Document 99ODBYEnJNaqMK73jbNKD0o7q
E2SC D. 15. Roush
March 16, 1972
Therminol FT! Lo Temp Conversion
cp/jjr P. W, Gann/Pile B2J.K W. B. Papageorge
1700 JACK MC Mill
Attached are copieo of our Therninol Pn conversion bullotln, mechanical seal bulletin, and heat transfer data per our conversation of March 15. At this point, I would suggest you look at Therminol 55 as a replacement fluid. It does have a -4oP pour point, but does not have the low temperature fluidity of PR Lo Temp. Also Important is the fact that Thermlnol 55 1s not classified as a fire resistant fluid as Is PR Lo Temp. Certainly, you will want to seek consultation from plant safoty and/or CEB's Property & Protection group on the use of a combustible heat ing fluid In your Claes I, Division I application. The conversion bulletin lists our suggestions on system clean out and return of pr fluid. A bulk return of PR Lo Temp seems practical and we ask you contact our conversion team at 694-2514 to arrange proper re turn and disposal. Ke also aok that you advlBe us on alternate fluid selected, 00 we can arrange adequate supply, ahould your selection be Thermlnol 55. Please contact me or any member of our conversion teem at 694-2514 If you have questions on the Thermlnol PR Lo Temp con version.
D. E. Roush
cs Attachments:
2 Conversion Bulletins 2 Mechanical Seal Bulletins 2 Coefficient & Pressure Drop Books
HONS 098630