 2022 to June 2023 Laboratory Quality Control and Quality Assurance records from January 2022 to June 2023
o Preliminary batch testing for disposable sampling and analysis equipment. For example, pre-weighed filters for TSS analysis, Colilert trays for E. coli testing.
o Blank testing of glassware or other equipment and instrumentation to ensure proper preparation, for example cleaning or sterilization.
Certifications and/or training documents for all technicians who perform analysis or sample preparation for regulated pollutants All standard operating procedures for the analysis, sample gathering, sample preparation, sample disposal, equipment and instrument preparation, and calibration of equipment for the analysis of regulated pollutants Documents were received from City of Espaola representatives via GoAnywhere Managed File Transfer on August 8, 2023, and September 7, 10 and 11, 2023, except for those listed as not-received previously in this report (see item 13 of the Laboratory Observations). Section VI - LIST OF APPENDICES Appendix 1 - Photograph Log - Eight (8) photos taken July 13, 2023 Appendix 2 - Selected Bench Sheets Submitted by City of Espanola Representatives
17
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Appendix 1 Photograph Log
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 1
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN2019.JPG Date of Photo: 07/13/2023 Time of Photo: 1:56 PM Photographer: Amy Andrews Description: View of grit floating in the anoxic zone of the treatment basin.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 2
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN2025.JPG Date of Photo: 07/13/2023 Time of Photo: 2:10 PM Photographer: Amy Andrews Description: View of denitrification occurring in the clarifiers, causing floating solids that have the potential to go over the clarifier weirs. Grit is present with the floating solids, and clarifier weirs are not level.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 3
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN2037.JPG Date of Photo: 07/13/2023 Time of Photo: 2:36 PM Photographer: Amy Andrews Description: View of effluent Parshall Flume with algae buildup on the bottom and turbulence.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 4
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN2035.JPG Date of Photo: 07/13/2023 Time of Photo: 2:30 PM Photographer: Amy Andrews Description: View of sump pump that was present in the UV building, plugged in, and plumbed such that pumped water would go into the UV trough after the UV disinfection.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 5
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN2003.JPG Date of Photo: 07/13/2023 Time of Photo: 12:42 PM Photographer: Amy Andrews Description: View of the mass balance used in TSS analysis with an expired National Institute of Standards and Technology (NIST) certification.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 6
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN1995.JPG Date of Photo: 07/13/2023 Time of Photo: 12:15 PM Photographer: Amy Andrews Description: View of a thermometer with an expired NIST certification.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 7
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN1990.JPG Date of Photo: 07/13/2023 Time of Photo: 11:40 AM Photographer: Amy Andrews Description: Photo of pH benchsheet from 07/3/2023 to 07/13/2023.
UNITED STATES ENVIRONMENTAL PROTECTION AGENCY
Photograph Log
Photo No. 8
Location: City of Espaola Wastewater Treatment Plant
City: Espaola
County: Rio Arriba
State: New Mexico
Photo File Name: DSCN1984.JPG Date of Photo: 07/13/2023 Time of Photo: 11:35 AM Photographer: Amy Andrews Description: View of pH buffer bottles with a written `received-on' date, but not an `opened-on' date.
Espanola, City of / Espanola Wastewater Treatment Plant Inspection Date 07/13/2023 & 08/16/2023
Appendix 2 Selected Bench Sheets Submitted by City of Espanola Representatives