Document 8VZD3gDv3qagY9xQJ98EG1jEK
I:Til V I C-OUl'OK ATION i: NC'.IXK UK ISC. L) EPAKl'MEMT
SPECIFICATION SP-92-1 HOT INSULATION
CONTENTS
ITEM
lV^GENERAL........................
1.1 1.2
==5,1.3 .<^1.4
Intent.................... OSHA COMPLIANCE . .
Scope.................... Line List................ Equipment List . . , Special Requirements
2,'^PIPING............................
2.1 Material................ 2.2 Securement .... 2.3 Weatherproofing . . 2.4 Fittings.................... 2.5 Details.................... 2.6 Hangers & Supports 2.7 Single Layer . . . 2.8 Double Layer . . .
2.9 Supports.................... / 3.'* EQUIPMENT....................
3.1 Material.................... 3.2 Securement................ 3.3 Weatherproofing. . . 3.4 Details.................... 3.5 Irregular Surfaces . .
TABLE I, THICKNESS
FIGURE 1 through 4 (Piping)............................
FIGURE 5 through 12 (Equipment)....................
5 6-9 10-17
ETH 002262
I
1'TUVI. COUPORATION r. Si.il FJUKTNt* Department
SPECIFICATION SP-92-T HOT INSULATION
Page 2 of 17
1 r* GENERAL ^
1.1 jntenfr The intent of this specification is (1) to define the materials to be used for insulation of vessels, equipment, and piping in hot service, and (2) to define certain details of insulation application. The purpose of this insulation is to conserve heat (H) and/or to protect personnel (P). Any specific details not covered herein shall be in accordance with best area practice.
1.2 OSHA COMPLIANCE. All design and construction done in the United States under this' specification shall be in strict compliance with the Williams-Steiger Occupational Safety & Health Act of 1970 (84 Stat. 1593, J600; 29 U.S.C. 655, 657) as revised. _
1 3 sfep<i~T This specification covers the design and application of heat insulation systems for piping and equipment (vessels, columns/ pumps, etc). It is intended to serve as a basis for contractor's bidding and performance. It is also intended to serve as a basic engineering guide to standardize and simplify the solution of recurring insulation problems.
1.4 Line Dst. A separate document, the LINE LIST indicates the pipe lines to be insulated in accordance with this specification. Insulation thickness will also be specified in the LINE LIST.
1*5 Equipment List. A separate document, the EQUIPMENT LIST, indicates the equipment to be insulated in accordance with this specification. The insulation thickness will also
be specified in the EQUIPMENT LIST.
1.6 Speclgfi^equirements
l
a. Lower Limit. Surfaces normally operating at less than 200?F shall not be heat - insulated unless specifically required for personnel protection or special process reasons.
b. Personnel Protection. Personnalj protection insulation shall be applied to piping and equipment operating above 150'F which may be accidentally touched by personnel. Such hot surfaces shall be insulated to a height of 7' above.or 3' to each side of normal walking, or working areas (including platforms and ladders). Personnel pro tection insulation shall not be continued beyond normal working areas. Alternatively, guards of expanded metal may be used if specified by Ethyl.
c. Valves, Flanges, & Fittings. Valves, flanges, and fittings, except unions, in steam and boiler feed water service shall be insulated. Valves, flanges, and flanged fittings in other services shall not be insulated except where required for personnel protection or special process reasons. Welded and screwed fittings, except unions, in insulated lines shall be insulated^ expansion joints shall not be insulated.
d. Steam Traps. Steam traps shall not be insulated except for personnel protection. Inlet piping to steam traps shall be insulated. Discharge piping which returns to a condensate collection system shall be insulated. Piping which discharges to a drain shall not be insulated except for personnel protection.
e. Steam Tracing. Steam traced piping or equipment shall be covered with oversized insulation to include the tracer lines. Insulation thickness shall be selected from Table I. Steam traced systems shall be completely insulated including equipment, valves, flanges, fittings, and tracer line loops.
f. Hydro Test. All equipment shall be pressure tested before the application of insulation.
g. Nameplates. Nameplates shall not be insulated. Insulation surrounding vessel markings and plates shall be sealed to prevent water from entering.
ETH 002263
I :tiIYI. <-OW I>OUALION i- nV.in-ki'kino Department
2r PIPING
SPECIFICATION SP-92-1 HOT INSULATION
Page 3 of 17
2.1 Matejpfgj. Piping to 1200F shall be insulated with calcium silicate, mineral fiber,
or expanded perlite; all products shall be asbestos free. Acceptable materials are:
Calsilite, Calsilite 1200
Celotex, Care/temp 1500
Johns Manville, Thermo 12
Eagle Picher, Epitherm 1200
Keene, Thermasil
Forty Eight, MF
Owens Coming, Kaylo 10
Holmes, Unisite
Pabco, Super Caltemp NA.
Lo^ Cay?_
Other materials may be used with Ethyl Corporation approval. In periods of material shortage, piping to400F may be insulated with Pittsburgh Coming Foamglas. Insulation thickness shall be as specified in the Line List; insulation thickness for piping not shown in the Line List shall be per Table 1.
2.2 Se4t<ifefhent. . Tie wire shall be 18-8 soft-annealed stainless steel. 16 gage for 10" and smaller pipe. 14 gage for 12" and larger pipe.
CuPS
2.3 Weatherproofing. Insulation shall be weatherproofed with 0.016" thick x 3/16"
corrugated aluminum with factory attached moisture barrier. Secure aluminum with
"5"" long x
sheet metal screws on 9" centers. All laps shall be at least
2" and shall shed water.
2.4 Fittings. Fittings smaller than 2" shall be covered with insulating cement (JM 450 or approved equal) and weatherproofed with GPM mastic (Ben Foster 35-01 alum gray or approved equal) 1/16" dry film thickness. Fittings 2" and larger shall be insulated with a material comparable to the adjacent pipe insulation and weatherproofed with GPM mastic (Ben Foster 35-01 alum gray or approved equal) 1/16" dry film thickness. The mastic shall be reinforced with Ben Foster Mast-a-Fab. Preformed aluminum fittinc covers may be used if economical and available.
. .
.
^a^rc^L'
2.5 ails. Details of piping insulation shall be as shown in figvm^ 1 through 4.
2.6 Ha/tg^nT& Supports. At all pipe hangers and supports, the necessary cutouts shall be carefully made and weatherproofed with heat resistant mastic, Foster 95-10 or approved equal up to 350F; above 350F use Eagle Picher Stalastic.
2.7 Singfe^Layer Application. For single layer application, the circumferential joints shall be staggered and the longitudinal joint shall be on the underside of horizontal runs.
t+ 2.8 Double Layer Application. For double layer application, the inner layer shall be
applied as the single layer in the preceding paragraph. The outer layer shall be applied with the joints staggered longitudinally and circumferentially with respect to the inner layer. Each layer shall be secured as shown for a single layer.
2.9 S^fSjaorts. Insulation on vertical lines shall be supported by ring flanges welded to the pipe. Supports shall be supplied by the Insulation Contractor or as directed by the Ethy Engineer. Ring OD shall be less than insulation OD. Start at bottom of line and install ring flanges at 2V intervals as needed. Allow for bolt removal at pipe flanges. See Fig.2.
X ETH 002264
TI1Y1. C.OKIHM* AT ION
N01Nl-:H>fI.N(. 1)III'AKTMIiNT
EQUIPMENT
SPECIFICATION SP-92-1 HOT INSULATION
3.1 Material
a. Small Cylindrical. Equipment to 1200F and 24" and less in diameter shall be insulated with calcium silicate, mineral fiber, or expanded perlite pipe covering; all products shall be asbestos free. Acceptable materials are
Calsilite, Calsiiite 1200 Celotex, Careytemp 1500 Eagle Picher, Epitherm 1200 Forty Eight, MF Holmes, Unisite
Johns Manville, Thermo 12 Keene, Thermasil Owens Coming, Kaylo 10 Pabco, Super Caltemp NA.
Other materials may be used with Ethyl Corporation approval. In periods of mat erial shortage, equipment to 400F may be insulated with Pittsburg Corning Foamglas.
b. Large Cylindrical. Equipment to 1200F and larger than 24" in diameter shall be insulated with curved block or beveled lags of the type and brand name specified in Para a above.
c. Flat. Flat surfaces to 1200F shall be insulated with flat block of the type and brand name specified in Para, a above.
d. Thickness. Insulation thickness shall be as specified in the Equipment List. Insula
tion thickness for equipment not shown in the Equipment List shall be per Table 1. Sf!
3.2 Sechffement. Bands for equipment insulation shall be 3" x 0.020" 18-8 3tainloss=stel
with 18-8
A. J. Gerrard or equal. 12" on centers.
(W 3.3 Weatherproofing
a. Vertical Jacket. Vertical straight shells shall be weatherproofed with 0.016"
thick x la" corrugated aluminum with factory attached moisture barrier.
b. Horizontal Jacket. Horizontal straight shells shall be weatherproofed with 0.016"
thick smooth aluminum with factory attached moisture barrier.
c. Vertical Seams. Vertical seams in aluminum jacketing shall be secured with ^ "
long x ^8 stnls stl sheet metal screws on 6" centers
d. Circumferential Seams. CZircumfere^ti^al seyms in aluminum jacketing shall be
secured with a 3" x 0.020" 18-8 stmnloss steel band at each seam, Continue to
apply bands circumferentially on 18" centers.
^fnls sil
e. Z Clips. Z support clips made from 3" x 0.020" -stainless steel band shall be
installed at the circumferential seams on 18" centers on vertical vessels.
Projections. At all projections (nozzles, brackets, etc) the necessary cutouts
shall be carefully made and weatherproofed with heat resistant mastic, Foster 95-10
or approved equal up to 350F; above 350F use Eagle Picher Stalastic.
Heads. Heads shall be weatherproofed as detailed in Figr 6. Alternatively, if
economical, available, and approved by Ethyl, a formed cover of 0.020" thick
smooth aluminum with factory attached moisture barrier may be used.
3.4 Details. Details of equipment insulation shall be as shown in Figures 5 through 12.
3.5 Irregular Surfaces. Pumps, turbines, and other irregular surfaces sh
`1
and weatherproofed the same as vessel heads.
ETH 002265
KTUYl. ('.OUPORATION
liNOlXlll'Xljn.i DEPARTMENT
SPECIFICATION SP-92-1 HOT INSULATION
Page 5 of 17 -=--Apr74
1
Recommended minimum thickness, nominal inches
pipe insulation for personnel protection
(Surface Temperature less than 161 *F.. Ambient Temperature 80*F.)
Nominal Pipe Size
,
TO 200
201- 301- 401300 400 BOO
501600
Tem jeraturo Hot Pipe, *F.
601- 701- 901- 901700 800 900 1000
m1" and Less 1-
1
1
1
1
1r
1V4 1V4
Wz"
1 1 1 1 . 1 Wz Wz lVi 2
2M 1 . 1 1 1 1 Wz Wz Hi 2
3'
1
1
1
11
Wz Wz 2
2
3 Vi"
1 1 1 1 1 1 Wz 1 Vi 2
4" 1 1 1 1 1 Wz Wz 2 2
5" 1 1 1 1 ' 1 Wz 2 2 Wz
6" 1 1 1 1 W . l'/2 2 2 Wz
8"
1
1
1
1
Wz Wz 2
2
Wz
10"
1
1
1
1
Wz Wz 2
Wz Wz
12"
1
1
1
1
Wz Wz 2
Wz Wz
14" to 18" Wz Wz Wz Wz Wz Wz 2
Wz 3
20" Wz Wz W, Wz Wz 2 2 Wz 3
10011100
2 2 2 2Vi 2 2'/2 Wz 3 3 3 3 3
Wz
11011200
2 2
2V5 2V4 2Vi Wz 3 3 3 3'A Wz 3V4 3 Vi
RECOMMENDED MINIMUM THICKNESS, NOMINAL INCHES, PIPE INSULATION FOR HEAT CONSERVATION.
PIPE SIZE
'/ >; l 11
PIPE TEMPERATURE, DEG F TO 201- 301- 401- 501- 601- 701- 801- 901- 1001- 1101 -- 2001 300 400 500 GOO 700 800 900 1000 noo 1200
-1] 2~
2
1
3
.M/i .i 4
5 6 7
.6
9 10
It 2
12 u 16
13 ~z~
20 2*
3
4.
t
5 4 56
3
RECOMMENDED MINIMUM THICKNESS, NOMINAL INCHES, EQUIPMENT'iNSULATION
FOR
HEAT CONSERVATION.
Temperature Range
Thickness
Up to0OOF 301 to 700F 701 to 900F 901 to HOOF 1101 to 1200F
2" 3" 4" 5" 6"
ETH 002266
WTHYI. COW I'ORATION
i-:N<ilNin!KJNl. Dlil'AJiTMENT
NOTE: Valve* shall b<> insuloted only in live steam and steam traced
SPECIFICATION SP-92-1 HOT INSULATION
Page 6 of 17 --Apt-74-
7y '
HOT SERVICE FIG, 1
ETH 002267
1:TIIYI. ('.OKI`ORATION
1-.Nr.iNiiuiiiNr. Department
SPECIFICATION SP-92-1 HOT INSULATION
Page 7 of] 7 M&rjK
For piping insulation, wire, jacket, etc , see piping insulation details.
PU<kS>*- .ON 'eftxti-
f/us M*-
att Cyx,
VERTICAL PIPE IkJSULATIQK! 5UPPCRT
i.
INSULATION DETAILS
FLANGES^
FIG
ETH 002268
I-.TII YI. COHI'OUATION
HNC.lNlil'RINC. Dli P/VRTMENT
SPECIFICATION SP-92-1 HOT INSULATION
Page 8 of 17 .----Apt~74
3. Secure pipe covering with 16 ga 18*8 wire on pipe* 10** & under; 14 ga 18*8 wire on pipe 12" & larger.
4. SECURE JACKET W7 1/2" LG X NO. 8 STNL~" STL SHEET METAL SCREWS ON 9U CENTERS.
5. FITTINGS SMALLER THAN Z* SHALL BE COVERED W7 INSUL CEMENT (JM450 OR APVD EO) ; 8 WEATHERPROOFED W7GPM MASTIC (FOSTER 35-01 ALUM GRAY OR APVD EO) 1/16" DRY FILM THICKNESS. FITTINGS 2" S LARGER SHALL BE INSULATED W7 A MATERIAL COMPARABLE TO THE ADJACENT PIPE INSULATION & WEATHERPROOFED W7 GPM MASTIC 1/16" DRY FILM THICKNESS. THE MASTIC SHALL BE REINFORCED W7 BEN FOSTER MAST-A-FAB. PREFORMED ALUMINUM FITTING COVERS MAY BE USED IF ECONOMICAL a AVAILABLE.
T. Two layer insulotion shall be applied with joints staggered longitudinally and circum ferentially. Each layer shall be secured as shown for single layer. SEE PAR. 2.8.
7. Weatherproofing Foster GPM 35-01 alum gray to run 3" over jacket on vertical lines and 3" under joeket on horizontal lines.
TYPICAL PIPING INSULATION
HOT SERVICE
FIG, 3
ETH 002269
KTI1YI. ('.OH 1 'ORATION HnoINEURING Department
SPECIFICATION SP-92-1 HOT INSULATION
Page 9 of 17 /W7r
TEMP. OF LINE DEGREES F.
300 425 550 675 800 1000 1200 1400
EXPANSION JOINT SPACING APPROX. SPACING REQ./FEET
Carbon Steel Stainless Steel 50 35 '35 20 20 17
17 12 15 11 11 9
86 75
Aluminum 25 17 11
--
-- -- --
Allowance for LONGITUDINAL expansion of large pipe and fittings shall be based on 1" for each listed number of feet In'the tabic.
, DETAIL OF PIPE INSULATION EXPANSION JOINT
FIG. 4
ETH 002270
. l ii'i |. i'.OUI'OHATI()N
I Nl.INKliNlW. l)l!PAHTMBNT
Seo* with heot fc:*ifcnt mastic,FOSTER 95-10 UP TO 350F, 351 F UP, USE EAGLE PICHER STALAST1C
SPECIFICATION SP-92-1 HOT INSULATION
Insulation on head same thickness as on shell Secure blocks with 3"x.020" 18--8 St Sti insulation straps & seals spaced 12" apart on circumference. Apply tack coot of Foster 35-01 Al gray. Bribed Foster Mcst-a-Fob into tack coat. 1/16" total dry film thickness.
,
For method of weatherproofing vessel heods see Fig. 6.
For type & thickness of shell insulation see Schedule.
Insulation supports by vessel fabricator. * For detail see Fig. 17.
J"x.020" Type 18-8 St Stl insul strops & seals spaced 12" o c over block insulation.
Fit metal jacket as close as possible around projections. Seol with heat resistant mastic, FOSTER 95--10. Use staggered joint construction. Seal cracks & joints with finish cement.
Allow !" space for expansion joint under each si'|>port. For detail see Fin. II.
For detail see Fig. 7.
Fireproofing os specified, by insul contractor.
Two layer insulation shall be upplied with joints Staggered longitudinally and circumferen tially. Each layer shall be secured as shown for single layer.
INSULATION DETAILS VERTICAL VESSELS HOT SERVICE FIG, 5
Page 10 of 17
Nozzle insulation when required to be included in piping insulation.
For detail of floating ring see Fig. 6.
0.016" thick corrugated aluminum jocketing with moisture barrier attoehed.
tape in jacket to be 4" an vertical seams & 3H on horizontal seems.
Apply jocket with No. 8 x " long -STNLS STL sheet metal screws spocea 6" on centers on vertical seems.
^x.OZ)" 18-8 St SH insul straos and seals, at circumferential seams end not over 18" apart. For "Z" clips see Fig. 11.
Handholes & stiffener rings will not be insulated except where specified.
Stiffener rings shall be encased with aluminum flashing.
Insulate & finish bottom head same as top head.
j
INSULATE W7 REMOVEABLE COVER, IF PERSONNEL PROTECTION IS NECESSARY; OTHERWISE, 00 NOT INSULATE.
Top of foundation.
ETH 002271
KTIIVI. COKI'OKATION'
i'.N(ilNl'l!HIN(i DkpAHTMEST
SPECIFICATION SP-92-1 HOT INSULATION
Page 11 of 17
Seal with heat resistant mastic!
DETAIL OF FLOATING RING
ETH 002272
i:tii v \. c:oui*okatiox
1' NC.lNl'UitlNli Dhl'AKTMIiNT
SPECIFICATION SP-92-1 HOT INSULATION
Page 12 of 17
NOTE - Fireproofing of vevsnl sk*rt< i>o* by insul contractor.
DETAIL AT SKIRT
rFIG, 7
ETH 002273
KTriVI. CORPORATION
HN<.ij>rEiim>rr, Diipajrtment
SPECIFICATION SP-92-I HOT INSULATION
Page 13 of 17 jtf
Insulation on heads shall be same thickness as an shell. Secure bolocks with 3/4" x .020" Type 18-8 St Steel Straps and Seals 12" opart on circumference. Apply tack coat of Foster 35*01 ol gray, Embed Foster Mast-o-Fcb into tack coat. 1/16" total dry film thickness
Ovr shell Insulation apply .016" thick SMOOTH aluminum jackal with moisture harrier ut Inched,
Lap in iackcl dial I be 4" on vortical seoms and 3" on horizontal seams.
Apply jacket with No. 8 x 1/2" long STNLS STL
. shut metal screw* spaced 6" apart on both horiiontql
. and vertical laps
*
INSULATE W7 REMOVEABLE COVER, IF PERSONNEL fiBOTECTION IS necessary; OTHERWISE, 00 NOT
For type ond thickness of * insulation, see Schedule
FOSTER 95-10 UP TO 350F, 351 F* UP, USE EAGLE PICHER STALAST1C
Two loyer insulation shall be applied with joints staggered longitudinally and circumferentially. Each layer shall be tcured as shown far single layer.
INSULATION DETAILS HORIZONTAL TANKS OVER 30" DIA.
ETH 002274
r.TU Y I. COKl'OUATION
i N<. I N K I! H JNl l) U HAKTMENT
SPECIFICATION SP-92-1 HOT INSULATION
Page 14 of 17 /A\
FOSTER 95-10 UP TO 350F, 351F UP, USE EAGLE RICHER STALASTIC
Block insulation. For typo end thickness see
schedule.
3/4" x .020" 18-8 stainless steel Insul straps
and seals spaced 12" on centers over block
insulation.
.016" thick corrugated aluminum jacket with
moisture barrier.
Laps in jaeket shall be 4" on vertical seams and
3" on horizontal seams using No. 8 x 1/2" long
STNLS STL 'sheet metal screws 6" on centers on vertical seams.
3/4" x .020" 18-8 stainless steel insul straps
and seals at circumferential seams and not over
18" o c For Z clips see Ftg^ll.
impervious first course such os Focmglas or equal,
sealed with Foster 95-44.
Fit metal jacket as close as possible around
nozzles and projections. Seal with heat resistant
mastic, Foster 95-10.
Use double straps at this point to secure lower
end of heod strops.
Flash and seal around projections and where
roofing overlaps metal siding. Furnish floating
rings where required to fasten insulation straps
For detail see Fig-^6.^/^
Use 3" wide black on root some thickness as on
lhell. Secure blocks with 3/4" x .020" 18-8
stainless steel insul straps and seals spaced 12"
apart on circumference.
Trowel on a 3/8" thick coat of JM30I
finishing cement filling alt voids and craeks.
Prime surface with asphalt primer and weather
proof with 2 plies of 15 lb saturated felt and
one layer of 55 lb asbestos felt roofing in
asphalt mopping.
Allow 1" space for expansion joint under each
support. For details see Fig. Il.^lnsui
suoports by tank fabricator.
Staggcred joint construction shall be used. Two
loyer insuiotion shall be applied with joints
staggered circumferentially and longitudinally.
Each layer shall be secured os shown for single
layer.
!
INSULATION DETAILS HOT STORAGE TANKS
FIG,9
ETH 002275
I- I 11 Yl. CDKI'OHATION
MI. I NI-. I! UIXI I) IS I*ARTME NT
SPECIFICATION SP-92-1 HOT INSULATION
ftage 16 of 17
Apr 74
^
/
fr-'r- i s
CIRCUMFERENTIAL SEAM DETAILS HORIZONTAL VESSELS
DETAIL OF Z CLIP
Clips to be spaced approximately 18,r apart or a minimum of four clips per width of sheet
HORIZONTAL SEAM DETAILS VERTICAL VESSELS FIG. 11
ETH 002276
KTI1YI. CORPORATION
Hngi.vkkrinc. Dup^rtment
SPECIFICATION SP-92-1 HOT INSULATION
Page 15 of 17
^pr 74
/
7s)
Jacket shall be cut to fit at nozzles and projections. Seal with heat resistant mastic, FOSTER 95-10 UP TO 350F, 351F UP, USE EAGLE PICHER STALA8TIC
For detail of flashing at flanges see Fig* 11
SEAL AROUND NOZZLES W7 HEAT RESISTANT MASTIC, FOSTER 95-10 UP TO 350F, 351F UP, USE EAGLE PICHER STALASTIC
Over shell insulation opply .016** thick SMOOTH aluminum jacket with mositvre barrier attached
laps in jacket to be 4" on vertical seems end 3W on horizontal seems
Apply jacket with No. 8 x 1/2" long STNL8 STL h*t metal screws spaced 6" o c' on all -
scorns
Furnish 20 gauge aluminum
jacketing with attached moisture barrier for insulated removable ends, outdoors
Seal cracks and voids with finish cement, JM30I
_
Nozzles when" required shall -be insulated per piping schedule,
NOTE: Exchangers over 30M in dia shall be insulated with beveled lags or curved blocks. Head insulation shall follow contour of the heod
INSULATION DETAILS
EXCHANGERS-HOT SERVICE .
FIG. 10
ML
ETH 002277
KTUVI. CORPORATION
Hnolnkhrtno Department
SPECIFICATION SP-92-1 HOT INSULATION
Page 17 of 17
CONTINUOUS SUPPORT RINGS SHALL BE SPACED 1 2 - 0 - 1 / 2 * .OC
MAX UNLESS OTHERWISE SPECIFIED ON DWGS
DETAIL OF HEAD SUPPORT TYPE "A"
DETAIL OF SHELL SUPPORT TYPE
INSULATION SUPPORTS
Table of Dimensions
Insulation Support Type "A" Support Type "B"
Thickness
Size Plate Clip
Width Plate Ring
1" 2" x 2" U" li" x li"
2"
li"
2" 12" x 12" 2i" 2" x 2"
12"
2"
3" 2i" x 2" 3" 3" x 3"
4" 3i" x 3"
2i"
3"
3i"
NOTE: Insulation Supports by Vessel Fabricator
Bend Line
-1/4* thick steel plate dips welded to head spaced I2N opart. For size of
I. clips see Table on Fig,* 12 fj Weld clip to Bottom Heod
Use some size steel clip os specified for heod support Type "A*
3/B" dia rod extending entire circumference
DETAIL OF HEAD SUPPORT TYPE "Crt
I
INSULATION SUPPORT DETAILS-
ETH 0Q2278
ETH 002279