CHAPTER 21
1959 Guide
respectively. These charts were developed by the ASHAE Research laboratory.1
The charts, figs. 2 and 3,` were constructed from die basic flow equation for the pressure loss in circular ducts (see Chapter 4):
(4)
where
H/ *=* head loss due to friction, inches of water. / " a nondimensionai friction coefficient, which for airconditioning work depends upon Reynolds number and the relative roughness of the conduit.-Approximate values of f were taken from the work of Moody* where e ** 0.0005 ft. (See Chapter 4, Fig. 4, Relation Between Friction Factor and Reynolds number.) It is numeri cally equal to the reciprocal of the number of duct diameters required to cause a pressure loss equivalent to one velocity pressure. I = length of conduit; feet'. D * inside diameter of conduit, feet.
H. = velocity pressure of mean velocity, inches of water..
The air friction chart is based on standard air with a den sity of 0.075 lb per cu ft, flowing through average, clean, round, galvanized metal ducts having approximately 40 joints per 100 ft. Fig.-2 should not be used to obtain values below the charts, by extrapolation, because critical flow would occur in this region and values so obtained would be unreliable.
Variations in air temperature of the order of 20 deg from 70 F affect duct friction very little. Figs. 2 and 3 wm therefore be used for aii air systems with temperatures from 50 F to 90 F.` For systems carrying air at much higher tem peratures, however, the values found in the charts must be corrected.' To determine the friction loss in such systems, the actual flow rate or velocity existing at the nonstandard con ditions must be used.
Changes in humidity, or the usual changes in barometric pressure or in the pressures required to circulate the air through the systems, have little influence on duct friction and can be disregarded in calculating friction losses in ordi nary air-flow systems.1 For unusual conditions, the friction .values obtained from Figs. 2 and 3 must be corrected.'
For ordinary applications, an excellent approximation for nonstandard temperatures is
where
A, -- AA,
(5)
A, " friction loss under actual operating conditions, inches of water;
he -- friction loss obtained from Figs. 2 and 3 using the ac tual Sow rate or velocity existing under the nonstand ard conditions, inches of water.
K -- friction loss correction factor, obtained from Fig. 4, dimensionless.
For ducts of other than standard sheet-metal construction, correction factors may be obtained from Figs. 5 and 6. The correction factors shown m Fig. 5 were computed for the value of , the roughness in feet, shown in Table 1.* Most ductwork today is fabricated from galvanized-iron or alumi num sheet metal, or flexible tubing. Fig. 6 presents in graphi cal form the recommended correction factors for aluminum
ductwork.4 The correct friction loss for ducts of other than standard sheet-metal construction may be determined by -multiplying the loses obtained from Figs. 2 and 3 by the factors found in Figs. 5 and 6.
Accurate experimental data on the absolute roughness for flexible tubing are not yet available. There is also little information on the friction loss in ducts lined with acoustical material. Until definite information is available, it is recom- mended that the correction factor for very rough pipes be . used for uncovered soft material, and the factor for medium roughness be used for material behind perforated metal.
Example l illustrates the use of Fig. 3 to determine friction losS in a galvanized sheet-metal duct. Example* t, S, and 4 illustrate the use of Figs. 4, 5, and 6 in applying correction factors for ducts of other than sheet-metal construction and for air at high temperature.
Example 1: Determine the friction loss when circulating 10,000 elm of air at standard density through 75 ft of .24-in. diameter galvanized duct.
Solution: Find 10,000 cfm on the left scale of Fig. 3 and move horizontally right to the diagonal line marked 24 in. The other intersecting diagonal shows that the velocity in the pipe is 3200 fpm; Directly below the intersection it is found that the . friction per 100 ft is 050 in.; then for 75 ft the friction will be 0.75 X 050 -- 038 in. In a like manner, any two variables may.
To correct for pip* rovghnmu multiply friction fact ofetafcwd from fig*. 2 end 9 by correction factor obtained from Fig. 5.
Fig. 5___ Correction Factors for Pipe Roughness
: -\ f I > j (* 1 ] V * ; \ i
-
4 i f ` *
** -
Air Duct Design
287'
Table 1 .... Values of Roughness < for Different Rpes*
Dogtvo Pipe of Ibugfcmtr
be determined by the intersection of the lines representing the other two variables.
Example t: If the duct in Example 1 is very rough, instead of galvanized, with 40 joints per 100 ft, find the total friction.
Solution.* On Fig. 5 find (by interpolation between 12-in. and 40-in. pipe) the intersection of the 24-in. very Tough pipe line and the 3200 fpm velocity ordinate, and at the left margin read a correction factor of 2. The friction loss in the rough duct is therefore 2 X. 038 -- 0.76 in.
Example 3.* If the duct in Example 1 is made of aluminum, of galvanized iron, find the total friction.
Solution: On Fig. 6 find (by interpolation between 12-in. and 36-in. pipe) the intersection of the 24-in. line and the 3200-fpm velocity ordinate, and at the left margin read a correction factor of 031. The friction loss in the aluminum duct is therefore 031 X 038 = 035 in.
Example 4: Determine the friction loss in the duct of Ex ample 1, if the temperature of the air transmitted through the duct.is 200 F.
Solution: For t -- 200 F, the density of the'air is = 0.060 lb per cu ft. Hence, the actual air-flow rate in the duct is
a 10.000 X 0.075 12,500 cfm 0.060
and the actual velocity
Qc 12,500 A m 3.14 4,000 fpm
With Q -- 12500 and D = 24 in., find A. -- 0.77 in. of water per 100 ft in Fig. 3 and K -- 0335 in Fig. 4. The friction loss under actual operating conditions is:
A. - 0335 X 0.77 = 054 in. per 100 ft.
The friction loss for 75 ft is then 0.75 X 054 = 0.48 in.
CIRCULAR EQUIVALENTS OF RECTANGULAR DUCTS .
An air-handling system is usually sized first for round ducts. Then, if rectangular ducts are desired, their sizes are selected to provide flow rates equivalent to those of the round ducts, originally selected.
A comprehensive study at the ASHAE Research Labora tory proved that for most practical'purposes rectangular ducts of aspect ratios not exceeding 8:1 will have the same friction pressure loss for equal lengths and mean velocities of flow as a circular duct of the same hydraulic diameter. When duct sizes are expressed in terms of hydraulic diameter, and when equations for friction loss in round and rectangular ducts are equated for equal flow rate and equal length, Equation 6 giving the circular equivalent of a rectangular duct is obtained.*
Drawn Tubing......................... ..... New Steel or Wrought Iron Pipe..
Galvanized Iron.............................. Average Concrete........................... Average Riveted Steel...................
Very smooth Medium
smooth Average Medium rough Very rough
0.00000150.00015
0.00056.003. 0411
* Used in computing value* for FI*. S.
where
. (aA)*-m d. 130
1.30
(o + '**
(05)' (o + 6)*
(6)
a = length of one side of rectangular duct, inches. b " length of adjacent side of rectangular duct, inches. da " circular equivalent of a rectangular duct for equal
friction and capacity, inches.
Table 2 gives the circular equivalents of rectangular ducts for equal friction and flow rate for aspect ratios hot greater than 11.7:1 based on Equation 6* Note that the mean velocity in a rectangular duct will be less than in its circular
equivalent. Multiplying or dividing the length of each side of a duct
by a constant is the same- as multiplying or dividing the equivalent round size by the same constant. Thus, if the cir cular equivalent of an 80 x 24 in. duct is required, it will be twice that of a 40 x 12 in. duct, or 2 x 23.0 = 46.0 in.
DYNAMIC LOSSES
Wherever eddying flow is present, brought about by sudden changes in the direction or magnitude of the velocity of the air flowing, a greater loss in pressure takes place than would occur in a steady flow through a similar length of straight duct having a uniform cross-section. The amount of this loss,, in excess of straight-duct friction, is termed dynamic-loss. Although dynamic losses may be assumed to be caused by changes in area actually occupied by the air flow, for con venience they are divided into two general classes: (1) those caused by changes in direction of the duct and (2) those caused by changes in cross-sectional area of the duct.
Dynamic losses vary substantially as the square of the mwin velocity of the air, and are therefore conveniently ex pressed as a fraction of the velocity head:
*`-c()'
m
. where
Ed -- dynamic pressure loss, inches of water. V -- mean velocity of air flow, feet per minute. C = an experimentally determined constant (dynamic loss coefficient).
Where different areas are involved, subscripts are used to denote the area to which the coefficient applies, as C\ for inlet area, Ct for outlet area, and C, for orifice area.
The dynamic loss coefficient C is dimensionless and repre sents the number of velocity heads lost at the conduit transi tion or bend. Values of the dynamic loss coefficient for elbows