Document 8VrbRm91qw0b0YeXVepO94r1K
HEATINC VENTILATING AIR CONDITIONING GUIDE 1943
. Factors Influencing the Performance of Rotary Dryers, by C. F. Prutton and C. O. Miller (Transactions, American Institute of Chemical Engineers, Part 1, February, 1942; Part 2, August, 1942).
Drying of Solids by Through Circulation, by W. R. Marshall and O. A. Hougen {Transactions, American Institute of Chemical Engineers, 1942).
Factors that Influence Drier Performance, by A. Weisselberg (Chemical and Metallur gical Engineering, August, 1932).
Typical Dryer Calculations, by O. A. Hougen (Chemical and Metallurgical Engi neering, January and March, 1940).
Symposium on Drying, Articles by W. K. Lewis, W. H. Carrier, A. E. Stacey, Jr. and R. S, Fleming, R. G. Metz, G. B. Ridley, C. O. Lavett, D. J. Van Marie (Journal Industrial Engineering Chemistry, May, 1921).
Principles of Drying Lumber and Humidity Diagram, by H. D. Tiemann (Forest Service Bulletin 104, 1912).
The Drying of Solids, by T. K. Sherwood (Bulletin Massachusetts Institute of , Technology, Nos. 237, 247 and 258).
Air Conditioning and Engineering, American Blower Co., 1935.
Drying in Industrial Plants, by J. O. Ross.
Elements of Chemical Engineering, by Badger and McCabe (McGraw Hill Co., 1931).
Fan Engineering, Buffalo Forge Co.
Die Trockentechnifc, by M. Hirsch (Julius Springer, Berlin, 1932).
Drying (Kent's Mechanical Engineers Handbook).
Drying, by W. H. Carrier (Marks' Mechanical Engineers Handbook).
Drying (Perry's Chemical Engineers Handbook, 1941).
.
Kiln Drying of Lumber, by A. Koehler and R. Thelen, New York, 1926.
Kiln Drying of Lumber, by H. D. Tiemann (Lippencott, 1920).
.i
- Modern Drying Machinery, by H,B. Grenshaw, London, 1926.
Principles of Chemical Engineering, by Walker, Lewis, McAdams' (Chapters on Evaporation, Humidity and Drying, McGraw Hill Co.).
I
764
Chapter 42
NATURAL VENTILATION
.Wind .Forces, Stack Effect, Openings, Windows, Doors, Skylights, Roof Ventilators, Stacks, Principles of Control, General Rules, Measurements, Dairy 'Barn Ventilation,
Garage Ventilation
<
VENTILATION' by natural forces, finds application in industrial plants, public buildings, schools, dwellings, garages, and in farm
buildings.
...
The natural forces available for moving air,into, through and out of
buildings are: (a) wind' forces, and (b) the difference in temperature
between the air inside and outside a building.. The air movement may
be caused by either of these forces acting alone or by a combination of the
two, depending upon atmospheric conditions, building design and loca
tion. The ventilating results obtained will vary, from time to time, due
to variation in the velocity and direction of the wind and the heat gener
ated in .the building.- The arrangement, location; and.control of the
ventilating openings should be such that the two forces act cooperatively
rather than in opposition. ' : -
.. . . ; ;
WIND FORCES
In considering the use of natural wind forces for producing ventilation, account must be taken of: (1) average wind velocity, (2) prevailing wind
direction, (3) seasonal and daily variations in velocity arid direction, and (4) local wind interference by nearby buildings, hills or other obstructions of similar nature. ; '
Values are given in Table 1, Chapter 7 for the average suinmer wind
velocities and the prevailing wind directions in.various localities through
out the United States, while Table 2, Chapter 6; lists similar values for
the winter, . In almost all localities the summer .wind, velocities are lower
than -those in the winter, and in about two-thirds of the localities the
prevailing direction is different during the summer and winter. While the
tables give no average velocities below 5 mph, there will be' times when
the velocity is lower, even in localities where the seasonal average is con
siderably above 5 mph. There are relatively few places where the velocity
falls below one half of the average for many hours per month. - Con-'
sequently, if the natural ventilating system is designed for wind velocities -
of one-half of the average seasonal velocity, it should prove satisfactory in
almost every, case.,- -
.
765
X