670 CHAPTERn40 q> *rwo"'2& ; V965: Goiae>And Data<Bobic - (c)-,The condenser water .flow rate;generally is estimated-,as 3.5 gpm per' too. Thus' the full load-, condenseryfiow rater,is 200 X 35 - 700gpm. . % ru ' (d) Tbechilled water flow rate is: 3 -y. < '<: i- ' Refrigeration lord (tons)* X 24 A" ' - ' ...gpra- .chilled.water;temp, difference. - V 200 X 24 ' - 600 gpm - -tS (e) The heat rejewJ. tp.'.^iecooliig tower.is:.,. - - 1 q)i2,o6ohiF*, " ' ' ",v r%..n-- ,Q, = heat rejected to.cooling tower, Btuh: * refrigeration load,'tons." Ft, -- heat rejection factor. ' T. A typical value of the heat "rejection factor may be taken as 2.6. Therefore:- i--'.'. 12,000 X 200 X 2.6 ' i - r- - 6,240,000Btuh Scale, (fouling).factors higher than 6.0005 in.the abeorbesf* condensercircuithave thesame-effect as-an increase in con- denser:water temperatures.-iF-or 'a: scale'(fouling)'factorrdf 0.001,' multiply,',the-overall capacity, factor by 0.85.`i Form scale /factor, of 0.002,-. multiply..the!overaU -'capaaty - factor <by 0.65. : 'Ir/-,.-- 'v- s.-yy, v >. Operating conditions not included within the limits:shown here may be considered sufficiently..unusual/to-require the -direct assistanceof manufacturers'-rcpresentativea.- The';se- .lectiomof.abeoiptibn-machine&to .operate on.hot- water..or other hot fluids.should'generally be-referred directlyito-tha manufacturer;! os' ! ',- - ; . o.` , ' REFKB^CES - The Abao^ionCoolutg'PTVcese' (Iniiitate_ of GaiTlxfinoIpgg -Bflrft'i^:i057).;i- - .rJ. -* ' ' M * S. E. Johnson: A look, at'today's absorption, refrigeration (ASHRAR'JnrmNAL.Septainber 1960.p.55). .. 7::.:r/jr;y.: F.;C.-Wood:Absorption or compression forair-conditioning ^Btesrrwlnch?.(Poer, Deeeinber.l963,,pi.60). _. .. ( W. FJ Stoecker: Refrigeration & Air. Conditioning ,(McGrawT Hill Book Co.-, Iric.,>New York,-1958)........... . H. Camer", R. K Cheme, W. A_.Graat, and W. H. Roberta: Modem'Air'.Conditiohmg, Heating and Ventilating (Pitman'Pub lishing CoTp.,:New York,' 1959; 3rd ed.). , _J - CHAPTER 41 AIR-CYCLE EQUIPMENT Air-Cyde Systems: Simple, Bootstrap, Regenerative, and Reduced Ambient Types/ Compartment Air Temperature Control, Air Flow Control, Wafer Separator Anti-Ice Control/ Sources of High Pressure Air/ Estimating Performance of Fixed-Size AirCyde Refrigeration Units; Design of Systems for Other Air Flow Capadty AIR-CYCLE refrigeration systems are used commonly, in Xi.the`air; conditioning of both military and commercial aircraft', principally because of the extremely lightweight) compact'equipment which is typical'of air-cycle systems. Air-cycle air conditioning has not been found to be economical in residential and commercial buildings, because higher power a required to operate an air-cycle system than a conventional yajporicycle system. " 'In a refrigeration system using the open air-cycle principle) the .refrigerant is air and is used directly to cool the space requiring refrigeration. Unlike the refrigerant of a. vapor- cycle system,'which continuously changes phase from a liquid to a gas and back to a liquid again, the refrigerant of an air- cycle system remains in the gaseous phase throughout the. cycle. J `' Refrigeration in a simple open air-cycle system is obtained by. three basic steps: (1) compression, (2) heat transfer,'and (3) -expansion accompanied by work extraction.' Air is first compressed in a compressor to a pressure' higher than the prcsure of the space to be cooled. The heat of compression then is removed from the air in a heat exchanger by rejecting it to a suitable heat sink such as air. In the third step air is cooled by extracting work from it as it expands through a turbine. The expansion of air through a simple throttling device, such as an orifice or a valve, does not noticeably lower the air temperature. .Therefore work must be extracted from the expanding air. This is accomplished by providing a load on-the turbine. The-amount of cooling derived from the turbine is a direct function of the amount of work' done by the turbine. The load in many cases is a fan which draws iwtlirig air through the heat exchanger located,, in most systems, immediately upstream from the turbine. The cold air from the turbine discharge is used directly for refrigeration pur poses. The Lockheed P-80 Shooting Star airplane made use of an early air-cycle system. That system, however, was-not truly a simple air-cycle system, because the cooling turbine fan was used merely as a loading device lor the expansion turbine, aad ram air pressure was used to force cooling air across the beat exchanger. In a true basic air-cycle system-the cooling turbine fan induces flow of cooling air across the beat ex- cbanger. A system of this type used for aircraft application was installed m the Douglas XB-43 airplane. ' Later a true banc air-cycle refrigeration unit was produced for the Lock- P-80 airplane. The heat exchanger of that unit was a multipass design utilising a tubular-type heat transfer surface. The cooling turbine contained a rotating assembly consisting of a turbine wheel and a fan fastened to opposite ends of a common shaft. The rotational , speed of this assembly was approximately 100,000 rpm.'The refrigeration unit weighed 16 lb and supplied cold air to the cockpit at a rate of 7 lb per min. Since the'time of the P-80 airpl&ne, almost all highspeed, high-altitude airplanes have been equipped with air-cycle refrigeration systems. Refrigeration units have been built in various sixes ranging iii weight from 6.5 to 200 lb and ranging in air.flow capacity between 7 and 150 lb per min, AIR-CYCLE REFRIGERATION SYSTEMS - The common air-cycle systems which will be lii^nwrf in this chapter are: (1) basic (or simple) type, (2) bootstrap type, (3) regenerative, and (4) reduced ambient type. There are also many other air-cycle systems that are'variations or combinations of these systems. The two systems which have had the greatest use are the basic and bootstrap types. - Basic and Basic-Evaporative Types The air-cycle refrigeration system, shown in Fig. 1, consists of an air-to-air heat exchanger and a cooling turbine. Highpressure, high-temperature air is cooled initially in the heat *en"* mpftMibffitr lor this ch*pUr b uaiftwd to TC S.4. Ttmaspar- 671 Rg. 1 .... Basic Air-Cyde Refrigeration System