HEATINC VENTILATING AIR CONDITIONING GUIDE 1941
CUBBBKT
Table 1. Classification of Motors
JSpbsd TEEZSTtCS
Full Voltage
Starting Tobqus
STARTING CuBBENT
Hr
Range
Ttpb or Application See Footnote*
1. Shunt
Direct
2. Compound
3. Series
Constant Speed Drives Constant Medium Medium All
Constant High or Variable
Medium All
(a) Fans and (c) Centrifugal Pumps
W (<0 (*) Recipro cating Pumps and fre quentor hand starting
Variable High
Medium Small ^ (d) Fans direct connected
Poly
phase
4., Squirrel Cage Constant Normal High
All
General Purpose
6-8 Times
(a) Fans and
(c) Centrifugal Pumps
5. Squirrel Cage Constant Normal Medium Medium (a) Fans and
Medium Torque
5-6 Times Small Centrifugal Pumps
6. Squirrel Cage High Torque
Constant High
Medium Medium 5-6 Times Small
(b) Reciprocating Pumps
(e) and Compressors started loaded
7. Automatic Start Constant High High Torque
Low 3 Times
Medium
(6) Reciprocating Pumps
(e) and Compressors started loaded .
8. Slip Ring
Constant High
Wound Rotor
Low
All
1-3 Times
with sec
ondary
control
() and Hoists
() Reciprocating Pumps (c) and Frequent (e) or Hand Start
9. Synchronous High Speed
Constant Medium Medium Medium (o) Fans and Cen5-7 Times Large trifugal Pumps
10. Synchronous Low Speed
Constant Low
Low
Medium (a) Reciprocating
3-4 Times Large Compressors start
ing unloaded
Single 11. Capacitor
phase
Constant High
Normal Medium (A) Pumps and Small Compressors
`Applications: a. Drives having medium or low starting torque and inertia (PFR1) such as fans and centrifugal pumps
or reciprocating pumps and compressors started unloaded. b. Drives having high starting torques, such as reciprocating pumps and compressors started loaded. c. Similar to (a) except where frequent or hand starting (large WR?) requires a higher starting and
accelerating torque. d. Fans direct connected. t. Stoker drives.
644
CHAPTER 35. MOTORS AND MOTOR CONTROLS
CUBBEKT
Table 1. Classification of Motors--(Continued)
Ttpb
Spssb CHARAC TERISTICS
Full Voltage
Stabtiko Torque
STARTING Current
Hr
Range
Ttpb op Application 8eb Footnote*
Single
phase
12. Capacitor Fan Constant High
Medium Medium (a) Fans--belted Small
13. Capacitor Fan Constant Low
Medium Medium (d) Fans--direct Small
14. Capacitor Start Constant Any Induction Run
Medium Medium (a) Fans Small (5) Pumps and Compressors
15. Repulsion Induction
Constant High
Medium Medium (a) Fans Small (A) Pumps and Compressors
16. Repulsion Start Constant High Induction Run
Medium Medium (a) Fans Small (A) Pumps and Compressors
17. Split Phase
Constant Medium and
Adjust able
Medium
Frac tional
(a) Fans (A) Pumps and
Compressors
Adjustable Speed Drives
18. Shunt Field Adjustment
Constant Medium Medium All
Direct 19. Shunt Armature Variable Medium Medium AH Resistor
(a) Fans and (e) Centrifugal Pumps
(a) Fans and (e) Centrifugal Pumps
Poly
phase
20. Squirrel Cage Variable Medium Medium Medium (a) Fans
High Slip,
Small
Tapped Winding
21. Squirrel Cage Variable High Slip, Trans former Adjust ment
Medium
Medium
Medium Small
(a) Fans
22. Squirrel Cage Constant Medium Separate Wind Multi- or High ing or Regrouped Speed
Poles
Low
All
(a) Fans (A) Pumps and (c) Compressors
645