Document 8RG24mGwOopgO07XB46GQz7VB

1 . MONS 000408 raUQJSKYMC ODs uncompromising performance from an environmentally compatible fluid The challenge In developing a new dielectric fluid to replace PCB In General Electric power capacitors was to maximize performance and minimize risk to the ' environment. Many of the more than one hundred fluids GE tested were environmentally acceptable. And many of tlicso fluids could even meet minimum product application requirements. But the real challenge was to produce an environ mentally compatible fluid with no sacrifico, no compromise In capacitor performance. General Electric met that challenge. The result Is achieved wtlh Diclcktrol II liquid, an ester-based capacitor fluid that meets or exceeds PCB performance. . Early In the GE program, Phthalate ester-based fcnprcgnant* emerged as the most promising candidates. Since 1972, GE has amassed millions of KVftR hours of Held service expcitence with Phthalate ester Irnprcgnants In power as well as In component-type capacitors. These norvPCB capacitors have gone to customers who by choice or of necessity have avoided PCB Impregnant*. Results have been excellent, for example 500 power capacitor units which have been In service In Japan for up to 2Vi yoars have led to only 2 rcpoited field failures. To assure that both environmental and performance criteria were met, GE conducted an exhaustive product testing progrant. Environmental testing has been and continues to bo carried out by some of the top Independent research organizations In the United States. Product performance testing Is done primarily at tire Capacitor Products Department in Hudson Falls. N.Y More than 40 million KVAK hours of power capacitor testing has been completed to date. Additional testing continues. These are the latest results. Environmental compatibility: In acute toxicity tests, Dlelcktrol II capaellor fluid has demonstrated low toxicity __ to humans, fish, fowl and soil microorganisms In concentrations that can reasonably be expected to occur. Even at concentrations far in excess of those expected, Dielektrot II flukl exhibits a low toxicity comparable to marry other commonly used industrial materials. . Acute Oral Toxicity -- Rats: Ran arc k-d a tingle dose, then ebtcrvrd Z weeks. Ttwrc dotage kveh pet leu. Tc*l to prerequisite to tS'day fading tardy. liquid LO SO body 1.| DINJIKTHOt. H NonPCOA Nun ICR R Brake fluid base Ctycetln Rvnwac 4 4 >10 IT \b Hair; V* rrJntev apprutUnial,' Mwt dcK lut a 70 Kf> (ISS fr.l man. Muter by 10 Dlelcktrol II fluid ha* not been found to be carcinogenic. The tests conducted lo date reveal that Dirk'kiiol II fluid degrades and metabolizes and thus will not persist In the environment. Preliminary lest results also Indicate there Is no btoaccutmilallon problem. Performance: Diclcktrol II capacitor performance Is equal to or better than that achieved with PCB. Partial discharge or corona start characteristics is one area where Dielektrot II capacitors arc dearly superior Power factor Is another characteristic In which Dielektrot II units ' outperform the PCB impregnated ones throughout the normal temperature ranges. Particularly significant Is the high dielectric constant of Dielektrol il liquid. This key characteristic permits the capacitor unit size to be essentially the same as that of PCB Impregnated units without raising the stress Imposed on the impregnant to values higher than those consistent with past practices. * Through overall performance Improvements, especially that of partial discharge, Dielektrol II units exhibit substantially greater reliability and life over equally rated fCB units In accelerated life tests. The same results are expected In the field. Ratings/Casc size: Dielektrol tl unit ratings, configurations and case sizes are virtually unchanged from GE Pymnol units and can be sobsttuted as direct replace ments. They fit all standard NEMA rack structures and can be paralleled with previously installed PCB units. Quality Power capacitor design technology demands consistently high quality In alt components and maieri sis and little variance can be tolerated without affecting field performance. For this reason. General Eleciiic bellcv- s that In-housc processing of major capacitor materials, sue!* as the liquid Impregnant as well as polypropylene film and aluminum foil, provides a better quality and more predictable supply than purchasing these key materials from outside vendors. In keeping with litis philosophy, Dielektrol II Is formulated and refined at Hudson Falls specifically for power capacitor use. By btending In-house and applying our own strict quality standards to the incoming chemical components and the refined blend, consistent product quality Is assured. Cost: Increased cost of the new Diclcktrol II units has been held to a minimum as the new fluid is compatible with existing dielectric structures and requites only a few key changes in manufacturing processes. Disposal: Unlike PCB capacitors, Diclcktrol II units have no severe disposal limitations other than normal good Industrial practices for chemical matcrtals. Suggested disposal methods are incineration or dty landfill disposal consistent with applicable regulations. Availability: Dielektrol II units 010 available now. Contact your local GE sales representative or write lo General Electric Company. Capacitor Products Department, Hudson Falls. New York 12839. f> likd.fMih < #* CWncifil t lr<Mr Cemfttiy HONS 000410 1 4 V `4 ; H A .' i V; ,i ' .1 .I 4. f<" v;- ' -- iW'.,.** ~ v" . v i; a! II 'I! ;V . i a '*> ; V .! ! 1 1 HONS 000*11 1I1V I -.1 hi ----- the living proof Every man-made subilanc makes some Impact on tho "natural" environment, The goal In developing Diclcktrol II liquid was to produce a fluid that would constitute no significant hazard to life forms and neither persist nor accumulate In the environment. All data 1 accumulated to dale show this goal has been achieved. To minimize (ho possibility that the new compound might have unknown and undesirable environmental characteristics, commodity liquids with a long history of use In subslanllal volume were chosen as the major constituents of Diclcktrol II fluid. For example, Dieteklrol II Imprcgnnnl Is composed of a Phlhalate ester plasticizer ' mixed with a halocarbon widely used as a textile dye solvent. Because the components have been used extensively In the past, GE has been able to review environments! compatibility through standard toxicity data bases such as Chcmlinc and Toxlinc. In essence, GC was able to "pte-assets" Oiefektroi It fluid's environmental Impact No significant effects have been recorded. Independent Confirmatory Testing lb confirm the environmental compatibility of Dieteklrol II fluid, GE commissioned several independent research organizations to conduct a wide variety of experiments and gather more data. While some tests are not yet completed, the preliminary data consistently supports Diclcktrol II fluid's environmental compatibility. Ibxldty Toxicity experiments assess the effects of a single massive dose (acute) or smaller doses over periods of time (chronic), Data (rom acute toxicity tests show Diclcktrol II ' fluid Is far less toxic titan PCB and approximately as toxic ' os many widely used Industrial materials considered * nonhazardout. Inhalation: Rats were put In closed containers and made to breathe Diclcktrol II liquid vapors (or one hour. Result: No effect was found during 14-day observation period. Dermal contact: Palettes of rabbit skin were exposed by staving and undiluted Diclcktrol II fluid put on skin and covered for 24 hours. Result: During a 14-day observation period, slight irritation was found such as might be caused by tome laundry soaps. ' l-yc contact: One dose of undiluted fluid was drojmrcd Into the ryes of rahblls. Result: No effect dudng .a 72-hour observation period Ingestion: Rats were led various concentrations of Dtrlektrol II fluid for 28 days. Result: Concentrations jtat might (to exported to occur do tto! pose a hazard. Pints (bhwglll, fathead minnow) were placed in tanks with Various concentration* of Dtelrklrot II fluid. Result: Dlck'kifot II flutri is approximately b times less toxic than PCB. It Is unkkfty to cause harm at concentrations which can bo expected to ocrur. Micro-organisms (4 difteicnt bacteria) were Introduced to soil impregnated with Diclcktrol II fluid. Result; Growth was not inhibited even at concentration# of 5,000 parts per million. Birds (pheasants, ducks) wcic fed single doses at. various conccnlratlons of the fluid. Conclusion: It Is unlikely to cause harm at concentrations which might be expected to occur. Biodcgradation/Bloaccumuhition " DielekUol II fluid biodegrades. In a river die away test, major constituents of the fluid and the refined Diclcktrol II fluid Itself aft produced results which Indicate that Dicfektrol fl fluid will not persist In the environment. Preliminary bloaccumulalion test results suggest that accumulation of Diclcktrol II fluid In tissues of fish tested Is so low as to be Insignificant, , > Continued testing * Additional testing is currently under way. Interim tesufls from chronic toxicity tests as welt as further . biodegradation and bioaccumulallon studies are expected by mid 1977. Results will be available as tests ore completed. LC SO Pith--W Hours Static Test BhicpIU Fathead mlnaon-i Dtetektio) II Non-PCB-A PCB-I2M 1) ppm 1 NA 16 ppm r t *AhtiMto lutdt toniktci'id NXr; LC 60 k-U Vicmv ronerntmtoA to pwu prr mflbon hrrmary to art 60% MOtuStyel SkX to fha UnX Lowet ppn> fcgwtt todkatt Mfhat toakty 28-day Rat Feeding Study ' lltpliral rmcfNliatlaa No edict Um tint I'vel txetektiot 11 NwPCBA PCD-1016 'Ahemaac Sutdi>mtdeicd 250 ppm 190 >25 1260 50 25 Natt: Yta M day k1 conrmkMtof* in partt prr mfXonMcniary to tauw Iw tmbrycHwnh hi tan. lawn ppm hsutn hidtaia MyWt toxkity HONS 000412 / >i ) " ' '*' ' * ' *7 1: /ft f ) ' a;~. .., mn- m.?fe i *( i / j i \ -:'l i why a III B classification doesn't tell the whole story . DleleklroJ ]| flukes, Me all other non-PCB fluid* developed to dale, (alls into the NPPA III 13 combustible category But there's more to Diclcklrol il liquid than tire III B designation Implies. . First, the NFI'A classification of the liquid does not mean the capacitor Is going (o tail and burn. GE has shipped more lhan 100,000 castor oil. mineral oil, and "GECONOL" Impregnated unlls (all lit B's) and overall the 90-years of experience has produced results comparable to these achieved will) PCB's, No fires occurred during Dielcktrol II fluid's 40 million KVAR hours of accelerated Ife testing, testing that pushed many units to the end - of life. ... y ' . * . >- . | j j t [ j ! j < ; Dtdektrol II Units Sclf-cxtingulsh '. During what Is probably the most extensive case rupture Study ever undertaken, GE deliberately failed 400 PCB, Dtelektrol II, and other non-PCB impregnated units and ' caused them to rupture. High speed movies record the results and one thing was confirmed: Dielcktrol II unit fires generally sclf-cxtingulsh In seconds due to the high fire point. In excess of 250C, of the fluid. Note: fSee page 10). For comparison, other non-PCB units would often continue to burn after Dtelektrol II units iqtf-extingufshed. ' % * Dtelektrol II Capacitor Fusing ' - Correct fusing minimises the possibility of case rapture and fire. Analysts of the case bursting data of several dHTuent : KM\R and voltage ratings indicates no significant difference between tire times to rupture of Dielcktrol If and PCB units. Thus, present fusing practice wifi provide the s* me . order of protcclion against case rupture with Dtelektrol II capacitors as previously experienced for PCB unlls. Supplementary Protection Additional protcclion against case rupture and Ms attendant fire hazard can be furnished In the form of pressure sensors built Into the GE capacitors. This optional protection feature can be used to operate capacitor switching devices, thereby protecting against low fault currents. Fusing lends to be least effective In low current fault occurrences. For more information on environmentally compatible Dtelektrol II Power Capacitors, contact your local GE representative or write to General Electric Company, ` Capacitor Products Dept, Hudson Falls. N.Y. 12R39. HONS 000414 W' "OUV/U/WAUSui >4 13 WM as good or better than PCB . Environmentally compatible Dielektrol II capacitors make no performance compromise. Overall characteristics are as good as PCB and in some areas significantly superior. Sec (or yourselt The results provided aro the product of move than <10 million KVAR hours of testing. Capacitance vs Temperature: Dielektrol II fluid outperforms PCB... there is no loss of capacitance to -40*C. Average capacitance Is better titan rated throughout normal temperature ranges to 90*0. See Figure #1. - Power Factor vs Temperature: Better than PCB. ( Curve for Dielektrol II fluid is lower than PCB at typical ' operating temperatures with losses less than 0.5 watts per KVHrt. Dielektrol power consumption will be less than ` lof PCB units. See Figure #2 and Figure 43. Power Factor vs Voltage vs Temperature: Excellent power factor stability with Increasing voltage Is shown in < Figure #4. Dielektrol II fluid's long term power factor ' stability Is confirmed by life tests at voltages In excess of twice rated. Partial Discharge Inception Voltage (DIV): Clearly superior to PCB units. Sec Figure #5. A substantially higher DIV is experienced over the normal operating tange. Measurements were made on Individual rolls In fuisizc powci'capacllors. More reliable, longer-lived capacitors are expected because of the greater margin between rated and partial discharge Inception and extinction levels. AC Breakdown: Individual capacitor elements consistently demonstrate AC breakdown values exceeding four times rated voltage. Even In applications subject to severe overvoltages and substantial transients, Dielektrol II capacitors are expected to deliver long-lived reliable service as a resull of the high AC breakdown values. ' See Figure 46, NEMA-ANSI Design Tests. Dletcklrol It units exceed all requirements (or DC dielectric strength, Impulse withstand, thermal stability, RIV and voltage decay. .. . *$#**** .- W'*, .ifeft* `ttn#; b, ... -V-,' i.{ **Vl *' 11 A t t}i fesBCWfev . .. . ' ,i -.i : ..VaI _... ' ; ................... . .u . -.:h '<*''. --W ...,.................................... **t 'Jl'WiiV ' ' r-er . *. . > l.* ' ; f " - : '/ 1L...... ti.. j... .."it. 1 . >, . 1" , . . ip " Yyv^ I : Jl. il ii (V jl.. .11...' , IJ'-rV'-l' : - ' Ji'i .. ^ /;. . ,. ' ' ./'.I HONS 000416 V-n:$fl mm the foundation for confidence Life Tests Units are being tested at 120% to 225% of rated voltage In ambients from - 40 C to 70'C. Kesult: Under all conditions, the Dielcklrol II units meet or exceed the pcrfomance of PCB unit*. Many l*CB units failed In less than 100 ftours due to partial discharge damage. Most Dleloktiol H units arc still on test after more than 4.000 hours under conditions which are equivalent to 100 years of normal service. ' ACCELERATION % RATED AMDIENT VOLTS 1LMP r)IIXS:KTROLtl UNITS SURVIVING AFTER SOT* OF ECU CAPACITORS FAILED . FULL-SIZE POWER CAPACITORS m tve 90 ns ss wo K wo ss 70 . 90 SO COMPONENT CAPACITORS 0Mtf en own 40 mNpn KSMt-kov* af MttteiMfa tn 'rrrtr' Switching Tests Dcmonslate ability to withstand duty in outdoor switched capacitor banks. Low Temperature Switching Tests . tmprcflnunl_____AmbUwt SOM* VMUsc* DJPir.KTnoui DIRUKTROLH -arc mxto'mxmld -WC_______J20% tol&0% nted _ AH totti were Maned wMi vnut cooled In amNant tempriMur. andMiirtird on wMia pcaSaamlcatvofttfr rquMto 170to IAU%ot di srak60HfMl wSayr. tttiull: Nataltwnia dale afii I mu at (tilt. Design and Process Proof Test Dielcklrol li capacitors have passed type tests structured to establish the product's reliability. For example, the test whkh qualified the 7620 volt-200 KVftR capacitor, was completed In December 1976. It is detailed below Design subjected to proof test--Cat. No. 58L107KC2 Design Issue Date: November 23,1976 ' Wt. 103 Lbs. She 5xl3Vix 26V. Design Parameters--FUm/Papcr Dielcklrol II Liquid Impregnated . 1524 voli/sectton, avg. stress 1037 vofts'mfl. film stress 1246 volU/mD Test Vehicles--Capacitors which had been subjected to a DC dielectric withstand tesi and PF stabilised by AC energisation. Step 1 -- Open one capacitor and DC breakdown rolls (elements) ' Establish--Average toll breakdown in volts DC Step 2--Test remaining three capacitors a. Read rating voltage PF--@25*C b. Apply 3 times rated AC for 5 seconds room temperature--all three units passed. c. Energise the three units (> 130% rated AC for 250 hours In room temperature ambient--aH threo units survived. d. Subject units to 6.25 x rated DC for 10 seconds--all three units passed. Step 3--Characterise lire three units tested. Rated Voltage Power Factor Rcchcck: All values within 0.005 ol the original. Roll Breakdown: ' Average In volit DC greater than Step 1 All values above 6.25 x-ralcd Conclusion --Cat. No. SBL107KC2 passed. Assurance of reliable long-lived service by capacitors of this design and construction whkh are manufactured by the same processes Is provfdedlH'causc:* ! 1) the capfttiror's atrlliiy to withstand voltage acceleration without degradation ol the dielectric system is demonstrated ly the power factor stability and (2) the capacitor's ability to survive transients and extended oveivollago Is proven by lire maintenance ol dtelechk itinoU HONS 000.17 I HONS 000418 A`l.: ii-'-'-'k' . .: . - ,,, % :<* -.'vy' {' ............... `.-..iVi - v ^ ;y<f T, EC?.., |*rv>v?>^*r ' . ! }**K . 1' wr w ! '.''s': .^ .; 'p:*:' - .'- ' - -'V..: ' ,.v-'^:`; -.'' ; " '.'. , \v" ; ' ~.}S'v" HONS 000419