Chapter 33--Hot Water Heating Systems and Piping
rooms. This arrangement is especially valuable when the regulating valves are control^ thermostatically by the temperatures in the two zones, because no matter how accurately the heating system may have been designed, the heat demand of any group of rooms varies with sunshine and with wind velocity, and these intermittent variations can be provided for only by the individual control made possible by changing the valve settings controlling the heat supplied to particular groups of rooms.
3. All piping must be installed so that it is free to expand and contract with changes of temperature without producing undue stresses in the pipes or connections. For this purpose it is generally sufficient to allow for a variation in length of 1 in. for 100 ft of pipe.
4. The pipe system must be installed so that each circuit has its correct friction head! To bring this about, it is necessary in some cases to minimize the friction, i.e., to make the pipe line as short as possible and to provide as few fittings as possible; and in other cases it is necessary to increase the length of the pipe and the number of fittings so that for every circuit, the friction head will be equal to the available pressure head.
The connections from the boiler to the mains should be short and direct, to reduce the friction head. It is frequently possible to avoid an elbow and to reduce the length of the
1
Fig. 11. Method of Connecting Radiator to Allow for Expansion of Pipe
pipe by running the pipe in a diagonal direction, either in a horizontal or in a vertical plane.
The mains and branches should pitch up and away from the heater, generally not less than 1 in. in 10 ft. The flow main should alwaysbe covered; the return main should be covered except where it is to provide the heating surface for the basement.
The connections from mains to branches and to risers should be such that circulation through the risers will start in the right direction. Hence, in a one-pipe system the flow connection must be nearer the heater than the return connection. In a correctlydesigned two-pipe system, the pressure in the flow main is higher than that in the return main, and a slight variation in the distances of the flow and return connections from the heater is not material; but it is generally best to have the two connections about equally distant from the heater.
In some cases it may be advisable to take the flow connection off the top of the main and the return connection from the side, but in most cases both connections should be at an angle of 45 deg. This method shortens the lines and substitutes 45-deg ells for 90-deg ells.
Preferably, connection of the flow riser to a radiator shdttld be to the upper tapping, and connection of the return riser to a radiator should be to the lower tapping. When hot water enters at the top of a radiator it will distribute itself along the entire length of the radiator, and as it cools it will settle gradually to the bottom; the cool water may then be taken out of the radiator at either end.
With forced circulation and high velocities, it is advisable to let the water enter at the top of the radiator and leave at the bottom of the opposite end. With gravity circulation and low velocities it makes little difference whether the water leaves at the end at. which it enters or at the opposite end.
*
620
The connections of the risers to the radiators should be such that provision is made for the.vertical expansion of the risers. This can be accomplished as indicated in Fig. 11 by using one tee and two ells for each connection. These connections should be pitched upward or downward, whichever may be necessary to prevent the formation of air pockets and to permit draining.
PROBLEMS IN PRACTICE
X Will altering a hot water heating system from an open to closed type system (a) increase the circulation and (6) give more heat?
a No. Tests conducted by the A.S.H.V.E. indicate that there is little, if any difference in the circulation when the system is under pressure. The difference in temperature between the supply and return, and the friction are the governing factors,
j. With a closed system the water may be carried at a higher temperature without boiling which permits warmer radiators.
2 What tends to prevent or to retard the circulation of water in hot water
heating systems?
In both gravity flow and forced circulation systems, the friction which must be overcome when the water is flowing through pipes, fittings, valves, heaters, and radiators tends to prevent or retard circulation. For a given pipe the friction varies approximately as the 1.7 power of the velocity, and for given fittings, valves, heaters, and radiators, the friction varies approximately as the square of the velocity. It is therefore sufficiently accurate to express the friction in fittings, valves, heaters, and radiators in terms of the friction in one standard elbow, as shown in Table 1.
3 In the elementary heating system. Fig. 8, what is the pressure head main taining the circulation if the water in the return riser is at 180 F and that in
the flow riser is at 200 F?
It is found, from Table 7, Chapter 1, that 180 F water weighs 60.61 lb per cubic foot and 200 F water weighs 60.13 lb per cubic foot. The pressure head is independent of the size of the pipe. If the two risers were each 1 ft square, the water in the flow riser would weigh 601.3 lb and that in the return riser would weigh 606.1 lb. Thus the water in the return riser would weigh 4.8 lb more than that in the flow riser. Consequently, the resulting pressure head is 4.8 lb per square foot. Pressure heads are generally expressed in feet, or inches, or milinches of water of a given temperature. In this case we are dealing with water at both 180 F and 200 F, so the pressure head.is expressed in terms of 190 F water. Such water weighs 60.39 lb per cubic foot, and to secure a pressure of 4.8 lb per square foot, it is necessary to have a column of water having a weight of 4.8 divided by 60.39 = 0.0795 ft, or 0.9540 in., or 954 milinches. This is the pressure head which maintains the circulation.
4 In the elementary system of Question 3, if the radiator dissipates 14,000 Btu per hour, what is the velocity of the water in the pipe line, if the pipes are 1 in. in diameter? What, if they are % in. in diameter?
Since the temperature drop through the radiator is from 200 F to 180 F or 20 F, every pound of water flowing through the radiators delivers 20. Btu; consequently, 14,000 divided by 20 = 700 lb of water, or for 190 F water, 700 divided by 60.39 = 11.59 cu ft of water must flow through the radiator and through the pipe lines every hour. .
The interior area of a 1-in. pipe is 0.864 sq in. The velocity in the 1-in. pipe is 11.59 divided by 0.864 and multiplied by 144 = 1932 ft per hour or 6.44 in. per second.
For M-in. pipe, the interior area is 0.533, and the velocity is 6.44 multiplied by 0.864 and divided by 533 = 10.44 in. per second.
5 If, in the elementary heating system of Question 3, a 1-in. pipe line is
ttsed, what would be the friction head?
If the radiator is connected as shown in Fig. 11, with the heater connected to provide
621