Document 8RkV9YpkwbkgRoYv7n4g6bMyo
HEATING VENTILATING AIR CONDITIONING GUIDE 1941
For example, corresponding to a degree of. saturation of 40 per cent at 100 F the difference between relative humidity and degree of saturation is 6.67 X 0.40 X 0.60 -- 1.6 per cent; hence the relative humidity itself is 41.6 per cent.
Dew-point
If moist, air. is cooled at constant humidity ratio W and constant ob served pressure P, a temperature will be reached at which the air just becomes saturated, and. formation of a liquid (or solid) phase just com mences. This temperature is called the dew-point corresponding to the given humidity ratio and observed pressure.
Example 5. Find the dew-point of the humidified air of Example 4.
. Solution. The given humidity ratio is 0.006296 which is the saturation value at 44.96 F (Table 6, assuming the total, pressure to be 29.921 in. Hg). This is therefore the dew point of the humidified air.
Example 6. Find the degree of saturation of air having a temperature of 90 F, a
dew-point of 60 F.
.
Solution. Assuming the total pressure to be 29.921 in. Hg, the humidity ratio is given
in Table 6 as 0.01103 lb per pound dry air. The saturation humidity ratio at 90 F is
0.03102 lb per pound dry air; hence the degree of saturation is 0.01103 -5- 0.03102 = 0.365 or 35.5 per cent.
Volume
' The .volume of moist air per pound of dry air contained in it is a very
useful quantity. It should not be called specific volume; for the adjective
specific should properly refer to volume per pound of mixture. Using
Equations 10a and 14 an expression for the volume per pound of dry air
is.obtained, namely,.
BaT , ( lF8Bwr\
V -- +H
p~)
(16)
' Example 7. Find the volume (per pound of dry air) of the humidified air of Example 4.
-( ) (-S: Solution.
53.35 X 529.7 \ , ,, An {0.01574 X 85.78 X 529.7\
29.92 X 0.49115 X 144 +0 40
92 X 0.49115 X 144
= 13.354 + 0.40 X 0.338 = 13.489 cu ft per pound dry air.
` Equation 16 is linear in degree of saturation p. and of the form
V = t>a + P as
' ' (17)
where ta denotes specific volume of dry air at temperature T and pressure P; and t/as denotes the difference between this and the yolume of the saturated mixture per pound of dry air 8. Strict linearity is, of course, a result of the use of Dalton's Law; but it is expected that it can be retained as a very close approximation even when the abandonment of Dalton's Law becomes possible.
' Example 8. Work Example 7 using Table 6. ' Solution: v = 13.34 -f- (0.40 X 0.34) = 13.48 cu ft per pound dry air.
'1
By putting p = 1 (100 per cent saturation) in Equation 16 an expression for ti8, the volume of saturated air per pound of dry air, is obtained. Values for standard atmospheric pressure (29.921 in. Hg) are listed in Table 6. Often it is preferred to express this information in terms of density, that
20
CHAPTER 1, THERMODYNAMICS OF AIR AND WATER MIXTURES
is weight of saturated air per unit volume. This can easily be done by dividing vs (volume of saturated air per pound of dry air) into (1 + ws) (weight of saturated air per pound of dry air). Thus, at 100 F, 29.921 in. Hg, the density of saturated air is, from Table 6, 1.04293 -f- 15.07 = 0.06921 lb per cubic foot.
Values in Table 9 are intended to aid in determining the density of saturated air at different pressures. Values for temperatures and pres sures other than those listed can be obtained by linear interpolation
which is aided by the next to last column of figures. Thus, at 100 F, 29.921 in. Hg, the density of saturated air is, from Table 9, 0.06818 + (4.21 X 0.00024) = 0.06919 lb per cubic foot, in approximate agreement
with Table 6.
A column of figures is included in Table 9 giving the approximate average increase in density per degree wet-bulb depression. This makes it easy to calculate a value for the density of moist air taking into account its moisture content as well as its temperature and pressure.
Enthalpy
Thermodynamically, Equation 10a implies that the specific enthalpies
of dry air and water vapor are independent of pressure and that the
enthalpy of moist air (per pound of dry air) is the sum of separate con
tributions from the dry air and water vapor according to the simple
equation
h = Aa + n (WoM
(18)
Equation 18 is also linear in degree of saturation p and of the form
h = ha -F p ha3
(18)
where ha denotes the specific enthalpy of dry air at the given temperature and total pressure; and has denotes the difference between this and the enthalpy of the saturated mixture per pound of dry air ha. Provisional values are listed in Table 6.
Example 9. Find the enthalpy (per pound of dry air) of air at 96 F, 60 per cent saturation and 29.921 in. Hg.
Solution. Using Table 6, h = 23.04 + (0.60 X 41.58) = 47.99 Btu per pound dry air.
Thermodynamic Wet-bulb Temperature
If liquid (or solid) water be injected into an air stream it will evaporate and thus increase the humidity ratio of the air. Enough water may be injected to saturate the air. If the process is one of steady flow with observed pressure constant; if it is adiabatic;' and if the temperature at which the air reaches saturation coincides with the temperature of the liquid (or solid) as added; then the common temperature is called thermo dynamic wet-bulb temperature. This lengthy definition is easily visualized by referring to Fig. 1 in which tiw denotes the specific enthalpy of the liquid (or solid) as injected.
The process being adiabatic, weight and energy accountings give
hi + (Ws - W,) h'w~= hs
(20)
If the temperature of the saturated air at the leaving section coincides 21