Document 93Oo0BGkD0Zx5JaELnqXraZNe
HEATING VENTILATING AIR CONDITIONING' GUIDE 1942
Table 6. Coefficients of Transmission (U) of Frame Interior Walls and Partitions0
Coefficients are expressed in Bln per hour per square foot per detree Fahrenheit difference in temperature between the air on the two sides, and are based on stiU air (no wind) conditions on both sides.
TYPICAL CONSTRUCTION ^TLA/TER. wroiy
1.
*ru rtt a #*/e^
Type op Wall Wood Lath and Plaster On Studding Metal Lath and Plaster* On Studding Plasterboard (X In.) and Planter*
On Studding
Plasterboard (% in.) and Plaster4 On Studding--bright aluminum foil ce mented to plasterboard on surface nailed to studding
H in. Rigid Insulation and Plaster4 On Studding
1 in. Rigid Insulation and Plaster4 On Studding
IH in. Corkboard and Plaster4 On Studding
2 in. Corkboard and Plaster4 On Studding
Wall No.
Single
Partition (Finish on One Side or Studding)
DOUBLE PARTITION (Finished on Both Sides or Studdino)
Air Space Between Studding
Gj?srFlaked
Between Studding
Rock Wool Fill6
Between Studding
Flexible
Insulation Between Studding (One Air Space)
A 77 0.62 78 0.69 79 0.61
B 0-34 0.39 0.34
C 0.11 0.11 0.10
D 0.076 0.078 0.075
E 0.21 0.23 0.21
80 0.42 81 0.35 82 0.23 83 0.16 84 0.12
0.24
0.16
0.18
0.033
0.12 0.066
0.081
0.052
0.063
0.045
0.063 0.054 0.044 0.038
0.14 0.097 0.070 0.057
Computed from factors marked by * in Table 2. Thickness assumed in.
'Plaster on metal lath assumed X in. thick. ^Plaster assumed X in. thick.
Table 7. Coefficients of Transmission (U) of Masonry Partitions*
Coefficients are expressed in Bttt per hour Per square foot per degree Fahrenheit difference in temperature between the air on the two sides, and are based on still air (no wind) conditions on both sides.
TYPICAL CONSTBCCTION
0\A/CtU.Y^
m
Walls
Walls
Plain Walls
Plastered
Plastered
No.
(No Plasteb)
on One Side
on Both Sides
Type of Wall 4-in. Hollow Clay Tile 4-in. Common Brick 4-in. Hollow Gypsum Tile 2-in. Solid Plaster
85 86 87 88
Computed from factors marked by * in Table 2.
104
A 0.45 0.50 0.30
--
B 0.42 0.46 0.28 --;
C 0.40 0:43 0.27 0.53
CHAPTER 4. HEAT TRANSMISSION COEFFICIENTS AND TABLES
O O V a
a
4e>
V JS
k a
e* c r
8
J3
k
o k V 3
<0
tc .G
i C ;c i-Sig ! 2:g !T'.; j63
J 3 :i
i Sc 5
105
separated from la th and plaster ceiling by 1 in. furring strips. B rig h t alum inum fo il cemented to plasterboard