CHAPTER 11
1951 Guide
Notes fob Table 6.
* The insideouteide temperature difference is 70-- (--10) or 80 F except where otherwise noted.
b Volume of infiltration, cfh = (no. air changes) x (floor or eeiling area) x (ceiling height).
From Equation 5a.
d The wiling heat losses are calculated-by estimating the attic temperature and then calculating the loss through theceuing using the proper temperature difference. This unheated attic is not ventilated during winter months. The attic temperature is estimated from Equation 1 to be 30.2 F when the outside tem perature is --10 F and room temperature is 70 F. The temperature difference is then 70--3012 or 39.8 deg. For the insulated residences attic temperature becomes 4.6 F and temperature difference 70--4.6 = 65.4 deg.
* Temperature in garage assumed to be 35 F.
-
1 Coefficient for wall adjoining garage calculated on basis of metal lath and plaster on both sides of studs, (U * 0.39).
s One half of value from Table 4, Chapter 10, for storm windows or weatherstripping.
b Exposed on two sides, weatherstripped windows offset by fire-place. Use 1H-
* Window on one side weatherstripped but double-doors are hard to close tightly. Hence, conservative value of V4.
J Awpiming kitchen vent, door to vestibule usually open, allow full table value of 1H-
k One-half value in Table 4, Chapter 10, increased to 1H by nearby outside door in vestibule.
1 Full value in Table 4, Chapter 10, to allow for frequent opening of outside door.
m Two sides exposed, large doors but large volume. Use value 1H as given in Table 4, Chapter 10.
D Two
unweatherstripped windows in protected location, but fireplace, indicate 1 change.
p Heat losses from these rooms into garage are heat gains for garage.
4 Neglect heat loss to basement, as losses from boiler', piping, etc., will probably keep basement near, if not above, 70 F.
r Upstairs hall ceiling, figured with downstairs. Heat should be provided downstairs for both.
* T.inaar feet of exposed edge.
Table 7. Summary of Heat Losses of Uninsulated Residence (Btu Per Hour)
Room ob Space
Walls
Ceiling and Roof
Floor
Glass and Doob
Infil tration
Totals
Garage _ Recreation
Design Totals Operating Totals0 Percentages0
5330 3490 2560 2650
670 16407260 3720 2850 3000
870 -1030*
840
33,850 33,850
38.4
6910 4660 3540 3020 1510
960
2390. --1270b
21,720 21,720
24.6
960 . 310
1060 . 570 2,900 2,900
3.3 .
1440 1440 970
720 500 320 1800 3100 950 1100 640 3710 720
17,410 17,410
19.7
2180 1470 1260 950 630 400 5400 3080 2300
550 1600 1910 2890
24,620 .12,310
14.0
15,860 11,060 8.330 8,300 3.310 3,630 14,460 9,900
6,100 4,650 5,500 4,380 5,020
100,500 88,190 100;0
* Wall heat loss of 2110 Btuh minus wall heat gains of 1280,700 and 1160 Btuh. b Heat gains of 960 and 3io Btuh. c Based on H oomputed infiltration. d Based on operating totals.
Table 8. Summary of Heat Losses of Insulated Residence (Btu Per Hour)
Room ob Space
Walls
Ceiling and Roof
\ Floor
Glass and Door
Infil tration
Totals
Garage Recreation
Design Totals
Percentages0
2480 1620 1190 1230 310 700 3370 1730 1320 1390 410 -470*
840
16,180 16,180
29.1
2460 1660 1260 1080 540 250
850. --910b
7,190 7,190
12.9
690 220
1060 570 2,540 2,540 4.6
1440 1440 970 720 500 320 1800 * 3100
950 1100 640 3710 ' 720
. 17,410 17,410 31.3
2180 1470
1260 950 630
400 5400
. 3080 2300 550 1600
1910 2890
.
24,620 12,310
22.1
8,560 6,190 . 4,680 _ 4,670 1,980 1,950 10,570 7,910 4,570 3,040 .3,500 5,300 5,020
67,940 55,630
100.0
* Wall heat log? of 9S0 Btuh minus wall heat gains of 590,320 and 540 Btuh. b Heat gains 090 and 220 Btuh. eBased on H oomputed infiltration. d Based on operating totals...
Heating toad
255
buildings may either be continuously heated or have more time allowed for heating up during the few minimum . temperature days, no allowance usually is made, except in the size of boilers or furnaces. For churches, auditoriums and other intermittently heated buildings, additional capacity
should be provided.
RESIDENCE HEAT LOSS PROBLEMS
Example 6. Calculate the heat loss of the residence shown in Fig. 3 located in the vicinity of Chicago. From Table 1, design outdoor conditions are --10 F and 12 mph wind velocity. Inside temperature from Table 2 is assumed to be 70 F. The attic is unheated. Assume ground temperature to be 50 F (see Fig. 3, Chapter 34) under basement and garage floors and 32 F adjoining basement walls. Estimate infiltration losses by the air change method. No wall, ceiling or roof insulation is to be con sidered in this problem, but all first and second floor windows, except in the garage; are to have storm sash. The building is constructed as follows (heat transmission coefficients U are in parentheses):
Walls: Brick veneer, building paper, wood sheathing, studding, metal lath and plaster (0.28). Walls of dormer over garage, same except wood siding in place of brick veneer (0.26).
Attic Walls: Brick veneer, building paper, wood sheathing on studding (0.42).
Basement Walls: 10 in. concrete (0.10).
Roof: Asphalt shingles on wood sheathing on rafters (0.53).
Ceiling {Second floor): Metal lath and plaster (0.69).
Windows: Double-hung wood windows averaging 70 percent glass (0.45; from Chapter 9, Table 19, Section D, the U value for wood windows with storm sash is 0.53 x application factor; by interpolation this factor is 0.85). Steel casement sash in garage and basement (1,13; from Chapter 9, Table 19, B is 1.13 for all glass and the application factor is 1.00). French doors in dining room 50 percent glass, no storm.' doors (0.85; from Chapter 9, Table 19, U is 1.13 for all glass; by interpolation the application factor is 0.75).
Floor (Bedroom D): Maple finish flooring on yellow pine sub-flooring; metal lath and plaster ceiling below (0.25),
Floor {Basement and Garage): 4 in. stone concrete on 3 in. cinder concrete (0.10).
Solution: The calculations for this problem are given in Table 6; and a summary of the results in Table 7. The values in column F of Table 6 were obtained by multi plying together the figures in columns C, D, and E. The heat losses are calculated to the nearest 10 Btu. See reference notes for Table 6 for further explanation of data.
Attention is called to the summary of heat losses (Table 7) for the uninsulated resi dence. As storm windows are used in this instance the glass and door transmission heat losses of 19-8 percent are relatively small. The infiltration losses of 14.0 per cent are also comparatively small because the storm windows are equivalent to weatherstripping. In this problem, the wall, ceiling and floor transmission losses comprise 66.2 percent of the total.
Example 7. _ Calculate the heat loss of residence shoivn in Fig. 3 based on the same conditions as in Example 6 but having construction improved or insulated to obtain coefficients as follows:
Walls, 0.13; Walls of Dormer over Garage, 0.12; Attic Walls, 0.28; Walls Adjoining Garage, 0.18; Basement Walls {Recreation Room), 0.10.
Roof, 0.53.
Ceiling {Second Floor), 0.15.
Windows (Same as in Example 6).
Floor {Bedroom D), 0.18.
Solution: The procedure for calculating the heat losses is similar to that for Examples.' A summary of the results is given in Table 8.
REFERENCES
1ACRMA Application Engineering Standards/for Air Conditioning for Com fort, (1947), Air Conditioning and Refrigerating Machinery Association, Inc., pages 4 to 7.