Document 914KrXzoBqLQdeRwkqyjOXmOp

American Society of Heating and Ventilating Engineers Guide, 1930 Table 3. Chimney Sizes for Low-Pressure Heating Boilers and Warm Air Furnaces Wash Air Furnace Capacity in Leader Pipe Sq. In. Steam Boiler Capacity Sq. Ft. op Radia tion Hot Water Heater Capacity Sq. Ft. of Radia tion Nominal Dimen sions OF FirbClay Lining In. Rectangular Flub . Round Flue Actual Inside Dimensions of Fire Clay Lining In. Actual Area Sq. In. Effec- . tive Area Sq. In. Inside Diameter of Lining In. Actual Area Sq. In. Height in Ft. from Grate 790 590 973 8^x13 1000 690 1140 7x11)^ 81 . 70 10 2 79 ea>uo- 900 1490 13x13 nxxnu 127 99 C.o 900 1490 8Hxl8 6%xl6X iio 100 1100 1820 12 113 gg 1700 2800 13x18 UJ4xl6K 183 156 1940 3200 15 177 gxi 2130 3520 18x18 15^x15^ 248 195 o-s 2480 4090 20x20 298 234 o 3150 5200 18 254 c *w 4300 7100 20 314 4600 7590 20x24 17x21 357 278 ^2 c 5000 8250 24x24 21x21 441 g* 5570 9190 24x24s 576 380 5580 9200 22 380 6980 11500 24 452 . a 7270 12000 24x28s 672 468 *T ee rt 8700 14400 28x28s 784 531. <3 8 3 9380 15500 27 573 10150 16750 30x30s 900 616 10470 17250 11800 19500 28x32s 896 635 30 . U jjj 707 as 14700 24300 33 855 c-fs w 17900 29500 36 1018 <2--ox: Dimensions are for unlined rectangular flues. Chimneys recommended for larger boilers 15 to 250 hp. may be pro portioned in accordance with the report made by a joint Committee of the American Boiler Manufacturers Association and Stoker Manufacturers Association and approved by these organizations. The sizes are given in Tables 4, 5 and 6. Chimneys for still greater horsepowers are given in Tables 5 and 6. CHIMNEYS FOR OIL FUEL1 The requirements for stacks for oil fuels are entirely different from those connected to coal-fired boilers, as there are certain losses through the boiler proper that are eliminated. Gas temperatures entering the stacks are lower for a given capacity, and the volume of gas is less than with coal. The cross-sectional area of the stack may therefore be less. In most instances this may safely be taken as 60 per cent of the area that would be furnished for coal-fired boilers. In determining the height, care must be taken to design a stack that will give a sufficient draft for the maximum requirements of the boiler, but no more. In this way the *Frora Marks' Mechanical Engineers Handbook. 256 Chapter 14--Chimneys Table 4. Draft Losses with Forced Draft Stokers and Corresponding Height of Stack for Average Installations (Sea Level)3 100 Furnace Draft**................................................ Friction Loss (Boiler)0--.................................. Friction Loss (Breeching)<i............................. Total Draft Required.--.;:..........................-.... Height of Stack (Ft.)._................................... - 0.15 0.18 0.10 0.43 80 Rating--Per Cent 150 0.15 0.4 0.10 0.65 112 200 0.15 0.6'5 0.10 0.90 145 250 0.15 0.9 0.10 1.15 178 300 0.15 1.20 0.10. 1.45 220 For boilers from 15 to 250 hp. bAllow 0.15 in. for forced draft and 0.35 in. or higher, depending on rate of combustion and fuel used, for natural draft. Friction loss through boiler varies according to construction. dAllow 0.05 in. for each right angle bend and 0.1 in. per 100 ft. of length. Table 5. Diameter of Chimney in Inches for Horizontal Return Tubular Boilers3 Nominal Horsepower 15 20 25 30 35 40 50 60 75 90 100 115 125 150 175 200 210 225 250 Rating--Per Cent 100 150 200 13 14 17 14 16 18 16 18 20 17 19 21 18 20 22 19 21 23 20 23 25 21 24 27 23 26 29 25 28 31 26 29 33 27 31 34 28 32 35 30 34 38 32 36 40 33 38 43 34 38 44 35 40 45 - 36 41 47 The figures in this table are based on the following assumptions: Rating.........................1........ Efficiency................................... CO*............ _..L........................... Stack Temp. deg. fahr.____ Pounds of gas............................ 100% 65% 8% 450 85 150% 65% . 9% 500 77 200% 63% 10% 550 73 efficiency is safeguarded, and the danger of a draft such as to pull through too large an excess of air is eliminated. Table 9, adapted from a similar table calculated by C. R. Weymouth {Trans. A. S. M. E., Vol. 34, 1912) and based on actual test data, will be found to give-.satisfactory results under the assumed conditions, as given for stacks with oil-burning boilers. 257