Document 93ndQxg0w2JgjOyNg3Y6g6dE3

BULLETIN NO. IC/FF-38R 2 <Rvi-d Amgmt, 18761 TRANSFORMER 9AA\U. Jf*______ V J Inspection & Maintenance Guide MCNS 073S43 i. SECTION A TRANSFORMER ASKARELS.......................................... 1 I. Introduction......................................................... 1 II. Hlvtory I Trade Name Types............................. 1 Table I - The Composition of Transformer Askareli ..........................................2 til. !ntcrchsnesbility .............. 2 IV. Table II - Official Transformer Adtaret Stripping Specifications....................................... 3 V. Orderinf Inefructiona ..........................................2 VI. VII. Stability................................................................ 2 Precautions When Handling Drums, Tank Cara and When Opening Transformers........................2 A. Keep Dry During Handling .......................... 2 Table III - Handling and Pumping Temperatures..................................4 S. Use Ordinary Personal Precautions..............4 C. Precautions on Opening an Askerel Transformer.......................................5 VIII. Avoid Environmental Pollution.......................... S 1. Libeling Askarei Transformers..................... 0 2. Disposal of Liquid and Solid Wastes ........... 6 3. Conditioning of New or Recycled Askarei .8 4. Teerdown of Transformers for Repair or Scrap ....................................... 7 5. Transformer Disposal.....................................7 IX. Expected Service Life..........................................7 X. Qeneral Characteristics of Transformer Askarei Fluid.........................................................7 XI. Sampling Transformer Askarei Fluid ................ 8 Ml. Evaluation of Askarei Received In Nmv Equipment.............................................. 8 XIII. DWeetrie Breakdown Voltage - Moisture Relationship..........................................8 Table IV -- Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askerel and Mineral Oil.......................................9 Table V - Approximate Solubility of Water In Transformer Askarei end Mineral Oil .... 10 XIV. Turbidity............................................................10 XV. Cheek Paints for Maintaining Adtaral Insulation .............................................10 A. Central Considerations................................ 10 B. Modern Sealing Procedures ........................ 11 C. The Older Sealing Arrangements................. 12 XVI. Periodic Fluid Impaction and What Checkpoints Maan ...................................12 A. Visual Inspection.......................................... 13 B. Dielectric Breakdown Voltage ................... 13 XVII. Impaction Checklist.......................................... 13 XVIII. Contamination in Transformers..........................14 Table VI - Efftct of Common Insulation Materials on Power Factor and Dielectric Strength.............................................14 Table VII - Effect of Common Insulation Materials on Voluma Resistivity of Askarei.......... .................................................14 XIX. AITM Method for Investigating the Compatibility of Transformer Insulation and Construction Materials in Askarels............15 XX. Refining Adtarel for Re-Use..............................IS A. Filtering Through Dry Blotter Pape* to Remove Moisture and Extraneous Particlas..................................... 15 XXI. XXII. Table VIII -- Water Removal by Filtering Askarei Through a Paper Press .......................18 B. Disposal of Solid Wastes ............................. 18 C. Solid Insulation Requiring Drying.............. 10 D. Earth Treatment for Maximum Improvement of Power Factor and Volume Resistivity .....................................16 Table IX -- Effect of Power Factor and Volume Resistivity........................ 17 Cleaning Arced Transformers...........................17 Sampling Adtarel...............................................17 SECTION B ASKAREL FILLED SWITCHES AND TERMINAL CHAMBERS .....................................19 I. Introduction...................................................... 19 II. Sources of Contamination................................19 III. Sealing Switches and Terminal Chambers...20 IV. Askerel Used Under Mild Arcing Conditions . 20 V. Maintenance for Askerel Filled Switches .... 20 VI. Askarei Under Excessive Temperature or Fault Conditions ......................................... 21 SECTION C TOXICITY AND SAFE HANDLING............................. 21 I. Inhalation........................................................... 21 II. Skin Contact...................................................... 21 SECTION D ANALYTICAL SERVICES ON TRANSFORMER ASKAREL AVAILABLE FROM MONSANTO............................... 22 Types of Analyses Available: ......................................... 22 1) Routine Maintenance Check.................................... 22 2) Complete Analysis................................................... 22 3) Analysis After Earth Refinement .......................... 22 SECTION E APPENDICES................................................................... 23 Appendix A -- Adtarel Stability and Composition of Arc Formed Gas..................................23 Appendix B -- Solubility of Gas in Transformer Askareli ................................................... 23 Appendix C -- Effect of Temperature on DMeetrie Breakdown Voltage of Askarei ...................23 Appendix D -- Comparison of the Approximate Viscosity in Saybolt Universal Seconds of Transformer Askarels and Mineral Oil.......................... 24 Appendix E -- The Density of Intrteen 54201 KA 7338*9 and Transformer Pyranof A1383B3........................................................ 24 Appendix F -- Thermal Conductivity Values of Transformer Pyranol A13B3S-3............................... 24 Appendix G -- Heat Capacity......................................... 24 Appendix H -- Coefficient of Expansion........................24 Appendix I -- Fire Resistance......................................... 24 Appendix J - Seals, Properties and Procurement ...........................................................25 Appendix K -- Caution Label......................................... 25 NOTICE: "Nothing contained herein is to be construed as a recommendation to use any product in conflict with any patent. MONSANTO MAKES NO WARRANTIES AS TO THE FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OF ANY PRODUCT REFERRE0 TO. no guarantee of satisfactory results from reliance up* on contained information or recommendations, and dis claims all liability for any resulting loss or damage." RONS Q7394A t. Introduction The term "askarei" as defined by IEEE, ASTM and the National Electrical Code generally describes a broad class of fire-resistant* synthetic chlorinated hydrocarbon insulating liquids widely used in transformers, reactors and accessory equipment operated at power frequencies. Askarels of various compositional types ere in use. (For the general properties and types see ASTM 0-2283.) Under arcing conditions the gases produced, while consisting of predominantly non combustible hydrogen chloride, can contain varying amounts of combustible gases depending upon the askarei type. This manual describes the operating characteristics of transformer askarei liquid insulation as manufactured by Monsanto and how it differs from mineral oil. Appropriate handling and disposal procedures for both scrap askarei liquid and impregnated solid materials art given In accordance with the guidelines recommended by the American National Standards Institute. The information is based on facts gathered by Monsanto over 40 years as a producer of askarei, plus knowledge gained from the experience of transformer manufacturers and users. This guide outlines the maintenance required for askarei fluid in "modern" transformers and offers suggestions for sealing and maintaining askarei in old units. By following this guide, we believe users will obtain maximum service from askarei insulation with a reasonable minimum of maintenance. If questions arise relating to the designing and building of transformers, these should be referred to regular transformer suppliers. Monsanto gratefully acknowledges the assistance, guidance and the contributions of certain data by the following: Edward l Raab - General Electric Dr. T. K. Soet -- Westlnghouse Electric II. History of Trade Name Types "Askarei" is the generic name for the fire-resistant liquid Insulation and coolant first used by General Electric Company in 1933 for thair Pyranol1 brand name fire-resistant transformers, Westinghouse Electric Corporation uses their brand name, Inerteen.* Whatever the trademarked brand, the askarei contains chlorinated biphenyl - one of the best liquid insulations developed by science. This inert material is chemically stable, fire-resistant, heat stable, non-corrosive, and has high dielectric strength under the operating conditions encountered in transformers. In addition to manufacturing Aroclor* chlorinated biphenyl , Monsanto also mixes this dielectric fluid with chlorobenzenes to produce the presently used Inertcen and Pyranol blends described in Table I. "NOTE: Material* designated 'fire resistant* generally ere mere difficult to ignite, or once ignited, burn at a slower rate than corresponding conventional materials. This term does not mean that fire resilient materials will not burn. However, when properly used. Monsanto's fire resilient ASKAAEL FLUIDS are useful in helping customers meet iheir lire safety requtrtments." ^Trademark of General Electric Company ^Tmdcmaik of Wesunijhouse Electric Corporation `Hegistered trademark of Monsanto Company HONS 073945 11 Table I The Composition of Typical Transformer Askarcti Type D Type Type G Trade Names Incrtcen 7030 Inerteen 10042 Pyronol A13B383 Ingredients (% by wt.) Arodw12S4. Chlorinated biphenyl 154% chlorine by weight) 70 Aroclor HM242, chlorinated biphenyl (42%chlorine by weight) _ Trichlorobanzene 30 Phenoxypropone oxide scavenger 0.18 to 0.22 Dilpoxide scavenger ~ 100 0.18 to 0.22 60 _ 40 0.115 to 0.135 ASTM Method D-2283, titled "Ch/orinared Aromatic Hydrocarbons (Atkarab) For Transformars", also lists the composition of alt transformer aikarels used at various times since 1933. Monsanto manufactures similar transformer askaret fluids in England where the trade name ftyoclor is used. Ml. Interchangeability In general all transformer askarals art interchangeable. However, it is suggested thet the transformer manufacturer be consulted prior to mining in significant proportions or total substitution. IV. Traniformer Askarel Specifications Sptcifications for the three modern transformer askarel fluids ere shown in Table II. V. Ordering Instructions Monsanto's currant policy is to sell askarel transformer fluids only to transformer manufacturers. Others interested in these fluids should contact the manufacturers of askarel transformers and not Monsanto. The transformer name plate indicates the transformer maker and usually gives sufficient data to identify the specific askarel fluids used. VI. Contamination Askarel insulation must never be mixed with mineral oil. Over two percent of mineral oil by volume in askarel begins to lower its fire resistance. In modorn transformers, the principal "enemy" of askarel is contamination by water. Keeping askarel water-free will insure long-time service. Askarel is heavier than water. If water gets into askarel insulation, only a liny amount (approximately 135 ppm} dissolves - the rest floats on fop. Askarel is very insoluble in water, only about 200p3rts per billion of askarel dissolve in water. at normal temperatures. VII. F'rocaulionsWhen Handling Drums, Tank Cars, and When Opening Transformers Inf Inbowmg ju* significant precautions: A. Kith Dry During Handling: in storing, sampling and inspecting askarel - and in TaUill Transformer Mwl Specifications (New F)uM) Specification Properties1 Color. APHA Curvi'lrott VV.it-r content, ppm IASTM 01533 60) Acidity, mg KOH'g (ASTM D974 55) D"?-;i.tric Strength. 25 C. 0.1 in. gap -ASTM 0877 491 Dn'ifctric Constant, 10(70. 60 H IASTM 0924 49) Volume Resistivity, 100C, 500 volts OC 0.1 inch gap, IQ9 ohm-cm IASTM DI1G9) lnorrwnri. chlorides, ppm (ASTM D1821 and G.E. Method E4C41B) Refractive index, 25 C (ASTM 01807) Viscosity at 37 8*0 (ASTM 088 56) Saybolt Universal Seconds Pour Point ^C IASTM D 97 57) Specific gravity 25.'15.5','C (ASTM 01810) Sum point IASTM D92) Distillation range (ASTM D20-56) corrected tor stem and barometric pressure General Electric Co. Transformer PyrancH A13838-3 ASTM 02283 Type G 150 max. Clear 30 max. 0.014 max. 35 KV, rnin. 4.2 to 4.6 100 0.10 max. 1.6110 to 1.6120 44 to 48 38 or lower 1.495 to 1.510 None to boiling 1st drop 20CTC min. 4Q% max. below 270*C 90% 3 79 to 394 8ntto#wen Transformer Inerteen 70-30* ASTM D2283 Type D 150 max. Clear 30 max. 0.014 max. 35 KV. min. 4.2 to 4.5 100 0.10 max. 1.6153 to 1.6173 56 to 61 -3) or lower 1.518 to 1.528 None to boiling 1st drop 200*C min. 35% below 27Q*C 90% 379 to 394 Werttnqhotne Transformer Inert*TM 100-42* ASTM 02233 Type E 60 max. Cleat 35 max. 0.01 max. 35 KV. min. 100 1.6240 to 1.6260 82 lo 92 17 or lower . 1.381 to 1.392 None to boiling 10% 325*0 min. 90% 3Q3 max. i* s e to snow Fmed chlorine Corrosion test Color. APH A Acidity, mg KOH'g I norgame chlorides ppm Condition Scavenger content Typical Properties* Coefficient of Thermal Expansion IASTM 01903). cn.2/Cm^/C Arc formed gases 'IVettmghoui* utts their privet* number tneneen 54&1KA for Inn teen 70-30 ntf fh#ir private number ln#M**n 54201 CM >or Inerieen 100*42. 56.4 + 0.5% 55.6% min. 43 0.5% After heating with aiuminum for 6 hrs. at 200 to 220C, the aluminum must no! be corroded on either visual or weight inspection and the askarel should meet the following specifications. 200 max. 200 max. 200 max. 0.014 max. 0.014 max. 0.01 max. 0.15 max. 2.0 max. 0.15 max. Clear Clear Clear .115 to 0.135% 0.18lo0.22% 0.18 to 0.22% Diepoxtde phenoxypropene oxide phenoxypropene oxide 0.0007 0.0007 0.00068 Asliarefs of various compositional types are used. Under arcing conditions the gases produced, while enn\niu<g predominantly of non combustible hydrogen chkyxi*, can include varying amounts of combusiiit^ U*p< <iu>g upon the askjret ryp* Irnuiation tyttems mcorpoijting these askareis and cdMottc or other Ofg*n>c n,*f.rr<jh may. when arced, produce gaseous mixtures whttfi are mod*'ately flammable. As a precaution, such gau:s should be removed from the asfcatel be dry nitrogen through the asfcarel and flushing the gas space ww dry nitrogen before any work is per loaned on tfe appaiatus These uuannurs a** final wist sp*c*i>cjtiof** only to the eaten, (hat they coincide with Morsantg's published specifications. 'This data is based upon samples tested m the i*bor*tgry nd is not guaranteed <or all ampfes. Write wt for complete sates esecifxenons for Askarai fluids. nitrating askarel transformers -- take every precaution to guard the askarel insulation from exposure to high humidity and moisture contamination. Keep 5 or 55 gallon drums of askarel dry; lay stored drums on their sides with the bung at the highest point from floor to keep water off the drum head (which can be sucked into the askarot by the drum "breathing'*). This piccaution it not necessary when drums are stored indoors, which is the preferred place for storage. To avoid leakage tho drums used for askarel are of heavy construction. Sixteen gauge metal is used, with special rim seal and bung construction. The drums should be drained as completely as possible and then flushed twice with kerosene type solvent to remove all of the askarel. Accumulated liquids and washings should be collected and should be incinerated at high temperatures, eg., about 2000eP, to destroy the polychlorinated biphenyls (PCBs). See Section A, VIII. Tank cars used to transport askarel* are in exclusive service and not used interchangeably for other products. All cars must be unloaded through the top (dome fitting) either by pumping or with controlled pressure using dry air or dry nitrogen. If nitrogen has been used for unloading it is necessary to advise the shipper so that whan the car returns the nitrogen can be replaced with dry air before any one may enter the car. If the car is to ba unloaded by pumping it will be necessary to use a dryer on the air intake line to remove moisture. All tank cars are fitted with steam coils, which are available for unloading under extreme low temperature conditions. Convenient handling and pumping temperatures are given in Table III. B, Use Ordinary Personal Precautions: Transformer askarel has been made, handled, and used for over 40 years. It can be handled safely with recommended precautions. If accidentally spilled on hands, no serious skin irritation will occur. However, liquid eskarei has a solvent action (similar to paint Table III Handling and Pumping Tamperatures Product Unloading, Handling and Pumping Temperature *C Pyranol A1383B3 Inerteen 70*30 Inerteon 100-42 20-55 20 - 55 35-75 thinner) on the fats and oils of the skin and prolonged contact may lead to drying and chapping of the skin. In case of contact, wash the skin with soap and water; remove and destroy saturated clothing. Clean up spills with rags, sawdust and af'KMtieni clay. Segregate these items for proper disposal. (See U.ijt* 6, "Disposal of Liquid and Solid Wastes".) Eye contact may n suit in painlul nutation but no permanent damage to tissues. If o>t-au-l gets m tho eyes, tlush with large amounts of water. As with a'l i-yo Inst j.J, tofer to a physician. To leliovo irritation, physi* r j'v. h.nc tisriI ait opthaimic anesthetic solution as well as opthalm.c cortisone acetate solution. In'u.uient cKiimiiK to askarel vapors will not cause ill effects. However, prolonged exposure lo high vapor concentrations should !>' auvdril II hot askarel must be handled in a closed or confined provide the area wnh mechanical exhaust ventilation - or HONS G73948 n wear an organic cartridge respirator approved by the U.S. Bureau of Mines. C. Precautions On Opening an Askarel Transformer: Askarcls of various compositional types are used. Undor arcing conditions the gases produced, while consisting of predominantly non-combustible hydrogen chloride, can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askarels and cellulostc or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas span with dry nitrogen before any work is performed on the apparatus. The American Institute of Electrical and Electronic Engineers Guide IEEE Std. 76*1974 gives more detailed instructions and guidance "For Acceptance and Maintenance of Transformer Askarei in Equip ment". This guide is published by the Institute of Electrical & Elec tronics Engineers, Inc., 345 East 47th Street, New York, New York 10017. We recommend that users of askarel transformers refer to this IEEE document. VIII. Avoid Environmental Pollution Transformer askarels contain polychlorinated biphenyls (PCBs) which have been used in the United States and elsewhara over ihe past 40 years for many industrial and consumer applications. During the past several years evidence has accumulated to indicate that PCBs are widely dispersed throughout the environment and that they can have adverse ecological and toxicological effects. The United States Government's Interdepartmental Task Foret on PCBs, Com*72*10419, in their March 20, 1972 raport titled, "Polychlorinated Biphenyls and the Environment", recommended restricting PCBs to use in capacitors and transformers. This raport is distributed by the National Technical information Service, U.S. Department of Commerce, Springfield, Virginia 22151. A document titled. "Guidelines far Handling and Dispose! of Capacitor and Transformer Grade Askarels, Containing Polychlorinated Biphenyls", has been prepared and is available from the American National Standards Institute, Committee Cl 07, 1430 Broadway. New York, New York 10018. Document number is ANSI C107.1*1974. (This guideline is being revised during 1976. The new edition should be available 1976/77). The scope, objectives and the composition of this committee are: ANSI Committee 0107 Scope: Procedures and guides for safe use. maintenance and disposal of askarel and askarel-soiked materials used in electrical equipment. Objectives: 1. Source of technical information and advice for Federal, State, local authorities and all others concerned. 2. Encourage development of suitable disposal facilities and keep all concerned informed. 3. Serve as the advisory group for United States participation in international organizations: CEE, lEC.CIGRE. Composition; Organizations active in or represented by this ANSI committee include: National Electrical Manufacturers Association, Electronic Industries Association, Institute of Electrical and Electronic Engineers, American Society for Testing and Materials. Electric Light and Power Association: Certified Ballast Manufacturers Association; Environmental Protection Agency; Olfice of Environmental Affairs; Genoral Services Admimsiialion; N.monjl HONS 0739*9 R\i">au of Standards; Department of the Army; Rural E U r.ti iftcal'on Administration; Division of Environmental R.'fi.uch, TVA; American Public Power Association, Water Poliuhon Comtol Federation; Food jnd Drug Administration; Nat.anal Fire Protection Association; Underwriters Laboratories; and several sections of the U.S. Department of Interior. The following are pertinent excerpts taken from the ANSI Guidelines for askarei transformers: V LABELING ASKAREL TRANSFORMERS (Pg. 16) 4.2.2.1 Now Transformers. All new transformers- that contain PCBs shall have a label oi adequate durability, permanently and prominently attached to the tank by the manufacturer, given adequate warning and instructions. A suggested /jM includes the following: CAUTION: The insulating liquid in this transformer contains polychlorinated biphenyls (PCBs). Care should be taken to prevent entry into the environment. In case of malfunction or leaks, consult the instruction manuei or the manufacturer. 4.2,22 In-Service Transformers. The transformer mam/* facturer should make available suitable labels with a similar warning as shown in 4.2.2.1 for use on existing transformers. 2. DISPOSAL OF LIQUID AND SOLID WASTES (Pfl. 15) 4.1.6.5.1 General. Disposal of askarefs and askare/soaked materials should ba accomplished by means in which there is no significant release of askarei to the environment. At present, disposal is accomplished by carefully controlled incineration of liquids and soaked software, and by com trolled landfill burial of apparatus and other hardware from which askarei has been previously drained and washed. Present knowledge indicates that proper incineration must involve e suitable balance between dwell time and temperature in the incineration plus oxygen availability and, finally, suitable scrubbers to remove the HCl that will be formed; for example, 2-second dwell time at 200CPF and 3i excess oxygen in stack gas, or 1.5-second dwell time at 270CPP and 2% oxygen in stack gas. These facilities should meet the applicable requirements of the state in which they are located end should control effluents within die limits set forth in this standerd. Controlled landfill or deep-well disposal can ba used where permitted by federal, state, and locel regulations. The ANSI Guide lists the locations of facilities that conform with the above requirements. Monsanto has such an incin erator at the W. G. Krummrich Plant. Department 831. Sauget. Illinois 62201, where arrangements can be made for scrap askarei liquid disposal for a modest fee. For disposal of solid scrap a controlled dry land fill can be used where permitted by Federal. State and local regulations. 3. CONDITIONING OF NEW OR RECYCLED ASKAREL <Pg. 1C) 4.2.13.1. Askarei Conditioning Equipment. The condi tioning umt should be located cither in the storage tank area or in the n-.un transformer manufacturing area for filling With ask.iri-f. 4.2.1.3 2 fuller's Earth. Conditioning of new askarei or recycled asi.ecl requires fuller's earth treatment. The spent fuller's ej'th m cartridges or hugs, wfien replaced, should be allowed to ihatn thoroughly over drip pans to remove as much liquid askarei as possible. The cartmige units of Steel mesh construction should Ik' placed in the "STEEL CON TAMINATED WITH ASK APE. i" container for disposition. Cloth fvjys tilled with fuller's earth should be placed in the SCRAP fHiRNAOLE ASKAREL WASTE" container for diqn*sdion. i ;* \ 1/ HONS C7395C 4. TEARDOWN OF TRANSFORMERS FOR REPAIR OR SCRAP <Pg. 16) 4.2.1.4.1 Drain all askarel from the unit either into J holding tank or reuse or into the drum labeled "SCRAP ASKARE L" for disposition, end then allow sufficient time for all of the askareI to drain from the core and cods. 4.2.1.4.2 Remove the core and coil assembly fiom the transformer. Sufficient absorbent material should be r 'ared on the floor to absorb any askare/ fluid that stdl drips from the transformer. 4.2.1.4.3 Place all materials in the appropriate salvage containers during the dismantling for later disposition. 4.2.1.4.4 All used materials, including rags, sawdust, tape. etc. regardless of quantity, shall be put into the appropriate containers for disposition. 6. TRANSFORMER DISPOSAL (Pg. 17) 4.2.3.6 The ultimate disposal of an askarel-filled trans former may be accomplished in either of two weyf (1) Complete drainage and dismantling with the proper disposal of the askarel and askarel-soaked components as described in 4.1.6. (2) Disposition of askarel transformers by means of junk or scrap dealers. This should be avoided unless a transformer is first drained. followed by soaking the interior with e suitable solvent. Accumulated liquids and waitings are to be disposed of as described in 4.1.6. IX. Expected Service Life Manufacturers indicate that properly designed and installed askarel transformers are expected to give trouble-free service for at least 30 years. Since their introduction in 1932. the manufacturers report finding the overall failure rate to be lest than 0.5% for all units under test and service conditions. The Edison Electric Institute's report (1956-1958) on their member utilities publishes the failure rate for askarel transformers as 0.13 per hundred banks per year. Mr. Frank M. Clark, who invented transformer askarels at tha General Electric Company in the early 1930s, made the highly pertinent comment based on his many years of experience with G.E. Pyranol (askarel type) transformers that - 'The important thing is to keep them dry - otherwise leeve them alone". These words of wisdom became especially applicable in more recent years when welding shut rather than gasketing became the main method of sealing askarel transformers. These units are sold with tha understanding that the liquid is in a normally hermetically closed system. X. General Characteristics of Transformer Askarel Fluid Appreciation of the following characteristics, as given in the IEEE Guide, leads to understanding the reasons for selecting dielectric breakdown voltage and moisture as the prime practical tests to iudge the quality of transformer askarel fluid. Also, due to these characteristics the power (actor of tiansformcr askaiel will he normally much higher than the corresponding values for mineral oil. In comparison to mineral insulating oil, askarel is a relatively polar mateiial. i.c., its molecules are dipoles, tree to rotjte jiound thru axes and responsive to orientation by electncal forces. Askarel also exhibits a much higher dielectric constant and capacitance than msuljting oil, and these differences must be kept in mind when interpreting electrical test data. Because it is relatively polar, and possesses high solvency power, askarel is much mure electrically sensitis.- than mineral Oil to traces of extraneous soluble {xil.M materials, jml consequently the choice of i 1i MCNS 033S51 construction.*) materials destined for use in askarel is very critical. This icnid.vdy u uMluctcd in the power fjetor and resistivity (specific rpvistaivce) of the askarel. It s important to note thjt, wih the exception of water, the dielectric breakdown vott.ige of askarel is not generally adversely affected by many of the soluble polar materials to which its power factor and let st-v'ty {specific res-stancs) are so sensitive. In fact, the dielectric breakdown voltage of askarel is somewhat greater than that of mutating oil. Therefore, the values assigned these dielectric fluids in newly supplied transformers are 30 KV mm. and 36 KV mm., respectively. As with insulating oil, askarel must be kept dty. It can pick up moisture from exposure to humid atmosphere. Under similar conditions of exposure, askarel can pick up nearly twice as much moisture when measured on a parts per million weight basts. XI. Sampling Transformer Askarel Fluid The following precautions about sampling are quoted from the IEEE Guide. "Representative samples, whether of the complete contents or only parts thereof, are extremely important from the standpoint of evaluation of the quality of the product sampled. Obviously careless sampling procedure or contamination in the sampling equipment wiil result in a sample that it not truly representative. This generally leads to erroneous conclusions concerning quality and incurs loss of time, effort, end expense involved in securing, transporting, and testing the sample. It is strongly recommended that all of the procedures and precautions outlined in the latest revision of ASTM D 923 (Sampling Electrical Insulating Liquids) be followed. "Because of the high specific gravity (relative density) of askarel (greater than 1), water and some other impurities are most likely to be found at or near the surface. The top sample, therefore, is considered to represent the worst condition." XII. Evaluation of Askarel Received in New Equipment Some users of askarel equipment find it desirable to make "as received tests" on ell equipment. It is quite common to use the dielectric breakdown voltage test and visual appearance as the most significant tests. If suitable equipment and trained personnel are available additional information may be obtained from the power factor, color, and moisture content tests. In sampling askarel contained in apparatus extreme care must be exercised in order to obtain a representative sample. ASTM Method D 923 should be followed. New equipment with askarel exhibiting the following characteristics is considered acceptable: Dielectric Breakdown Voltage Color Condition Visual Water Content Power Factor at 25* C 30 KV min. 300 max. (Straw color) Clear 35 ppm max. ' ASTM Methods D 877 D2129 D 1702 D 1533 0 924, D 150 *The power factor of askarel taken from new transformers, reactors and accessory equipment can reflect the presence of moisture, dissolved polar compounds, or other contaminants and may vary with the type of equipment from which the sample was taken due to the dilfeienl ratios of liquid to solid insulation and to the hujh solvency |>owef of the askarel. Given an acceptable vs .liei content and du/lednc bieakdown voltage of the askatel as indic.itetf .drove, a high power factor seldom impairs the seivMi'ahihty of the ask.net within father broad limits and is I MQNS 073952 indicative ol the degree of uxtunrout solub1- ;x>Ui m.-.i !-al% present. Recognizing t1.' rowbibiy '/ a w ute f jrge of r > r fjrt bring recorded for a^mt'l in new iijuiprrvMt, it is iMi'c.iM to i-.t.ioinh a Single limit wha'i would be jctvptjlj!-.* to both j:.J uteri fo< all applications. However, as a broad guide, j uwer taciort up to about 10'.- j: ?0'Cand 69 cycles |v* secomt ' riUI do not in general indicate any abnoimal contamination inovidmg that the Other criteria (water content, dielectric btcakd nvn volt. ^. etcj are met. Much higher power factors may indicate excessive contamination o< the ms.u>i,tlication of the sol'd materials used in manufacture in contact with the askarel and should be investigated. XIII. Dielectric Breakdown Voltage -- Moisture Relationship The dielectric breakdown voltage of askarel is highly sensitive to excess moisture; not sensitive to ordinary dissolved polar materials. While the dielectric breakdown voltage can also be lowered by severe arcing, askarel turns noticeably black or has particles of sooty carbon floating in it if arcing has occurred. Then the transformer should be repaired and the askarel replaced. If the dielectric breakdown voltage is checked periodically and decreases significantly - this indicates moisture pick-up. arcing, or both. When the dielectric breakdown voltage has dropped to 26 KV or less, an analysis for water is necessary. If water it found In excess of 40 ppm at room temperature, its source should be located and corrections made. When the moisture content approaches 125 ppm (saturation level at room temperature), the dielectric breakdown voltage of askarel drops below the value required for efficient insulating. The moisture content should not be allowed to rise over 70 ppm, sampled at operating temperature. If the moisture content is found to be in a satisfactory range and the dielectric breakdown voltage is low, the transformer manufacturer should be consulted. Table IV shows the relationship of dielectric breakdown voltage vs. moisture and Table V indicates the approximate water solubility limits in askarel and mineral oil. Table IV Relation of Dielectric Breakdown Voltage to Amount of Dissolved Water in Askarel and Mineral Oil Water Content (PPM) Breakdown Voltage (ASTM D877) Askarel Mineral Oil 0 70 KV 50 KV 20 55 39 40 47 30 60 40 26 80 38 22 110 10 5 fl 1 HONS 073953 Table V Approximate Solubility of Water in Transformer A'.kartl and Mineral Oil Amount of Water (PPM) Dissolved *C. Askarel Mineral Oil 30 -22 20 4 10 14 0 32 10 60 20 68 30 86 40 104 8 16 28 41 65 94 126 170 6 10 13 20 33 58 85 130 XIV. Turbidity ... may be the visual sign of undissolved water, or mav indicata din. Cloudiness may also result from cold precipitation of tin tetraphenyl "scavenger" that was used in the earlier Pyranol transformers. This scavenger begins to come out of solution around 15*F above zero. To radissolve it requires heating to 150-200*? and agitation. High dielectric breakdown voltage will quickly indicate that any turbidity present is not moisture; that the insulating efficiency of the askarel is still excellent. However, if the dielectric strength is below 26 KV, moisture should be determined, using the Karl Fischer method (ASTM D1533-60). The dielectric breakdown voltage test for eskerel serves primarily es en indicator for moisture. It is by fer the most importsnt maintenance test for transformer askarel. XV. Check Points for Maintaining Askarel Insulation A. General Considerations: Modern askarel transformers with welded construction or silicone or Vlton* gaskets (hand hole-cover, switch and terminal compartment covers) and with properly constructed bushings require little maintenance. With properly constructed trans formers. annual or semi-annual visual inspection and dielectric breakdown voltage test of the askarel fluid should suffice for routine maintenance checking over many years of service. However, many askarel units were installed in the early 1930s -- before the development of some of the better modern gasketing maiariafs and before improved designs were developed for sealing out moistura. Such early units should be, and can bt, modernized. Leaky or deteriorated gaskets should be replaced. If the askarel has become contaminated, it should be reconditioned. At the same time, a general clean-up of the unit and possible refinishing may be desirable. If it is not convenient to take an old transformer out of service for general repairs, leaky gaskets can be sealed temporarily by painting over the leaky area with epoxy cement. A sutvey ol users indicates a good number of early-built askarel transformers (over 20 years old! are kept in continuous service in criiirjl installations by the following steps (instead of modernization). The operating units are oqu>pf>od with compound pressure gauges (or rujdmg pressure above arxl below atmospheric. Positive *1 ladema'X nl C. I. Durum DcNomouit & Company, Inc, MONS 073954 picture is maintained on the 3tv:ll by intioducmg nitrogen jt ? to 3 pounds above a'mospheric. Regular workmen m the area d.nly record the temperature end pressure, If a sudden pressu>< drop s noted more nttrogert s introduced and the gjs-.eis arc ch* > k.-d for leaks with soap solution. Leaks are scaled by applying epoxy cement. I. Modern Sealing Procedures: Transformer purchasers should specify the following modern techniques for scaling: 1. Welding Construction: Covers, radiator connections, switch * and terminal housings, instrument connections, etc. should be welded. 2. Bushing Connections: A number of bushings have been developed to obtain e proper seal for the electrical connection through the tank wall. They are classified at follows: 1) Welded Type - (Bushing flange welded to lank wail) a. Cast resin bushing with a molded seal to the bushing stud and external stainless steel or copper flanges. b. Rolled flange bushing with the metii to porcelain seal at the cap and flange made by being rolled into grooves in the porcelain over silicone rubber rings. The seal between the cap and stud is made by welding. C. Porcelain or glass bushings with metal to glass or metal to porcelain seals. 2) Bolted Type (Bolted to tank wall) a. Cast resin bushings with cither cast or metal flangts containing recessed gasket grooves. b. Porcelain or glass bushings with flangts containing recessed grooves or gasket stop. The gaskets may be either of rectangular or circular eross-soction, usually % inch thick. Bushings with recessed grooves are suitable to use with cork, cork-nitrile rubber combinations or nitrile rubber as well as gasket materials such as silicone or Viton. 3. Small Size Connections: When not possible to weld, small size connection seals should be made with Flexitailic* stainless steel rings. The surfaces must be machined end parallel. The filler between the steol laminations of the Flexitailic ring should be either silicone or Viton. 4. Gaskets for Hand-Hole Covers: Modern design specified silicone gaskets. Such gaskets must be retained in a groove. The groove preferably is machined into the flange or cover. However, it can also be formed by welding concentric steel strips to the flange or the cover. Generally the gaskets should be 5/16 to 1/2 in. thick for covers, depending on the depth of the groove or stop. A rectangular cross section >t usually used. The silicone material should be Dow Corning No. 50 Silastic** or equivalent. This is a low compieiuon set material. For best scaling 20 25 * compulsion is recommended, with ample ctuaranco m the groove o> stop to allow for this compression. No cement is requited. With reasonahl'* care th-* gjskct is removable without damage and is reusuable. Silastic 50 is slightly swelled by askatel which contuiiut to the lightness of the seal. It ts not dctcnpr.iteil by jsk,.i. l fluid or vapors. It resists weathering and it u tln-rm.llv viand Tr.iHematk ol F IcmMlIit G.ivket Comp.my *Ti.itlcmark o> Uow Cmmrs) MONS 073S55 flexible at all operating temperatures. It is an excellent moisture barrier. NOTE: Dow Corning. Midland. Michigan will supply a list of Silastic SO gasket fabricators to all transformer manufacturers or users. They will also furnish technical data. See Appendix J: Seals. Properties and Procurements. C. The Older Sealing Arrangements: The older type gaskets consist of either cork or cork-nitrile rubber combinations or straight nitrile rubber. . 1. Cork-Nitrile Combinations: Covers for the main tank, hand-holes, switch and terminal chambers, relief diaphrams, ate., art held in place by studs welded to the flange or by bolts. The gaskets art cut with openings and placed over the bolts. Often Shellac (Westinghouse Style No. 1150419, or Oantral Electric Company's Glyptal* 12761 is used to cement the cork to the flanges. The following is recommended for sealing with the cork -- nitrile rubber combinations: Usa Armstrong NC-757 cork-nitrile material or equivalent. The gasket can be cut from a single sheet or by scarfing strips of the material. A convenient method for joining strips is to make a Keystone Type joint. Por this purpose, Westinghouse, Sharon, Pennsylvania, offers their gasket cutter Style No. 326 6614 G01, (about $15). The joints - and also the gasket - should be cemented to the flange, using one of the above cements. Excess cement should not b allowed to reach the interior of the transformer. Aftar installation and bolting, the outside edge of the gasket should be coated thoroughly with epoxy cement to increase waather resistance. This epoxy cement is a pasta to which a curing catalyst is added immediately before use. Typical are: a. Epoxy Patch Kit #1-C Hysol Corporation, Olean, New York b. Scotchcast** Resin *4 Minnesota Mining & Manufacturing Company Si. Paul, Minnesota c. Adhesive A-1 and Activator Type B Armstrong Products Company Argonna Road, Warsaw, Indiana d. Adhesive 9860-1, Synthetics Organic Company, Cleveland. Ohio, used with activator diethylene triamine (Carbide and Carbon Chemical Company) 2. Straight Nitrile Rubber: When straight nitrile rubber was originally used, invariably the gasket was recessed in a groove. This was to prevent gasket flow and to protect the material against excessive compression. Although this type seal was not eementud, the nitrile rubber gasket is not reuseablc. Since grooves or stops have already been provided for the nitrile rubber sojI. Silastic SO cjn be easily substituted and is recommended. This conforms with modern practice. XVI. Periodic Fluid Inspection and What Checkpoints Mean On a regular schedule - at six, nine, or iwi-lvc-month intervals - make a tim|ii-< visu.il instx-ction of your askarel insulation and run a dielectric breakdown voltage check. *Ti*1em.tiik a* Gencal Electric Cumnjny *' TijUtirMiK o< Minnesota Muting & ivunuiectunng Company 7:i) i HONS 073956 A. Visual Inspection: Askarel is a clear, faint yellow liquid. After longterm use tbit color may gradually intensity to light brown. The fluid should remain clear and free liom turbidity or cloudiness. Any color change - such as to a green, red or blue cast - indicates extraction of impurities (color materials) from the solkf insulation. If a distinct foreign color pick up is noted, check the complete range of electrical characteristics and notify the transformer maker. Blackening of the askarel may indicate an arcing condition. Other color changes alone are not danger signals since the dielectric breakdown voltage is not likely to be impaired. Dielectric Breakdown Voltage If the dielectric breakdown voltage has decreased significantly from the last inspection, or if it has gradually decreased below 26 KV range (at 25'C) - RUN A CHECK FOR MOISTURE. Use ASTM DI533 (Karl Fischer Method). The dielectric breakdown voltaga of askarel is the mqor indicator to the operating efficiency of your liquid insulation. Besides the visual inspection tests, dielectric breakdown voltage is the only test necessary to run on a routine basis. Well seeled askarel transformers have service records of 2S to 30 years on the original askarel. XVff. Inspection Checklist 1. If askarel is clear -- even though darkened to light brown, has no sediment or turbidity, has dielectric breakdown voltage over 26 KV -- give it the inspection "OK". 2. If askarel is clear, but has foreign color of blue, green, red ... it it "extracting color" from internal materials. This Is not, of itself, an operating hazard when the dielectric breakdown voltage stays ovar 26 KV and moisture remains low. However, this rare occurrence caffs for checking into the condition of the interior oorntroctioo end consulting the transformer maker. However, when sampling the fluid cere should be taken to avoid getting color into the askarel from paint that may be inside or outside of the sample valve. 3. If the moisture content is found to be above 70 ppm et operating temperature, then sampling should be dona at more frequent intervals to establish a possible trend, particularly on outdoor installations. 4. If askarel is clear, but dielectric breakdown voltage drops to 22 or lower KV, and moisture rises over 60 ppm when sampled et operating temperature ... the askarel is ready tor simple "refining". If the moisture is near the saturation level (about 126 ppm at room temperature) a thorough inspection should be made for water droplets in the transformer tank, end even for "globules" of water floating on the askarel surface. If found, the transformer manufacturer should be consulted for reconditioning both the transformer and the fluid. 5. If askarel it dark brown to black, if black particles of carbon are teen, and dielectric strength is low ... the askarel has been broken down by arcing. It cannot be refined and should be removed and incinerated under proper conditions. (See ANSI C107.1-1974, Section 4.1.6). If any of these five simple inspection tests appear out of the ordinary or the relationship between appearance and test values is abnormal, contact your transformer supplier for a complete analysis. Whenever a sample is to be shipped to Monsanto, please follow the directions shown undvr: "SAMPLING ASKAREL". MONS 073951 XVIII. Contamination in Transformer! Moisture, particulate matter and arced decomposition products are known 10 be serious contaminating influences on transformer askarel. The power factor test normally used for the detection of contamination in mineral oil filled transformers is of little use for this purpose in askarel filled transformers, due to the extreme effect of extraneous soluble polar materials. This increase in power factor as illustrated in Table VI has no adverse effect on dielectric breakdown voltage. Table VI Effect of Common Insulation Materials on Powtr Factor and Dielectric Strength (Heat Aged 96 Hours in Askarel at 100*C.) Materiel Immersed None (control) Black varnished doth Copptr Pressboard Manila paper Phenol formaldehyde resins Shellac Iron Synthetic rubber Askarel After Exposure Power Factor, Dielectric Percent at 60 eye., nxrc Strength 25*C. 1.0 35 KV 85.0 42 1.5 40 2.0 37r 1.6 39 1.6 41 6.0 36 6.0 39 70.0 39 Similarly, tract contaminants from commonly used construction materials can lower the volume-resistivity of askarel, without* effecting its dielectric breakdown voltagt. This is shown in Table VII. Table VII Effect of Common Insulation Materials on Volume Resistivity of Askarol Sample Volume Resistivity x 10 ohm-cm let 10CTC..500 Volts DC., 0,1" gap) 1. New askarel before heat aging 2. New askarel after heat aging 96 hours at 100*C 3. After heat aging with 1 iq. inch specimens of: s. Phenolic resin tap changer material b. Paper c. Grade A pressboard (tan) d. Grade A pretsboard (gray) a. Grade A pressboard, laminated strip f. Cotton wrapping g. Glyptel 1276 cement, cured 48 hrs. at 110^ 2,000 1,900 1.200 750 500 500 400 300 100 While trace contamination easily lowers volume resistivity from high levels, it is important to note that heavy contamination (as when arced) does not lower the resistivity below the order of 10 ohm-cm, at 100*C. The dillercm bchjvior of askarel vs. mineral oil in these respects can be summan/ed as follows: High power lactor and low volume resistivity in transformer mmeial oils arc commonly regarded as "danger signals" that the 0*1 hii d>'W*rio'.iU'iJ and broken down chemically or excessive moisture rs prevent. This is NOT TRUli of jsKjic-I liquid insulation unless the dielectric breakdown solt.iij'.* iv low oi the moistuie content is high. MONS 073958 Manufacturer; of askarei typ* transformers point rv.t that >\ >s o.ntt well known that aikarcl trjnsformers with j-kvi>r ,.t me askarei fluid m excess of 50 j at room trmp.*fatu*e a-.I 10 H/ . <; vmg satisfactory serv ce life. Mcv/'wer. tlve r* .1, to he .r wuntr t- both dielectric breakdown voit-rge and moisture arc at sat sfjetory (r.c v and do not show adverse trends. XIX. ASTM D3255 Method For Investigating The Combat* ibility of Transformer Insulation and Construction Materials in Askarels This method uses the change of electrical and/or chemical characteristics of transformer askaret resulting from its controlled exposure to insulation and construction materials, in order to evaluate their immediate major "contamination'* effect on the askarei fluid. Delayed or long time contamination effects may not be detected. The method also utilizes various physical tests on the insulation and construction materials alter controlled exposure to the eskarel to determine the compatibility of these materials with transformer askarei. Properly proportioned specimens of the insulation or structural materials are immersed in refined askarei for 168 hours at 100 * 1*C in a forced draft oven. Changes in electrical and chtmical properties of the transformer askarei are compared against a control tempi* of tht askarei treated in the same manner, in absence of the test specimens. Dissipation factor (ASTM D 924) change is one of the criteria used. The askarei fluid is refined by absorptive treatment to a dissipation factor level of 0.05 max. at lOOX and 60 Hz and 0.01 max. at 25*C and 60 Hz. Corresponding values of the askarei fluid after heating 168 hours at 100C in absence of a test specimen are 0.075 and 0.02 respectively. The maximum dissipation factor levels suggested for the askarei after heating in presence of the test specimen ere 0.20 at lOOX and 60 Hs and 0.04 at 25*C and 60 Hz. XX. Refining Askarei for Reuse A. Filtering Through Ory Blotter Paper to Remove Moisture end Extraneous Particles: Most operators prefer portable refining apparatus, such as a Plata press fitted with a doily, available from Sparkler, Mundelein, Illinois or General Electric Company, Pittsfield, Maaiachusetts; or the earthen cartridge filter type available from Industrial Filter Corporation, Lebanon, Indiana. Filter paper liners tor the plate press are available from Carl Schleicher and Schueil Company, Keane, New Hampshire and manufacturers of filter presses listed above. ' The fitter paper must be dried immediately before use. For best results, spread the paper for maximum surface exposure in a hot air circulating oven and heat it for 4 to 6 hours at 110*C. Circulate the askarei hot (but not over 40*C) through the filter fitted with the dry paper liners. After filtration the dielectric breakdown voltage of the askarei should be 35 KV minimum. PRECAUTIONS: 1. Filtering should not be done when the relative humidity exceeds 75%. 2. Any flexible hoses end gaskets on the refining equipment should be lined with or made of materials that will nut be softened by contact with askarei fluid. (Materials lined with Silicone, Viton or Teflon* or flexible m (jl materials arc suitable.) Trademark of E. I. OuPont DeNcmours A Company. Inc. MCNS 073359 TABLE VIII Guide to Rate of Dissolved Water Removal By Filtering Askarel Through a Paper Press Passes Through Paper Press Water in Askaret PPM 0 115 1 35 2 22 3 - 18 4 12 10 6 10 B. Disposal of Solid Wastes: The ANSI guide C107.1*1974, Section 4.1.6 gives detailed recommendations. C. Solid Insulation Requiring Drying: If the solid insulation of the transformer requires drying, consult the transformer manufacturer or an apparatus service shop, as in such case oven drying is preferred. D. Earth Treatment for Maximum Improvement of Power Factor and Vofuma Resistivity: Wa question whether pumping and filtering the fluid solely to aehleU a change in power factor or volume resistivity alone is iuitifitd in today's ecological climate regarding PCBs. We recom mend that in these situations the original transformer manufac* turer ha contacted. 1. Procedure: Tha askaral liquid should be relatively dry prior to the following earth filtration. As a coating on tha filter paper surface use finely divided Attapulgus* clay or Fuller's earth dried and activated by hailing for 12 hours at 300-35CFF immediately prior to use. The amount of earth used should be 0.1 to 0.2 percent by weight on the weight of the askarel to be treated. Askarel weighs about 12.5 pounds per gallon. To deposit tha earth evenly, stir one-third of the earth with a small portion of askarel in a dean container. Pump the mixture through the filter and follow with two more one-third portions. Then circulate askarel taken from near the top of the transformer, pass it warm (not over 55T) through tha earth-coated filter and feed back through the bottom transformer outlet. Continue circulation until the fluid is dear and test shows that (he electrical properties are fully restored. 2. Effect of Earth on Removal of Scavengers Only slight and insignificant loss by selective absorption of tin tctraphenyl and epoxides occurs when askarel is refined by treatment with 0.1 to 0.2 percent by weight of earth. To remove significant amounts ol the scavengers requires repe titious treatment with much latger amounts of earth. *1i,nr*naik ol EnmM.v<J Mineral! and Ch*fnic;Pf Corp. HONS 073960 B. Mjke sure that th askarel is at least as waim as the surrounding <r. (Cold liquids can condi-nse moisture from humid air.) C, When sampling askarel from transformers, it is best to take the sample when the unit is warm and operating at average or maximum load, especially for a check on moisture as reflected by a dielectric breakdown voltage test. Sampling the warm askarel more truly represents its condition during operation. Experience shows that water will migrate from a transformer's solid insuletion to the askarel liquid and vice versa, depending on temperature. Therefore, when the transformer is hot, the moisture ll most likely to be found in the liquid. This accounts largely for periodic variations in dielectric breakdown voltage. For example, a relatively high dielectric breakdown voltage may be found during winter months and a relatively low dielectric breakdown voltage during the summer months on samples taken from the same unit. When testing has been completed, the remainder of the fluid temple should be destroyed by high temperature incineration described in Section VIII. MQNS 073961 CQAS AsIk&ireH F7* rTn^ <-Tl C?;-*v~i dLi. LitM^ Vvi k-' V V l~ * n rrri 9 __ ri ppi^r, ;| C^Liuw Lw^..--uJ Chzziz'.zzza I. Introduction High voltage leads are usually connected to askarel or mineral oil-filled network transformers and power centers through terminal chambers and* switches. In some cases terminal chambers are not used, and the high voltage leads are connected directly to the switch terminals. They may be filled with either askarel or mineral oil. Switches are usually rotary or drum type fitted with a revolving block and portelain unit as the principal element arranged for three-phase service. Askarel transformers with attached switches have been in use for about 30 years. When they were first introduced, the availability of insulating and gasketing materials was rather limited and evan the best materials at the time had no service history. As a result, inadequate gasketing materials such as cork, nitrile rubber, and nitrile rutober and-cork particles were used. While satisfactory for a limited period of time, these'materials cannot be depended upon for the expected long lift of the equipment. The terminal chamber is usually above or below the switch compartment and separated by a steel well through which the bushings are inserted. When bushings are properly selected and correctly installed, there is no leakage from one compartment to tha other. With poor bushing seals, and the terminal chamber above tha switch, potting compounds or cable oil can seep into the askarel. Whan the terminal chamber is below tha switch, askarel can drain into the terminal chamber. II. Sources of Contamination There are three possible sources of contamination for askarel in switches end terminal chambers; they rank in this order of frequency: (1) water entering through poor gaskets; (2) decomposition products from arcing when switch is used to break magnetizing current; <31 entrance of pothead or cable compounds through leaky bushing seals. Unlike an askarel transformer where the amount of contaminant is likely to be very small (probebly only trace amounts) in relation to tha volume of askarel fluid -- in switches or terminal chambers with faulty seals, the amount of contamination can be relatively large. Experience has shown that, based on the number of installed skarel-switch units, the percentage of failures is extremely small. When investigated, it has been found that most failures originate in the switch chamber. Water is the chief source of contamination. However, heavy contamination of askarel with petrolatum and asphalt material, due to leakage, have caused a few failures. Petrolatum is used frequently for filling terminal chambers. When either cable oil or petrolatum seeps into askarel, no great harm results. The fire resistance wifi be somewhat decreased and power factor of the askarel will increase with an accompanying drop in resistivity. While highly undesirable, it is doubtful that failure of the unit results. Where asphaltic compounds are used in place of petrolatum, the danger It increased somewhat because asphaltic contamination may cauae excessively high dielectric losses in the askarel. When the terminal chamber is below the switch chamber, the potting compound can bo contaminated by askarel if the bushing ii-jlt are leaky. This is undesirable because the askarel will increase the power factor and conductivity of the potting compound or cable ml and develop heat from dielectric loss. If this mixture is drawn into the cable HONS 073962 Irv.u'T'on, * cable failure h likely. This again emphasizes the importance of light bushing assemblies. III. Scaling Switches and Terminal Chambers Prop''! bushing construction, use of Silastic seals and welding wherever po'vhl*? is highly desirable (as eovored in Section A|. Where an elastomeric seal is to be used in contact with both askarel and petroleum oil, DuPont's Viton is suggested. For new equipment the user should specify these modern sealing arrangements to keep out contaminants and minimize maintenance. IV. Askarel Used Under Mild Arcing Conditions . The IEEE Guide for Transformer Askarel cells attention to the following: * "Askarel is used, to some extent., in apparatus where it is subjected to light intermittent arcing, such as in self-contained induction regulators, where operating switches are continually producing slight arcs, in transformer de-energizing twitches, etc.. Under normal conditions, deterioration of the askarel is very slight. However, improperly adjusted or defective switches in this type of apparatus can produce excessive and prolonged arcing and accelerated deterioration of the askarel. It it recommended that whan iskaral it used under these conditions, checks of the liquid, specially for moisture end dielectric breakdown voltage made more frequently than when it it used only et coding and insulating fluid. Deterioration of this type it indicated by e blackening of the liquid. It can usually be reconditioned at previously described. Special attention should be given to maintaining the scavenger at the appropriate concentration." V. Maintenance for Askarel Filled Switches A. Switches used for grounding after power source has been de-energized will not undergo arcing. B. Switches interrupting magnetizing current will be subject to arcing; the amount of decomposition wilt depend on power interrupted, time and frequency of operation. At a general rule, the liquid should be checked after 5 to 10 operations. 1. On newly installed switches, check the askerel et 3, 6 end 12 month intervals: if found satisfactory, check once annually thereafter. With proper attention to the gasketing of covers and bushings, experience will probably indicate that lest frequent inspection is warranted. . 2. Check eskerel for: a. Dielectric breakdown voltage (ASTM D877): It should be 26 KV minimum. If dielectric breakdown voltage is low, confirm pretence of water by Karl Fischer method ASTM D-1533. Filter to remove moisture. Dielectric itrength should then be 30 KV minimum. b. Presence of carbon from arcing: Fluid should be relatively free of carbon. If badly arced and very block, replace fluid. If only minute amounts of carbon are present, filtration is recommended. Check power factor of liquid (should not be over 5% at 25'C and 60 cycles). Flush out switch chamber with several gallons of fresh askarel before refilling. 3. If there is discoloration. hiQh power factor, detectable change in specific gravity or refractive index, or if fluid flashes below 25frF, there is a possibility of seepage of potting compound into the switch compartment. In this case, correct any leaky bushing seels with proper replacements end fill with new asketel. 4. If terminal chamber is below switch, chTtk potting compound for presence of askarel (can usually be detected by odor or by an increase in specific gravity). If askarel it present, correct any leaky bushing teals with proper .(placements, and renew compounds. 6. Examine cover gaskets visually. Deterioration can be detected MGNS 073963 by iv *'.r'j j.-j i r,u Kr-g of the exposed edge. In jci u< i-\> . '.f;<. jt'on, liquid s...'pjge is usually present. 6. C- s ujr fit gland of switching shaft. II k*>.. }. (vpdck with aS.la'i'C nng type gasket. VI. Askarel Under Excessive Temperature or Fault Conditions The IEEE G'.j-I. o'-.o points out that. "Chfotob i-wvnes usrd m transformer eskarels begin to boil at temp- ri'uf' '. of about ?0b!C. under atmospheric conditions. If the matcti.ii is lu'-Mrd *o such high temperature in a seeled system, . ptessutt ti.' ; tom. Pi'.ssurc wih also develop in the system if the askarrl is a.-cud sufliccntly to generate copious hydrogen chloride gas. "Theiefoie. it is recommended that wherever possible, seeled tkarcl-filied equipment be provided with pressure relief devices. These devices must be large enough to provide immediate relief at a definite pressure, and to prevent further build up of pressure if decomposition continues. It must be remembered diet the presence of devices of this sort does not necessarily preclude the rupturing of containing vessels, since pressure build up can be extremely rapid under violent arcing conditions." TTmEdlyci IHIaiEilBiinig I. Inhalation At ordinary temperatures the chlorinated biphenyls in Askaaef have not presented industrial toxicological probltrm. The hazard of potential toxic exposure varies with their volatility: the lower-chlorinated, more* volatile ones present more of a potential problem from the standpoint of both inhalation and skin contact. Whan Askarel fluids art used at elevated temperatures, engineering controls mutt be applied, either by the use of closed systems or by effective local-exhaust ventilation together with general workroom exhaust. Vapors of Askarel at room temperature should not be breathed In a confined space, and no vapor of any fluid evolved at elevated temperatures should be etlowed to be dispersed Into the general workroom. Inhalation tests on animals indicate that the maximum safe concentretion of vapor is in the range of from 0.5 to 1.0 milligram par cubic meter of air. The threshold limit value (maximum allowable concen tration of an 8hour working dayl set by tha American Conference of Government Hygienists are 1.0 milligram of tha lower-chlorinated biphenyl compounds per cubic meter of air and 0.5 milligram of the more-highly-chlorinated compounds, per cubic meter of air. II. Skin Contact Prolonged or repeated skin contact with the Askarol fluids must be avoided by the use of gloves and protective garments, because of the possiblo occurrence of a condition called chloracne. Although reports of this condition caused by Askarel are rare, it can be produced by excessive skin contact. II the fluid is spilled on the skin the Skin should be washed in the usual manner with a soap solution. A burn caused by contact with a hot Askarel should be treated like any ordinary burn. For disposal instructions of Askarel fluids, see Section A - VIII, p;'9* 6. HONS 073964 Transformer users not wishing to make their own fluid analyte* can obtain the service from Monsanto. Simply contact Monsanto and specify what analyses are wanted. You will he sent the proper-sited, clean sample container, fitted with a proper label. When you receive this, carefully take your sample (following tho procedure for sampling in this Qutde). Send the container to Monsanto's laboratory. Charges listed include sample container and laboratory costs. The charges are those in effect August 6, 1976, and are subject to change. * Types of Analyses Available Analysis 11 ROUTINE MAINTENANCE CHECK Total Charge: $35.00 Per Sample To determine the general condition of the fluid and find whether further analysis is necessary, (one-quart sample required) Properties Tested Dielectric Breakdown Voltage Color and Condition Moisture You will be notified of the results of this test. If further testing is indicated, and you want a complete analysis, you will be sent a flvt-pint sample container. This sample will be used for the following series of tests: Analysis 2) COMPLETE ANALYSIS Total Charge: $165.00 Per Sample II) To determine the extent of fluid contamination, (2) earth refinement to determine whet degree of restoration of electrical and Insulating properties it possible, (3) check test to see how the fluid responded to earth treatment, a) Complete Aneiytii: to determine the extent of contamination Proparties Tosted Free Chlorides Color and Condition Aridity Specific Gravity Dielectric Breakdown Voltaga Refractive Indox Power Factor, Dielectric Constant, and Resistivity Water b) Earth Refinement Response: Consists of treatment for 2.5 hours at 50-60"C. with 0.1 to 0.2 percent by weight of properly conditioned Attapulgus day and than filtration through dry filter paper. c) Analysis Aftar Laboratory Earth Refinement: Properties Tested Acidity Refractive Index Dielectric Breakdown Voltage Water Power Factor, Dielectric Constant, and Resistivity Free Chlorides You will be notified of the results of this test series on your sample. Then after refining your entire transformer fluid fiH you can ehack on the results by requesting the following analysis: Analysis 3) ANALYSIS AFTER EARTH REFINEMENT Total Charge: $70.00 Per Sample (This charge will not apply when analyses 1 and 2 have already been made.) To determine whether the entire lot of the askarel fill responded to the same extent as the laboratory sample. Ifive-pint sample required) Properties Tested Free Chlorides Color and Condition Refractive Index Acidity Dielectric Breakdown Voltaga Water Power factor, Dielectric Constant, and Resistivity To arrange for the tests described above write to the following address: David Wood Monsanto Industrie Chemicals Company 800 North Lindlvrgh Blvd. St. Louis, Missouri C3IC6 S.mpU'i to l*' tested >hovild be dearly marked lor identification and sent directly to: f.Vmanto Company Kftimmnch Liluxatory i, ISI.mut icVOl ion J. A. Gloockner RONS 073965 ! j 1 | APPENDIX A AtkariM and Composition of Arc Formed Gas: Askarel insulation is one of the most inert, chemicallystablc heat rc- it.tnt. non corrosive liquids known. It writ not break down, oxidize or sludge when exposed to air and hich temperatures, l>OC. or even somewhat higher. Arcing, however, wilt break down the compound to liberate some hydrogen chloride and small amounts of carbon. APPROXIMATE COMPOSITION ARC-FORMED GAS FROM TRANSFORMER ASKAREL BLENDS ASTM TYFES D AND G ONERTEEN 70-30 AND PYRANOL A13B3B-3, RESPECTIVELY) Gas carbon monoxide carbon dioxide oxygen inert gases hydrogen chloride (note the absence of phosgene) Amount 0.3% 0.3% 0.6% 1.5% 97.3% This re formed gas from ASTM Type D and Type F transformer askarels is non-flammable and non-combustible. For att practical purposes, the amount of gas liberated from askarel under a given set of arcing conditions is about 100 cubic centimeters per kilowatt-second. APPENDIX B_________________________________________________________________ SOLUBILITY OF GAS IN TRANSFORMER ASKARELS ASTM TYPES D AND G Carbon dioxide Air Nitrogen Hydrogen chloride1 1 In absence of scavenger Percent of Gas By Volume Corrected to: 25*C 760 mm Q*C. 760 mm 25-C 71% 6.7 6.0 37.8 100-C 47% 4.9 4.8 60.9 25*C _ 5.8 5.5 - 100-C 6.0 4.4 - APPENDIX C________________________________________________________________________ EFFECT OF TEMPERATURE ON DIELECTRIC BREAKDOWN VOLTAGE OF ASKAREL Temperature *C -60 -40 -20 0 20 40 GO 80 Dielectric Breakdown Voltage ASTM D877 67 KV 63 57 55 50 50 48 45 HONS 073966 C * APPENDIX D COMPARISON OF THE APPROXIMATE VISCOSITY IN SAYDOLT UNIVERSAL SECONDS OF TRANSFORMER ASKARELS AND MINERAL OIL Tmp.*C -20 0 20 40 60 80 100 Pyranol A13833-3 1,000 100 70 45 39 34 . 30 10-C Mineral Oil 1,000 150 88 49 40 34 30 Inerteen 70-30 2,800 196 86 50 40 38 33 APPENOIX E THE DENSITY OF INERTEEN 70-30 AND TRANSFORMER PYRANOL A 13838*3 Approx. Density gm/cc. Ttmp.-C 0 20 40 60 80 Inerteen 70-30 1.574 1.552 1.529 1.607 1.485 Pyrenol A1303B-3 1.577 1.555 1.532 1.610 1.488 APPENDIX F Ths thermal conductivity values of transformer Pyrenol A13B3B-3 t 27*C end 5S*C ere 26.2 and 26M x 10* calories centimeter*'1, degrees centigrade*1, second*1, respectively. Or, approximately 0.06 BTU per (hr.) (tq. ft.) pf.) per foot. This same approximation applies to Inerteen 70-30. APPENDIX 0_________________________________________________________________________ Heat Capacity Over the temperature range of 25* to 125*C the specific heat of transformer askarel is dose to 0.30 calories per gram per degree. APPENDIX H__________________________________________________________________________ Coefficient of Expansion The average coefficient of expension of transformer askarel over the temperature range 20 to 100*0 is 0.0007 cc/ccfC. One gallon would increase to 1.056 gallons on heating from 20 to 100*C. APPENDIX t Fire Resistance Askareli of various compositional types are used. Under arcing conditions the gases produced, while consisting *of predominantly non-combustible hydrogen chloride can yield varying amounts of combustible gases depending upon the askarel type. Insulation systems incorporating these askareli and celluiosic or other organic materials may, when arced, produce gaseous mixtures which are moderately flammable. As a precaution, such gases should be removed from the askarel by bubbling dry nitrogen through the askarel and flushing the gas space with dry nitrogen before any work is performed on the apparatus. 4 mcns APPENDIX J tacit. Ptopottics and Procurement Dow Corning Corporation. Midland, Michigan with Diltrict! It Atlanta, Boston, Chicago, Cleveland, Dallai, Lot Angafet, New York City, Washington, D.C. and Toronto hat available Bulletin 09-019, August 1962 entitled "Silastic Oetign Data". This lists the gasket labricatort throughout the country from whom the "SHattic SO" gasketing can be purchased in sheet, extrusions or molded shapes. - Generally, SHattie BO sheet goods are stocked by local die cutters, hence, could be generally purchased locally. Usually small guamltiet of gaskets are die cut. If larger quantities are needed, tools are made of the same type used to cut other tfattomers. Where the gasket It extruded for fitting into a machined groove or between gasket stops, Dow Corning advises use of e scanted loint. This foint is then cemented using Oow Coming's Silastic 140 (dear) or their RTV 731 Iwhite) materials, which air cure. Dow Coming points out that die local "rubber" fabricators purchase the Silastic 50 in billet form. This is worked on a roll mill In preparation for sheeting or extrusion. Then to obtain the desired physical properties the fabricator must oven cure die Silastic 50 for 24 hours at 480>F. SPECIFICATIONS* ASTM DB76 ASTMD412 ASTMD412 ASTM D396 Color Specific Gravity at 77*F Hardness, Shore A. Scale Tensile Strength, osi. min Elongation, percent, min Compression Set after 22 hrt at 30CPF, percent, max White 1 JO+ 0.02 45 to 60 800 250 30 *AN physical properties measured on 0.075 inch thick samples molded 6 minuter at 240"F, and oven cured 24 hours at 4B0f. APPENDIX K___________ __ _______________________________________________________________________ rwun I ehel The following or equivalent caution statements should be fixed on all containers of transformer eskweis and dw trans formers themaelvea-. TMl product contains Polychlorinated Biphenyls (PCBs). Care should be taken to prevent entry into the environment throudh spills, leakage, use, vaporisation, or disposal of liquid or containers. Avoid prolonged breathing of vapors or mists. Arold contact with eyes or prolonged contact with skin. If skin contact occurs, ramose by washing with soap aid water. Following eye contact, flush with water. In case of spillage onto clothing, the clothing diould be removed at non at practical and the skin washed. Dispose of any contaminated materials at suggested in the American National Standards Institute document Cl 07.1, "Guidelines for Handling and Disposal of Capacitor and Transformer Grade Aekareis, Containing Polychlorinated Biphenyls". Monsanto MONSANTO INDUSTRIAL CHEMICALS COMPANY FUNCTIONAL PROOUCTS GROUP 900 N. UNDBE RGH BLVO. ST. LOUIS, MISSOURI 93169 The information herein regarding obtaining optimum results from askerel fluids in your transformer has been accumulated by Monsanto for over 40 years from the experience of makers and users of atkarel transformers and it is believed will be helpful. Nothing herein dull be construed at applying to other then atkarel insulation. Data and maintenance suggestions herein do not apply to the other components of the transformer. All operating and maintenance suggestions recommended by the manufac turer of the transformer should also be carefully followed. Because these maintenance directions apply only to the atkarel Insulation, Monsanto disclaims any liability for damaga to property or in|wy to persons arising from transformer operation. RONS C73968 US CUSTOMER SERVICE CENTERS A*ft0*. ONTO 44399 SOSmrtfmOo Drko 5tSwiiNiir,w ATLANTA. OSONOIA 90999 T*. (400 43+4949 HOUSTON, T9KAS TT009 19009*4 CM T**m TOL (71919919090 L09AN0SLSX CALtfOANIA 1491 Dftv Jtreer mmrt 9mi9. CHNwmk 99009 m (71419399100 NSW YONM. NOW TOOK 10099 1114 Ao99m*t tht Ammfmt TO. (91917910000 ST. LOWS, NtSSOUNI 99199 m (910 09+1000 INTE RNATIONAL OFF ICES AmONTlNA Mmmhi ArsmOm XAI.C wwAfrU*XiS.llL?n trm* 1 AUSTRALIA 9m Tstm, frkm Om 910*. ioi r------------- SOTmtS+m " OoSSS'** fmoiNwSm 11111c. AOaiom A A Sou 99k NmONm Count OmmtOmO. Ammtk 4907 AUSTMA 91*m*to* OnkN A*9tpt* AlOSOWkm.Amsmk Mmtmts Sm*m XA AmnmOt TOmnm 97+979 9* 1109Otfook. Orto^on 9NA9IL MMriii Mmmm ink. ftm minfh foot ftmn 9m Amo. Onto 01990 Mmtmn CmtOo LlO. in Otmorn Oh4. AmM, pftnn*. QsitsM . _ . *0$ Lot. lOOfmh 9mm. Sum 701 Wm Ymtmm. OX.. GmoOo CHIU tOsmmntm CM* OmnwW # LmtwOt SOitkk Sworn Otkim 099 Gollo tuoOO 337 OrnttofoOfCMo COLONS!A Otoiwnn COiomOfom trm. Corroro 14. No 77 -09 OSNMANK Motuonto AX 0 Hytonttoonifom OK 1544 C ` St SALVAOON Mimmtitw Cmtrommrkm (St Sotmdort SJL SOffiMAhi STAvmiOtOmyCNksSmm fte* 9m SsbmOor. SISNnOmr FSDSNAL NSfUSUC Of OSNMANY 0-4000OrmMOorf. TtOmst NmrbtkM Ommmv Ar*s4im*sw OC 30 00100HskkAt to fktmO fNANCS $mtm ObnwttW SJL OrmO'Arsmsm TSfnkmfrmm OUATSMALA SOHkkCsm TsAmUOsTtl Zm*9 Omtsmsk PIT, Omtmmk ONOKONO Mhumid fm Sm L* Ifcwefmewc Mmtm, 2*0 fkmt SOCwniAmomm HtooKono NktOk Chsmksk LtO. NkksthlOMm*w 119+nn NX. OmkrO Smm Otmktv 400001. H*Ok MktQk Chwmkak LtO. 19 N0mOmmOt kmttmfm NO. oomm 700001, ktok tttmOk Chsmksk LtO 910911 LkfhJCtmty somt mom 900001. OtOk MkOk Chsmkth LlO. 90 Amt AU Hom NtmOsmt 110001. tnOk mOONSSIA f. T. khmmm fm Sketrmkt 191 Of. Or SNmOH JNtmw. tnOmwk ITALY Oktmnm hs'isns XpJL Vkmkhkm Okkt mm4 90194. tntf ktmmnw Jspm LtO. Aoom 917. Shk KMvmi 9M+ +1. klsnmmcki J*ww CAtymmrn. r**r, Jwm MALAYSIA Mmtmw fm fitflML (Nskyus Ormtht 114. Jstm Smimwi fttstm* Mrs. Sstsnffm. Mstsvtk MSXICO Mmwi* Comsrtkl S.A. OsC.V. Thkn We. 949 A*M*ce f. O.F., Msnkm NSTHSRLANDS Mmtmts XV. N4tmo. me NSWSSALAND Mmtmm Nm ZmmO LlO. 19 Qnst Sewtft NmO AmektmO t, Nsw imtmO NtCANAOUA lOmtmi* (Nkwnpmt XA f.O.944 999 NONWAY Mmtmn Norm AX fnOOkmwi* 11 Oskt.K fHtUfftNSS MWMMtfp NttHmksi toe. som 1101 Smrnltr om19 That OTOOAyskAv*. musti turn o-TOOkftwkmm fUSNTO NtCO Mmsmw fymw Nkm Cw>n)> NkfkOma.hmmNtm SINCAfONg - ^ X+w+m Crnwmp tfnJLW. NOW 709 CNmv 9I0+. TOt ffmr 9hmt SkrtiN. Slnmfin 9 SOUTH AFRICA Mmtmw 9mn* A+im (ftyJ LW. limftmr.SmOtmCnr 9Nk Mmmnw tSmks XA ' MM >f4*e*r 9WSOSN Shmmw fSsmWmrkt AS XMhmrmnmmt 97 SWIT7SNLANO Monmtte (Sotml XA TAIWAN tOmmnm fm Sm LtO. MChmtf Am Sm NmO, < THAILAND Mmwim ThsftmOLtO. $0 Stmt, Ksmmkij 9*0*. ITOSOcm NmO UNITSO KINGDOM Mommto LtO. 10-19 VktorkSkwm LmOm SWIM ONQ Si^mo VSNEZUSLA Nonmnto (Vmmmkl CA Tomfhstptfkm94 fkn Vmttmk Cmsern tot. Vmwmk MONS 073969 Monunls InduUrM Chamicali Co. / A Unit o( Monunto Company / *00 N. Llndber^t Nvd.. SI. Loull. Mo. U1M UMO IM