Multi-Functional Powered Roof Ventilators
MODEL ER (Exhauster and Potent No. 2700931
Recirculator)
Other patents pending
MODEL ES (.Exhauster and MODEL PRE (Power
Supplier)
Roof Exhauster)
MODEL RS (Recircu- DELVXE MODEL ERS lator and Supplier) (Exhauster, Recirculator and Supplier)
Unit selection table dependent upon roof height (To be used with all models except Power Roof Exhausters)_________________
Max. Roof Height--To 12' 14' 16' 18' 20' 22' Over
Genie-Air Unit Size-- 15 17 19 21 25 31 38 GENTE-AIR Performance Data For All Models
s
Unit size
fi Voltd JS
u* sx
15-10 1000 1140 w 1 15-14 1400 1140 ** 1
115 115
17-18 1800 114C V* 1 115-230
17-22 2200 1140 H 1 115-230
Drive
DD DD DD DD
Weight
PRE ER
70 80 70 80 75 85 75 85
19-27 2700 1140 u 1 115-230 DD 19-30 3000 1140 1 115-230 DD
85 95 85 95
21-33 3300 1140 M 1 115-230 DD 21-37 3750 1140 H 1 115-230 DD
100 110 100 110
25-41 4100 1140 M 1 115-230 DD 25-47 4700 1140 K 1 115-230 DD
150 160 150 160
31-55 5500 850 *$ 1 115/230 31-65 6500 750 *$ 1 115/230 31-80 8000 750 Vt 1 115/230
BD BD BD
260 300 260 3C0 265 305
38-10 10850 900 M 3 220/440 BD-DD 310 360
38-13 13000 545 l 3 220/440 BD
315 365
38-14 14400 1140 1 3 220/440 DD 315 365
38-16 16800 1140 IH 3 220/440 DD 320 370
GENIE-AIRS exhaust, recirculate, sup ply or mix recirculated and supply air-- any 1,2,3 or all 4 functions with the same unit. MODEL ER exhausts in summer and re circulates in winter. During the recircu lating cycle the butterfly dampers, which seal the opening between the roof jack collar ana sleeve section, remain in closed position and the heated air trapped at the roof line is recovered through the opening between the venturi and jet and returned to the occupied area; thus improving the efficiency of the heating system and reducing operating costs as well as initial costs. The cycle of operation may be changed at any time through a three-position switch or ther mostat. In new design the amount of heat normally required can be greatly reduced when used in conjunction with these units. This model, with slight modifications, can also provide for sup ply of fresh air. MODEL ES either exhausts or provides for supply of fresh air merely by revers ing fan rotation through a three-posi tion switch. MODEL PRE is a typical power roof ventilator. This unit is equipped with butterfly dampers, which prevent heat loss in winter. Domes are optional. MODEL RS recirculates or supplies; also, any proportion of recirculated and supply air may be obtained by varying the opening between the venturi and jet thru a manually, pneumatically, or elec trically-operated mechanism. Filters are
optional. DELUXE MODEL ERS provides all four functions listed above. Filters are op tional. Raise the sleeve or fan section for recirculated or exhaust air and close it for supply. The sleeve or fan section is raised or lowered by: (1) gear ratio motor and rack assembly, controlled either by a three-position switch or ther mostat or (2) manual mechanism. This model available in sizes 31 and 38 only. NOTE: Cfm delivery of all models has been calculated on the basis of the static pressure through the unit. As the per centage of cfm delivery is reduced when fan blade rotation is reversed, specify on which cycle of operation the greater cfm is required. Units having larger capaci ties or special combinations of fan blades, motor sizes and speeds are avail able on special order.
m W, :< '%
-ft
6 Mk
#
%
$ I i
m
M
.te
A
1418
Genie-Air
Air System Equipment
Roof Ventilators
Dimensional Data
Dimensional Chart For All Genie-Air Models
Size
CD
DD
WBS
SSD
FSD
"U Diam."
15 16
34 19 15 15 22*$
17 18
38 21 17 17 25
19 20
38 23 19 19 26
21 22
42 25 21 21 28
25 26 45 31 25 25 33
31 32*$ 54 35 31 31 39
38 39*$ 59 44 38 38 48
Dimensions in Inches
Models ER, RS, ERS
Models ES and PRE
See charts below for A, B, A SL dimensions.
Type 1 and Type 2 roof jacks, as illustrated below, are furnished with all Genie-Airs
Any model may be installed in either type of roof jack; however type 2 is preferred
because of its simplicity of installation. In either case, CD dimension plus 2 in
must be held vertically clear downward through the full length of equipment be-
low the underside of roof. Unit sizes 31 and 38 require support in addition to the
roof jack; Support is to be furnished by others. See suggested method for framine
or support.
6
The Following Dimensions Are to Be Used With Type 1 Roof Jack:
Oeme Air
Size
15 17 19 21 25 31 38
Models ER, RS, and ERS
A *SL *B
27 27 37 29 27 38 29 27 38*$ 35 27 39*$ 39 27 43*$ 42 27 51*$ 44 28 52*$
Models PRE Models ES
A *B A *B 27 16 27 17 29 16 29 17 29 16 29 17 35 16 35 17 39 17 39 1742 18 42 17 44 19 44 18
TYPE 1 ROOF JACK--"RO" (roof jack opening-- inside dimensions) for unit sizes 15,17,19, 21 A 25 is 28 in.x 28 in.; size31 is 36in. x 36in.; size 38 is 42 in x 42 in.
TYPE 2 ROOF JACK--B2 (inside dimensions of roof jack base) for unit sizes 15,17,19 & 21 is 31 in.x31 in., CH (collar height above base) is 6 in., F2 (finish surface dimensions of curb) must be 30H x 30*$ in * B2 for unit sizes 25, 31 & 28 is 43 in.-x_43_in., CH is 8 in., F2 must be 42*$ in. x 42*$ in. All curbs must be 6 in. minimum cn high side of roof.
The Following Dimensions Are to Be Used With Type 2 Roof Jack:
GenieAir
Size
15 17 19. 21 25 31 38
Models ER, RS, and ERS
Model PRE
A SL *B A ' B
21 27 43 21 22 23 27 44 23 22 23 27 44*$ 23 22 29 27 45*$ 29 22 33 27 49*$ 33 23 36 27 57*4 36 24 38 28 58*$ 38 25
Model ES
A B
21 23 23. 23 23 23 29 23 33 24 36% 25 38 26
iieigni cut may JDe varied.
* Dimensions (in inches) Based on 6 in. Curb Height (High Side of Roof) But May Be Varied.
SUGGESTED METHODS FOR FRAMING OR SUPPORTING SIZES 31 & 38
Typical Installation With Steel Frame Support
Typical Installation With Wood or Steel Frame
Support
NOTE: On flat or slightly pitched roofs 14-gauge steel collar may be connected above roof decking with necessary support framing on underside of roof. NOTE: Conformance of installations with local agencies and governing codes is the responsibility of others.
SUGGESTED ELECTRICAL SWITCH WIRING USING 3-POLE DOUBLE-THROW SWITCH