Document 8OBEKbBkpwDankyyJYwqe0yD5
Local Exhaust System
exhaust volume of 50 cu ft for each pound of wood refuse handled
The arrester used to collect woodworking scrap is traditionally the cyclone It is ade quate for chips, shaper cuttings, boring scraps, sawdust, and other relatively large size par ticles Sanders release especially fine dust and unless it goes into an air stream which is already carrying chips and shavings from other types of machines, it is too fine to be trapped by the usual cyclone
The cyclone may be followed by a cloth collector which removes the fine dust and often allows the air to be recirculated
Cast iron machining
Dust from cast iron machining has been receiving an increasing amount of attention, not so much because of any health hazard, but because it is a distinct annoyance the operator's clothing and skin are coated with gray and rust-colored powder, and machinery, motors, and controls eventually require un due maintenance Higher machining speeds and multiple-operation machine tools have steadily raised the concentration of fine dust per unit of floor space
Usually, no effort is made to carry off the chips, although some will be caught The exhaust systems are aimed at removing the fine air-floated dust Fortunately, because of the small particle size of the dust, it can be brought into the hood by mass air movement, even though the actual air velocity is rela tively low
Hood designs vary according to the machine tool, the part being finished, and the opera tion performed Usually, small hoods with face velocities of 400 to 2000 fpm can be de signed, and placed most advantageously after watching the machining operation and ob serving the exact point of dust release
As always, the hood should be close to this point, and should surround it as much as possible On the other hand, it cannot inter fere too much with the operator's line of vision, movement of the machine tool parts, or the placing or removal of work At times it will be possible to enclose much of the work ing area, in which case the total rate of air flow can be set to assure an indraft through the remaining openings of 100 to 150 fpm Transparent plastic windows and doors allow the machinist to watch the work
With local hoods, and branch sizes of 4 to 6 m , exhausting 400 to 800 cfm will often be sufficient Many modem machines, how ever, require 8- or 10-in branches capable of handling 1500 or 2400 cfm Except where only a few isolated machines are to be hooded, central systems --as contrasted with unit col lectors -- seem to be preferred because of their lower maintenance and more uniform air flow
Oil mist
Oil mist is a problem m shops where oil is used as a coolant as rooms can become filled with an oil haze, floors soaked with oil present a slipping hazard, and condensation on walls and ceilings becomes a fire hazard
Hood sides must act as splash guards, be cause air flow alone will not arrest the oil thrown from the operation The hood must incorporate such splash guards, but still per mit the machine to be serviced and the opera tion observed when required A few manu facturers have provided their machine tools with plastic enclosures that meet these re quirements Although all should do so, too often the "built-m" hood is omitted
Ingenuity will show the way for attaching hoods to most machines, but all are different Usually, an exhaust volume of 400 to 600 cfm will provide the recommended 100 to 150 fpm indraft Sometimes, when considerable heat is generated or where the hooding fails in being a complete enclosure, 1000 to 1500 cfm must be exhausted Duct velocities of 2500 fpm are ample Duct joints should be tight to prevent oil leakage and ducts should be pitched to allow condensed oil to flow back to the machine or to a special collector
Electrostatic precipitators and wet (oilfilled) centrifugal collectors are sold as ar resters for oil mist exhaust systems To elimi nate ductwork, units small enough to mount directly on the machine are available
An additional bonus collection and reuse, of oil may offer considerable savings
Melting furnaces
The design of hoods for metallurgical melt ing furnaces depends on the type of furnace and the metal being melted The fumes may constitute a health hazard to the operator or a source of community air pollution
The tilting crucible furnace is often
886
\ /