'840
CHAPTER 42
1949 Guide
sorptive materials installed in the duct system or. by special constructions designed to absorb sound. Experience has shown, for example, that where ventilating re quirements permit, introduction of ah expansion chamber or a change in area in the duct will frequently provide further reduction in low frequency noise.
DESIGN ROOM NOISE LEVEL
Measurements of noise levels have been observed by several investi gators in various rooms and locations and are listed in Table 1. The
Table 1. Typical Noise Levels*
Rooks
.Voisa LKm xs Dsczbszb to bb Anticipated
Min. Representative Mai.
Sound Film Studios.__________ -- - ....... ......--:--
Radio Broadcasting Studios..
Planetarium........................................................ ........................
Residence, Apartments, etc.....
----
Theaters, Legitimate.-
--
Theaters, Motion Picture-
Auditoriums, Concert Halls, etc.
Churches______
--
-------
Executive Offices, Acoustically .Treated Private Offices
Private Offices, Acoustically Untreated..
General Offices....
.....- ~
Class Rooms___
_____
Libraries, Museums, Art Galleries..
Public Buildings, Post Offices, etc.------------------------------------
Small Stores.-
--------
Upper Floors Department Stores. ____ _
Stores, General, Including Main Floor Dept. Stores.--
Restaurants and Cafeterias.------------------------------------------------Banking Rooms-
Office Machine Rooms--.
10
10 15 33 25 30 25 25
30 35 50
25 30 30
45 30 40 40 50 40 50 . 50 65 60
14 14 20 40 30 35 30 30
38 43 60 40 35 40 55 35 50 50 60 50
60 ' 55 77 70
20 20 25 48 35 40 40
35, 45 50 70 55 45 45 60 . 45 60 55 70 60 70 60
. 90 80
Vehicles
Railroad Coach........... ..............-...... -.....--
Pullman Car___
__ .
-
Automobile__ --.
Vehicular Tunnel--
n
................ -
--------
\
60b 55b 50 75 75
. 70 65
65 " 85
80
80
. 75 80 95 90
These values are tentative.- More detailed measurements by D. F. Seaoord. Bell Telephone Labora tories (Journal Acoustical Society of America. Vol. 12. pp 183-187. 1940) Rive average values and stand ard deviations of room noise in residences, offices, stores, factories, etc., in large,American cities.
* bFor train standing iq station a level of about 45 db is the niaadmum which can ordinarily be tolerated.
values given were determined with the air conditioning or ventilation equipment out of operation, and with all windows and doors closed simu lating the conditions of an actual installation. This is an important consideration, since, in offices or stores adjacent to busy thoroughfares the difference between the typical noise level in the space with the windows and doors open and closed may be as high as 10 db. Minimum, representative, and maximum levels are given for each type of space.' The values are intended to give the variation with respect to location and not to time, and may be roughly classified as shown in the following paragraphs. ;
Sound Control
841
Minimum loudness refers to: Spaces-of expensive construction, typified by double windows, carpeted floors, heavy upholstered furniture, or acoustically treated walls and ceilings.
Representative loudness refers to: Spaces of average construction and furnishings which are exposed to external noises typical of the locality in which the space is usually found.
Maximum loudness refers to: (1) Any space of inexpensive construction, and bare furnishings where noise is not an important factor. (2) Spaces in close proximity to very intense street traffic or to intense factory noise.
In general, if the, noise level in the space resulting only from the opera tion of the air conditioning equipment is equivalent to or less than the typical level given in Table 1, the installation will prove satisfactory. If the typical level and the equipment level are equal and heard together the resultant level will be 3 db higher than either of them alone.
In some cases it is desirable to keep the equipment noise level in the ventilated or conditioned room at such a value that it actually will not increase the noise level in the room to any measureable degree. This can be accomplished if the equipment noise at the room can be kept 10 db below the noise levels shown in Table 1.
NOISE GENERATED BY FANS
Noise generated by fan wheels may be divided into two classifications, rotational noise and vortex noise. In ventilation and air conditioning work, where the maximum ratio between the fan tip speed and the velocity of sound is not greater than 0.12, vortex noise is by far the most important. The rotational noise may be described as that due to the thrust and torque applied to the air. Vortex noise is'that due to the shedding of vortices from the blade and is dependent on the angle of attack, velocity, air turbulence, and blade shape. Vortex noise is due to pressure variations on the blade as a result of variations of air circulation. Given the noise level at the outlet or inlet of one type of fan construction under specific conditions of size, tip speed, and total pressure, noise levels at other values of tip speed, total pressure, and size may be approximated by the relationships:
1. For constant.size and point of rating, the noise level of a fan will increase with
increasing speed.
/rpmA db (change) = 551ogu \rpmJ
(1)
2. For constant pressure and tip speed, the noise level of a given type of fan will increase with increasing fan size.
db (change) = 20 log,.
(2)
Fan size refers to wheel diameter, housing height or some dimension that is directly proportional to lineal units. Fan sizes based on arbitrary systems or systems of preferred numbers have no significance.
The,noise of a given, fan is not constant at constant speed if the air . delivery changes due to change of resistance. In general, a backward curved blade fan is lowest in noise at or near the point of maximum effi ciency; a forward curved blade fan at or between the point of maximum efficiency and shut-off; an axial flow fan at or between the point of maximum efficiency and free delivery. The noise level of a double width fan may be