Document 91Ew62rrVx3wbbZ5yXJRnBj07
670
CHAPTERn40 q> *rwo"'2&
; V965: Goiae>And Data<Bobic
- (c)-,The condenser water .flow rate;generally is estimated-,as
3.5 gpm per' too. Thus' the full load-, condenseryfiow rater,is
200 X 35 - 700gpm. . %
ru
'
(d) Tbechilled water flow rate is: 3 -y.
<
'<: i-
' Refrigeration lord (tons)* X 24 A" '
- ' ...gpra- .chilled.water;temp, difference. -
V 200 X 24 ' - 600 gpm -
-tS
(e) The heat rejewJ. tp.'.^iecooliig tower.is:.,.
- - 1 q)i2,o6ohiF*, " ' ' ",v
r%..n-- ,Q, = heat rejected to.cooling tower, Btuh: *
refrigeration load,'tons." Ft, -- heat rejection factor.
' T.
A typical value of the heat "rejection factor may be taken
as 2.6. Therefore:-
i--'.'.
12,000 X 200 X 2.6
' i - r-
- 6,240,000Btuh
Scale, (fouling).factors higher than 6.0005 in.the abeorbesf*
condensercircuithave thesame-effect as-an increase in con-
denser:water temperatures.-iF-or 'a: scale'(fouling)'factorrdf
0.001,' multiply,',the-overall capacity, factor by 0.85.`i Form
scale /factor, of 0.002,-. multiply..the!overaU -'capaaty - factor
<by 0.65. : 'Ir/-,.-- 'v-
s.-yy, v
>. Operating conditions not included within the limits:shown
here may be considered sufficiently..unusual/to-require the
-direct assistanceof manufacturers'-rcpresentativea.- The';se-
.lectiomof.abeoiptibn-machine&to .operate on.hot- water..or
other hot fluids.should'generally be-referred directlyito-tha
manufacturer;! os' ! ',- - ; . o.`
, ' REFKB^CES -
The Abao^ionCoolutg'PTVcese' (Iniiitate_ of GaiTlxfinoIpgg
-Bflrft'i^:i057).;i- - .rJ. -* ' '
M
* S. E. Johnson: A look, at'today's absorption, refrigeration
(ASHRAR'JnrmNAL.Septainber 1960.p.55). .. 7::.:r/jr;y.:
F.;C.-Wood:Absorption or compression forair-conditioning ^Btesrrwlnch?.(Poer, Deeeinber.l963,,pi.60). _. .. (
W. FJ Stoecker: Refrigeration & Air. Conditioning ,(McGrawT Hill Book Co.-, Iric.,>New York,-1958)........... . H. Camer", R. K Cheme, W. A_.Graat, and W. H. Roberta: Modem'Air'.Conditiohmg, Heating and Ventilating (Pitman'Pub
lishing CoTp.,:New York,' 1959; 3rd ed.). ,
_J -
CHAPTER 41
AIR-CYCLE EQUIPMENT
Air-Cyde Systems: Simple, Bootstrap, Regenerative, and Reduced Ambient Types/ Compartment Air Temperature Control, Air Flow Control, Wafer Separator Anti-Ice Control/ Sources of High Pressure Air/ Estimating Performance of Fixed-Size AirCyde Refrigeration Units; Design of Systems for Other Air Flow Capadty
AIR-CYCLE refrigeration systems are used commonly, in
Xi.the`air; conditioning of both military and commercial
aircraft', principally because of the extremely lightweight)
compact'equipment which is typical'of air-cycle systems.
Air-cycle air conditioning has not been found to be economical
in residential and commercial buildings, because higher power
a required to operate an air-cycle system than a conventional
yajporicycle system.
" 'In a refrigeration system using the open air-cycle principle)
the .refrigerant is air and is used directly to cool the space
requiring refrigeration. Unlike the refrigerant of a. vapor-
cycle system,'which continuously changes phase from a liquid
to a gas and back to a liquid again, the refrigerant of an air-
cycle system remains in the gaseous phase throughout the.
cycle.
J
`' Refrigeration in a simple open air-cycle system is obtained by. three basic steps: (1) compression, (2) heat transfer,'and
(3) -expansion accompanied by work extraction.' Air is first
compressed in a compressor to a pressure' higher than the
prcsure of the space to be cooled. The heat of compression
then is removed from the air in a heat exchanger by rejecting
it to a suitable heat sink such as air. In the third step air is
cooled by extracting work from it as it expands through a
turbine. The expansion of air through a simple throttling
device, such as an orifice or a valve, does not noticeably lower
the air temperature. .Therefore work must be extracted from
the expanding air. This is accomplished by providing a load
on-the turbine. The-amount of cooling derived from the
turbine is a direct function of the amount of work' done by the
turbine. The load in many cases is a fan which draws iwtlirig
air through the heat exchanger located,, in most systems,
immediately upstream from the turbine. The cold air from the turbine discharge is used directly for refrigeration pur poses.
The Lockheed P-80 Shooting Star airplane made use of an
early air-cycle system. That system, however, was-not truly
a simple air-cycle system, because the cooling turbine fan was
used merely as a loading device lor the expansion turbine,
aad ram air pressure was used to force cooling air across the
beat exchanger. In a true basic air-cycle system-the cooling
turbine fan induces flow of cooling air across the beat ex-
cbanger. A system of this type used for aircraft application
was installed m the Douglas XB-43 airplane. ' Later a true banc air-cycle refrigeration unit was produced for the Lock-
P-80 airplane. The heat exchanger of that unit was a
multipass design utilising a tubular-type heat transfer surface. The cooling turbine contained a rotating assembly consisting of a turbine wheel and a fan fastened to opposite ends of a common shaft. The rotational , speed of this assembly was approximately 100,000 rpm.'The refrigeration unit weighed 16 lb and supplied cold air to the cockpit at a rate of 7 lb per min.
Since the'time of the P-80 airpl&ne, almost all highspeed, high-altitude airplanes have been equipped with air-cycle refrigeration systems. Refrigeration units have been built in various sixes ranging iii weight from 6.5 to 200 lb and ranging in air.flow capacity between 7 and 150 lb per min,
AIR-CYCLE REFRIGERATION SYSTEMS
- The common air-cycle systems which will be lii^nwrf in
this chapter are: (1) basic (or simple) type, (2) bootstrap type,
(3) regenerative, and (4) reduced ambient type. There are
also many other air-cycle systems that are'variations or combinations of these systems.
The two systems which have had the greatest use are the
basic and bootstrap types. -
Basic and Basic-Evaporative Types
The air-cycle refrigeration system, shown in Fig. 1, consists of an air-to-air heat exchanger and a cooling turbine. Highpressure, high-temperature air is cooled initially in the heat
*en"* mpftMibffitr lor this ch*pUr b uaiftwd to TC S.4. Ttmaspar-
671
Rg. 1 .... Basic Air-Cyde Refrigeration System