American Society o/ Heating and Ventilating Engineers Guide, 1931
by Computation) and by the temperature difference between the inside
air temperature t at the proper level (in many cases not the breathing line) and the outside air temperature t0. Therefore,
where
Ht ~ AU (t -- tQ)
(12)
Hi = B.t.u. per hour transmitted through the material of the wall, glass, roof or floor.
A = area in square feet of wall, glass, roof or floor, taken from building plans or actually measured. (Use the net inside or heated surface dimensions in all cases).
t -- t0 = temperature-difference between inside and outside air, in which l must always be taken at the proper level! Note that t may not be the breathing-line temperature in many cases.
Fuel Saving
ECONOMIC VALUE OF INSULATION
Any reduction in the heat losses through the walls and roof of a build ing, such as by the use of insulation, will reduce the amount of fuel required to heat the building.
The saving in coal resulting from the installation of a commercial insu lation in the walls and/or roof of a building can be estimated by the following formula:
where
F = ('U~ U(> X N X (* ~<a) XA CcXEcX 2,000
,,oi
Fc = saving in fuel in tons of coal per heating season. , U = coefficient of heat transfer of construction without insulation. U\ = coefficient of heat transfer of construction with insulation.
N = number of hours during heating season.
t -- inside temperature at proper level for wall or roof. <a = average outside temperature during heating season N. A = net wall or roof area. Cc = calorific value of coal. Ec = overall efficiency of heating system.
To illustrate the use of this formula, suppose that the coefficient V of a certain factory roof without insulation is 0.30 and that the coefficient Ui of this roof with a given thickness of a certain type of insulation is 0.15. Let it also be assumed that the heating season is 210 days or 5,040 hours and that the average outside temperature L during this heating
season is 35 deg. fahr. The roof area A is 10,000 sq. ft., the calorific value of the coal is 13,000 B.t.u. per pound, and the overall efficiency of the
heating system is assumed to be 60'per cent. If the inside air tempera ture t is 75 deg. fahr. (at the roof in this case) and is maintained con stantly during the heating season, the saving in fuel will be:
(0.30 - 0.15) X 5,040 X (75 - 35) X 10,000 tc 13,000 X 0.60 X 2,000
= 20 tons of coal per average heating season.
If in the foregoing problem the building is heated intermittently, the fuel consumption and fuel saving will be reduced correspondingly, but
42
Chapter 3--Heat Losses by Transmission
not in direct proportion to the number of hours the heating plant is not in operation. Recent tests indicate that a saving in the fuel consumption of from 10 to 20 per cent will result by allowing the heat to be shut off after working hours and only heating the building to the required tem perature during the period of occupancy each day. Hence, the fuel saving
of 20 tons would probably be reduced about 15 per cent by shutting off the heat at night in which case, the net fuel saving would be 17
tons of coal per heating season.
If the applied cost of the insulation is 11 cents per square foot for the thickness involved in this case,, and the cost of coal including the han dling of it, and disposal of ashes is $10.00 per ton, the annual return on
the investment will be 100 X ^ 16*000 or
Per cent' neglecting
insurance and depreciation.
Experiments recently conducted at the University of Illinois indicate that ceiling insulation increases the temperature head, thus offsetting the effect of the insulation to a slight degree, and changing the value
of l in equation (13). In the case of Hat roofs, the change in temperature head is due solely
to the slight increase in temperature of the air underneath the ceiling. In the case of pitched roofs with unheated attics, not only is the tem perature underneath the ceiling higher, but the attic temperature is lower after the installation of the insulation, excepting where the attic contains windows, ventilators, etc., in which case the attic temperature will be practically the same in both instances, and will approach or equal the outside temperature. If the attic contains no windows, ventilators or wall surfaces, the attic temperature before and after the insulation is. installed may be estimated by equation (11), assuming the temperature t under the ceiling to be the same in both cases. By using the combined coefficient of transmission of the roof, attic and top-floor ceiling (Table 32), then the change in temperature of the air in the attic space can be neg lected, and only the increase in temperature under the ceiling need be
taken, into consideration.
To be strictly correct, this change in temperature head should be con sidered in figuring fuel saving problems, but in most cases this degree
of accuracy is not warranted.
In the case of vertical walls, the temperature head will be the same
before and after the insulation is.installed. :
If oil is the fuel burned the annual saving in gallons of oil can be esti
mated by the following formula :
Fz,o_----(-U-------U--i)cXTxNeXTx(t W- t-o-)--X---A-
(14)
where
F0 -- saving in fuel in gallons of oil per heating season. Co -- calorific value of oil. E0 = overall efficiency of the heating system for an oil-fired furnace
(usually taken as 70 per cent). W = weight of oil per gallon, pounds.
43