Document 99Gnop5Jj6jzdXZvXQx5aeZGV
Heating Systems Specialties
Armstrong Machine Works Representatives
851 Maple Street, Three Sixers, Mich.
in Principal Centers
^**"2 I***"
Steam Traps... Air and Air Relief Traps... SOItCeOaXmU HUluMmUidiiuifuievrts* ......R-----e---f-r-Wigerant Purg_ ers
All Armstrong Products are Sold on a Basis of Satisfaction or Your Money Back
Traps Stocked by 39 Factory Representatives and 13S Jobbers; Available Through Anv Jobber.
ARMSTRONG INVERTED BUCKET STEAM TRAPS
APPLICATIONS. Armstrong manufac tures inverted bucket steam traps for any pressure from 0 to 2400 psig; for dis charging to high pressure, gravity or vacuum returns; for draining mains, risers, coils, heaters, radiators, unit heat
ers and process equipment.
FEATURES. High Quality Mechanisms in Armstrong traps for low and medium pressures are identical in design, work manship and materials to those used in
traps for 950 psi, 900F.
from 500 to 1500 cu ft free air per hour when steam is first turned on. High Capacity for Size. The patented free-floating lever mechanism makes pos sible wide opening of discharge orifices large for overall trap size and price. Arm strong capacity ratings, based on actual tests with hot condensate, are entirely
reliable.
Automatic Air Discharge. Standard traps discharge normal amounts of air along with condensate. "Blast" traps with thermic bucket vents discharge at rates
O
' No. 800-814
b---------- <-.---------
No. 880-881
Pipe Connections list Price (Regular) List Price (Blast Trap) Telegraph Code (Regular) Telegraph Code (Blast Trap)
Height Diameter.......... Humber of Bolts Diameter of Bolts
, Weight . Maximum Pressure, lbs. ,
Continuous dis charge capacity in lb of water perhour at pressure indi cated. For more complete informa tion see the Capa city Chart in Arm strong Steam Trap Book.
Pipe Connections List Price (Regular) List Price (Blast Trap) Telegraph Code (Regular) Telegraph Code (Blast Trap) Height... Diameter Diameter of Bolta Number of Bolts Weight...... * Maiimum Pressure, lb...
1536
Armstrong Machine Works
Heating Systems specialties
Non-clogging. Swirling action of conden sate carries dirt through trap. The larger sizes seldom require the extra cost of strainer protection.
Quick-Acting. Condensate and air are discharged as fast as they reach the trap, providing fast heatup and maximum temperatures.
CHOICE OF BODY STYLES. In the most commonly used sizes, Armstrong traps are available in several body styles to simplify, and reduce the cost of, in stallation.
Side Inlet Series. Traps number 800, 811, 812, 813, 814 have horizontal and oppo site pipe connections. Capacities and mechanisms of 811, 812, 813, 814 are identical to bottom inlet traps 211, 212, 213, 214.
Integral Strainer Models. No. 880 and
881 traps have strainers in the trap body; otherwise identical to 800 and 811 traps. No. 880 lists at $11.50, 881 at $16.00. Both cost less to buy and install than a trap plus separate strainer.
Right Angle Trap. No. 801 capacity and price identical to No. 800 listed.in table. For replacing old radiator traps or wher ever angle connections are simplest.
Bottom Inlet Traps. No. 211 through 216 have bottom inlet top outlet connections.
TECHNICAL LITERATURE. (Avail able free upon request) Catalog J. The Armstrong Steam Trap Book. 44 pages of data on trap selection, installation, maintenance and trouble shooting for all classes of equipment.
How to Select Traps for Draining Unit Heaters--lists the Btu Output Ratings for all sizes and types of 30 makes of unit heaters in a convenient single source.
ARMSTRONG STEAM HUMIDIFIERS For Stores, Offices, Hospitals, Factories, Laboratories
Operation. These units provide auto matic, closely controlled humidification by introduction of steam directly into the room. Installation is comparable to unit heaters. A solenoid discharge valve on the hu midifier is controlled by a sensitive humidistat. A fan or venturi nozzle aids steam dispersal. Where an electric spark is an explosion hazard, air operated models are available. A large model for installation in air ducts and central heat ing systems is also made. Capacities range from 31 to 630 lbs/hr steam.
Advantages. Installation cost is as much as 80 per cent less than some types. The
smallest unit, capable of humidifying up to 40,000 cu ft, lists at $182.25 complete with control. No extra load on the heat ing system. No dripping--any moisture in the steam is re-evaporated in the steam - jacketed separating chamber. Control is accurate within a few per cent R. H.
Bulletin No. 1775 gives complete data on required relative humidities, selection and installation of Humidifiers.
OTHER PRODUCTS (Bulletins free on Request)
Bulletin 2062--Armstrong ball float traps for venting air from hot water systems. Bulletin 1921--Armstrong Purgers for
discharging air, other non-condensable from refrigerating systems.
Bulletin 241--Armstrong liquid seals.for refrigerating systems.
1537